47
S280-77-4
!
SAFETY
FOR LIFE
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
134
1
0
YES
1-2-3-4
1
--
High-Current Trip - Phase
0
(Active Trip Number)
134
1
0
YES
1-2-3-4
1
--
High-Current Trip - Ground
0
(Active Trip Number)
•
Indicates on which trip operation High-Current Trip is
active.
•
Trip operations, on which High-Current Trip is active,
are customer selectable, via the keyboard, for any
combination in sequence (i.e., select 3, 4; or 1 only,
2 only; or 1, 2, 3, 4, etc.) .
•
Use the PHASE/GROUND key to examine phase or
ground.
High-Current Trip (cont’d)
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
133
1
0
YES
9
1
--
High-Current Trip - Phase (cycles)
1
(Trip Time Delay)
133
1
0
YES
9
1
--
High-Current Trip - Ground (cycles)
1
(Trip Time Delay)
•
Time delays are selectable from 1 to 9 cycles, in
increments of 1 cycle, based on 60 Hz. For 50 Hz
systems, multiply the number of cycles by 0.83.
•
The high-current trip time delay should be set faster
than the normal time current curve. If the high-current
trip is set slower, actual timings will be faster than
the high-current trip time programmed.
•
Use the PHASE/GROUND key to examine phase or
ground.