Specification

Rated Power: 

8, 15 or 25 watts RMS continuous (at 77°F).

Certification: 

UL listed for USA and Canada: 

 

 

– Class I, Div 2, Groups A-D 

– Class I, Zones 1, AExd IIC T4.

 

 

– Class II, Div 2, Groups F & G

 

ATEX approved:  EN50014, 18, 19.

 

No. BAS00ATEX2097X.  EExd 11C T41/T5

 

Cert. No. BAS00ATEX2098X.  EExd 11C  T41/T5

 

Zones 1 not for use in atmospheres containing carbon disulphide

Material: 

Body & horn in anti-static, UV stable, glass reinforced polyester.

 

Swivel bracket in stainless steel.

 

Captive cover screws in stainless steel.

Finish: 

Body and horn, natural black or epoxy paint coated to client’s 

color require-

ments.

Output: 

97 dBA at 1 Watt at 10 feet

 

109 dBA at 25 Watts at 10 feet 

 

Measured in accordance with IEC 268.

Weight: 

11lb./

5.0kg approx.

Certified Temperature: 

–67°F to +158°F (55°C to +70°C)

Ingress Protection: 

NEMA 4x & 6, IP66 & IP67.

Frequency Range: 

400Hz to 8kHz.

Voice Coil Impedence: 

8 ohms.

Transformer: 

Used  to  vary  the  rated  power  by  selecting  different  tappings  (see  table  below).

 

  Transformer 

Power

 

 

Tappings 

25W 

15W 

8W

 

 

1:2 

25.0* 

15.0* 

8.0*

 

 

2:3 

12.5* 

7.5* 

4.0*

 

 

3:4 

6.0 

5.0 

2.0

 

 

1:3 

4.0 

4.0 

1.5

 

 

2:4 

2.0* 

2.0* 

0.7*

 

 

1:4 

1.0 

0.8 

0.4

Transformer Options:
i)  Standard Tapping: (4 x 2) terminal tap change (8 terminals).
ii)  Optional Tapping:  4 terminal tap change with 2 terminals (5 & 6), directly connected 

to driver (8 ohms).

Other tappings & driver impedances available on request.
Terminals: 

8 x 14AWG

Mounting: 

Bracket with ratchet facility.

Labels: 

Duty and tag labels optional.

Cable Entries: 

2 x 

1

/

2

" NPT.

DB4

Type 

 

Code

UL listed   

UL

Transformer 

Code

Yes 

  X*

None 

N

*Std 100V
  Other values available,
  specify voltage.

 

Max. Rated Power 

Certification 

Transformer 

Labels 

Entries 

Color

Label 

Code

Duty 

D*

Tag 

T*

None 

*Please specify wording

Color 

Code

Natural Black 

Red 

Special 

S*

*Please specify

Power 

Code

  8 watt 

  8

15 watt 

15

25 watt 

25

Entries 

Code

1 x ½" NPT  

1C

2 x ½" NPT  

2C

Configuration Options:

Polar plot (1W/1m) for 25 watt version.

Polar plot and frequency response curves for other speakers are available upon request.

Transformer Tappings

WE ENCOURAGE AND SUPPORT NICET CERTIFICATION

3 YEAR WARRANTY

Made in USA

273 Branchport Avenue

Long Branch, NJ 07740

Phone:  (800) 631-2148 

Fax:  (732) 222-2588

www.cooperwheelock.com

DB4 04/07

Standard Models

Series

Model Number

Order Code

Decription

DB4 DB425ULXN2CR 109208-001 Speaker, 25 Watt, Transformer, Red Finish

DB4 DB415ULXN2CR 109208-002 Speaker, 15 Watt, Transformer, Red Finish

UL

To specify certified plug, suffix ap-
propriate code with 'P'.  e.g. 2CP is 2 
x 1/2" NPT entries with one certified 
plug

*Include blocking capacitor for DC supervision of field wiring

Reviews: