background image

P82623 F 

Sheet 5 of 6 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  

If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage 
the product. 
 
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Notification recommends use of the largest 
backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and 
minimum stress on the product from wiring. 

FLUSH (4" BOX)

A

10

4

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

 SCREW COVERS

#8-32 SCREWS

4" SQ. X 2-1/8"

DEEP BACKBOX

B

FLUSH (2-GANG BOX)

2-GANG x 2-1/2"

DEEP BACKBOX

AWG #18  AWG #16  AWG #14  AWG #12

10

8

8

4

MAXIMUM NUMBER OF CONDUCTORS

#6-32 SCREWS

SCREW COVERS

 

C

SURFACE (INDOOR/OUTDOOR)

#8-18 SCREWS

INDOOR/OUTDOOR

WOOD

 SCREWS

SCREW COVERS

12

12

12

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX IOB

D

CONCEALED CONDUIT MOUNTING

EXISTING

BOX 

#8-18 SCREWS

INDOOR/OUTDOOR

SCREW COVERS

12

12

12

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

BACKBOX IOB

 

EXISTING FSB

                 BOX

RETROFIT PLATE MOUNTING

E

12

12

12

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

SCREW COVERS

#8-32 SCREWS

RETROFIT

PLATE

DBB OR 4" SQ. X 2-1/8"
DEEP BACKBOX

ISP EXTENDER

SURFACE OR SEMI-FLUSH (4" X 2-1/8" BOX)

F

12

8

10

12

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

SCREW COVERS

#8-32 SCREWS

 

SURFACE OR SEMI-FLUSH (4" X 1-1/2" BOX)

G

#8-32 SCREWS

SCREW COVERS

MAXIMUM NUMBER OF CONDUCTORS

AWG #18  AWG #16  AWG #14  AWG #12

8

8

4

10

ISP EXTENDER

DEEP BACKBOX

DBB OR 4" SQ. X 2-1/8"

 

 

AMT Appliances can be wall or ceiling mounted. 

 

Summary of Contents for AMT-12/24

Page 1: ...letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS NOTE All Canadian installations should b...

Page 2: ...THE SYSTEM S PRIMARY AND SECONDARY POWER SOURCES NAC CIRCUITS OR WHEELOCK S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND...

Page 3: ... SOUND OUTPUT LEVEL THAT IS BELOW THE MINIMUM CODE REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS STEP 2 Set desired alarm tone as follows refer to Figure 3 and Table 5 AMT Multitone Appliances are field set for any one of eight groups of self prioritized tones by setting a four position switch SW1 as shown in Fig...

Page 4: ...room prior to installing backboxes and conduit 1 AMT Multitone Appliances can be flush mounted to a standard 4 inch square by 2 1 8 inch deep electrical box Figure A or a standard 2 gang by 2 1 2 inch minimum deep electrical box Figure B 2 Select largest backbox shown in Mounting Options where possible to provide additional wiring room for easy installation 3 Conduit entrance to backboxes should b...

Page 5: ...G BOX 2 GANG x 2 1 2 DEEP BACKBOX AWG 18 AWG 16 AWG 14 AWG 12 10 8 8 4 MAXIMUM NUMBER OF CONDUCTORS 6 32 SCREWS SCREW COVERS C SURFACE INDOOR OUTDOOR 8 18 SCREWS INDOOR OUTDOOR WOOD SCREWS SCREW COVERS 12 12 12 12 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS BACKBOX IOB D CONCEALED CONDUIT MOUNTING EXISTING BOX 8 18 SCREWS INDOOR OUTDOOR SCREW COVERS 12 12 12 12 AWG 18 AWG 16 AWG 14 AW...

Page 6: ...ision reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between the equipment and receiver 3 Connect the equipment into an outlet on a circuit different from that to which the receiver is connected and 4 Consul...

Reviews: