Cooper CFDAU30 Installation And Maintenance Manual Download Page 16

 

PR000-00-527-01 PINSTCFDAU30 

 

Page 16 of 18

 

Page Input

 

The paging input is an unmonitored input, at line level and the PTT line is connected to 5V to operate. 

Once operated paging will mute the music input, once paging is complete the music will return gently. 

The Ptt line goes to 5V when either the Fireman’s microphone or message generators are in use, the 

Cooper desk microphone uses this signal to light the busy LED on the microphone. 

The UNDM1 provides a complete solution to paging applications, and contains a chime generator, 

microphone pre-amplifier and signal limiter to prevent clipping of the CFDAU30 and corrects for poor 

microphone technique. The UNDM1 provides busy indication and first come first served logic for 

cascading microphones. 

Microphone connections:- 

 

 

Using 3

rd

 Party Microphones. 

Third party microphones can be used with CFDAU30 as long as they can provide a volt free Ptt contact, 

and a balanced line level (0dBV) audio output. A 24V 100mA feed is available on the page connector to 

provide power to an external microphone pre-amplifier to boost signals from microphone to line level.  

Note: the Cooper CFDAU30 does not contain a chime generator, and the microphone used must 

provide this if required. 

 

The level of the paging microphone can be independently adjusted using the front panel recessed 

control marked “PAGE” 

Summary of Contents for CFDAU30

Page 1: ...CFDAU30 Voice Alarm System Installation and Maintenance Manual Cooper Lighting and Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL 44 0 1302 321541 FAX 44 0 1302 303220...

Page 2: ...ommended for all public buildings and multi story buildings over four floors by BS5588 In public buildings it s not possible to fire drill the public as they visit the premises infrequently so systems...

Page 3: ...e system designed to be used by the controlling officer 2 Message Generator this has three messages all messages latch until reset from either the front panel recessed button or from the cancel button...

Page 4: ...s follows Weekly Broadcast the test message to all zones and check speaker operation microphones should be checked for operation if fitted record results in the site log Monthly Trigger the fire alarm...

Page 5: ...e is playing Green for test Yellow for the Alert Message and RED for the Evacuate message Paging Lights green when the paging microphone is in use Music Lights green when the music channel is open no...

Page 6: ...nits are distributed around a site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a un...

Page 7: ...line Resistors e Crimped Battery Link Lead f Black jumper header to Enable Fire Microphone Monitoring Using the HEX key supplied remove the front cover Verify the following items are present 1 2 off...

Page 8: ...ved fill the hole with a good quality cable gland 18 knockouts are provided 8 on the top face from left to right Speaker Network A Speaker Network B Fault Fire alarm Interface Fire Microphone connecti...

Page 9: ...ed for the fire alarm interface loudspeakers fireman s microphone paging background music equipment and slave amplifiers please refer to the relevant sections later in this manual Note that correct ca...

Page 10: ...and 1 hour operation 2 number 12V 17AH batteries are required these will need to be fitted in an external battery enclosure the monitored charger in the Cooper CFDAU30 is capable of charging and monit...

Page 11: ...le speakers for CFDAU30 MUST have a thermal fuse to disconnect the speaker if it is in the area in fire and a DC blocking capacitor fitted typically the capacitor is 2 2uF 250V DC The wiring goes thro...

Page 12: ...ction point see earlier in this manual preferred types are screened soft skin cables such as FP200 although MICC can be used Cable Length Chart The following table shows the maximum cable run to achie...

Page 13: ...the top on the Cooper CFDAU30 the Au pin is at the bottom of the block The CFDAU30 is shipped as standard with the monitoring of the Fire Microphone DISABLED to enable the monitoring fit the jumper su...

Page 14: ...n isolator and can be hard or soft addressed by the Cooper addressable panels CFDAU30 is fully monitored and controlled by any Cooper Fire addressable Fire Panels NOTE MESSAGES WILL ALWAYS PLAY TO THE...

Page 15: ...messages can be independently adjusted using the front panel recessed control marked MESSAGES the messages Override paging and music when operated the level of the individual messages can be altered...

Page 16: ...limiter to prevent clipping of the CFDAU30 and corrects for poor microphone technique The UNDM1 provides busy indication and first come first served logic for cascading microphones Microphone connect...

Page 17: ...ted when mains fails in line with BS5839pt8 to preserve battery life The level of the paging microphone can be independently adjusted using the front panel recessed control marked MUSIC NOTE If music...

Page 18: ...E Sensitivity 6dBV to 4dBV Ptt Type 5V to access Power 24V nominal 100mA self resetting fuse Fire Interface Inputs 3 off isolated 12V to 33V Alert Evacuate Reset Outputs 1 Relay open on fault 30V 1A M...