Standards
Design to comply with EN54 Part 4 1996 and Part 2
1996
Electromagnetic Compatibility EN 50130-4 1996
Alarm Systems Part 4 EN50081-1 1992
EN61000-2-2-1994
Number of Zones
4(MF400) 2(MF200)
Number of alarm Lines
2
Mains Input Voltage
10%-15%
Standby Duration
24Hr
System operating Voltage
24Vdc Nominal
Indicators
Fire
High intensity red Light Emitting Indicators (LED)
Fault
High intensity yellow LED's
Power
High intensity green LED
Fault Indications
Zones
Open and short circuit, detector removed
Alarms
Open and short circuit
Power
Mains fail, battery fault, battery charge fault. All fuses are
monitored.
Earth Fault
Any Earth connection to low voltage system
System Fault
Micro contoller fault
End of Line Elements
Zones
22kohm
Alarms
22kohm
Maximum No of detectors per zone
20 (24V-30µA each)
Maximum Alarm Load
750mA 24Vdc
Auxiliary DC Output
32mA 24Vdc (Up to 100mA at the expense of Alarm Load)
Auxiliary Fault Output
24Vdc pull to 0V. Maximum 10mA
Remote Signal Output
24Vdc pull to 0V. Maximum 10mA
Standby Power source (Battery)
One Valve Regulated (Absorption Type) Lead Acid
12V Battery Recommenced replacement period 4
years. Capacity 4AH (24Hr Standby) 7AH
(72Hr standby) Max current draw is 3A resistive.
Battery Recharge Period
48Hrs
Terminal Connector Capacity
0.5mm
2
to 2.5mm
2
Dimensions
300mm X 300mm X 74mm
Panel Weight (Mass)
24Hr 4.8kg, 72Hr 6.0Kg
Panel operating temperature
-5°C to +40°C Humidity 75% (Non Condensing)
PAGE 11
TECHNICAL SPEC