Cooper CFDAU30 Installation And Maintenance Manual Download Page 11

 

PR000-00-527-01 PINSTCFDAU30 

 

Page 11 of 18

 

Speaker Circuits 

Cooper has two speaker Circuits, A & B. to fully comply with the requirements of EN60849 the speakers 

should be wired in an interleaved pattern, so if one circuit fails messages can still be heard in the areas 

covered (note it is accepted practice to only place one speaker in an office, as long as the connecting 

corridor is on the other circuit). 

Each output of Cooper can support 30W of speakers, this is typically five 6W speakers, ten 3W 

speakers or twenty 1.5W Speakers. 

6W speakers are generally fitted in noisy offices or reception areas, 3W speakers are usually used in 

corridors, and 1.5W speakers in small rooms or open plan offices. 

 

Caution Speaker circuits carry 100V AC 

Disconnect before servicing to prevent Shock hazard. 

Speaker Circuits on CFDAU30 are DC monitored

Suitable speakers for CFDAU30 MUST have a thermal fuse to disconnect the speaker if it is 

in the area in fire and a DC blocking capacitor fitted, typically the capacitor is 2.2uF 250V DC. 

 

The wiring goes through each speaker, and in the last speaker the end of line resistor. Each circuit can 

have 2 spurs, the CFDAU30 is provided with two end of line resistors per circuit, both must be fitted to 

avoid faults being shown on the panel. If only one spur is used per circuit, one resistor resides in the 

panel; one resistor resides in the last speaker on the circuit. 

 

Before connecting the speaker lines to CFDAU30 count the number of speakers and note the tapping 

they are set at, (most manufacturers will supply speakers at the maximum tapping, or at the half power 

tapping) this value should not exceed the 30W rating of the Cooper CFDAU30 for a single circuit. 

It is desirable to have an impedance meter available (this measures the AC load that the Cooper 

CFDAU30 sees). The measurement on the impedance meter should not be lower than 330 Ohms at 

1KHz. 

Summary of Contents for CFDAU30

Page 1: ...CFDAU30 Voice Alarm System Installation and Maintenance Manual Cooper Lighting and Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL 44 0 1302 321541 FAX 44 0 1302 303220...

Page 2: ...ommended for all public buildings and multi story buildings over four floors by BS5588 In public buildings it s not possible to fire drill the public as they visit the premises infrequently so systems...

Page 3: ...e system designed to be used by the controlling officer 2 Message Generator this has three messages all messages latch until reset from either the front panel recessed button or from the cancel button...

Page 4: ...s follows Weekly Broadcast the test message to all zones and check speaker operation microphones should be checked for operation if fitted record results in the site log Monthly Trigger the fire alarm...

Page 5: ...e is playing Green for test Yellow for the Alert Message and RED for the Evacuate message Paging Lights green when the paging microphone is in use Music Lights green when the music channel is open no...

Page 6: ...nits are distributed around a site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a un...

Page 7: ...line Resistors e Crimped Battery Link Lead f Black jumper header to Enable Fire Microphone Monitoring Using the HEX key supplied remove the front cover Verify the following items are present 1 2 off...

Page 8: ...ved fill the hole with a good quality cable gland 18 knockouts are provided 8 on the top face from left to right Speaker Network A Speaker Network B Fault Fire alarm Interface Fire Microphone connecti...

Page 9: ...ed for the fire alarm interface loudspeakers fireman s microphone paging background music equipment and slave amplifiers please refer to the relevant sections later in this manual Note that correct ca...

Page 10: ...and 1 hour operation 2 number 12V 17AH batteries are required these will need to be fitted in an external battery enclosure the monitored charger in the Cooper CFDAU30 is capable of charging and monit...

Page 11: ...le speakers for CFDAU30 MUST have a thermal fuse to disconnect the speaker if it is in the area in fire and a DC blocking capacitor fitted typically the capacitor is 2 2uF 250V DC The wiring goes thro...

Page 12: ...ction point see earlier in this manual preferred types are screened soft skin cables such as FP200 although MICC can be used Cable Length Chart The following table shows the maximum cable run to achie...

Page 13: ...the top on the Cooper CFDAU30 the Au pin is at the bottom of the block The CFDAU30 is shipped as standard with the monitoring of the Fire Microphone DISABLED to enable the monitoring fit the jumper su...

Page 14: ...n isolator and can be hard or soft addressed by the Cooper addressable panels CFDAU30 is fully monitored and controlled by any Cooper Fire addressable Fire Panels NOTE MESSAGES WILL ALWAYS PLAY TO THE...

Page 15: ...messages can be independently adjusted using the front panel recessed control marked MESSAGES the messages Override paging and music when operated the level of the individual messages can be altered...

Page 16: ...limiter to prevent clipping of the CFDAU30 and corrects for poor microphone technique The UNDM1 provides busy indication and first come first served logic for cascading microphones Microphone connect...

Page 17: ...ted when mains fails in line with BS5839pt8 to preserve battery life The level of the paging microphone can be independently adjusted using the front panel recessed control marked MUSIC NOTE If music...

Page 18: ...E Sensitivity 6dBV to 4dBV Ptt Type 5V to access Power 24V nominal 100mA self resetting fuse Fire Interface Inputs 3 off isolated 12V to 33V Alert Evacuate Reset Outputs 1 Relay open on fault 30V 1A M...

Reviews: