Cooper Notification 109919 Installation Instructions Manual Download Page 2

 

 

    P84557 

 

 

          Sheet 2 of 14 

 
Two SP4-RMX modules can be ganged together when connecting them to an SP40S panel.  This provides a maximum of six remote 
microphones providing “All Call” for the entire system.  One SP4-RMX can be connected to each audio booster providing three non-
alarm/general page remote microphones for that audio booster audio output.  Each SP4-RMX provides a line level, 600 Ohm auxiliary 
audio input. 
 
There are two configurations for the Priority levels of the remote microphones can be set. One configuration sets the priorities as: 
RM1, priority 1; RM2, priority 2; and RM3, priority 3.  For instance, if RM3 is broadcasting, RM1 or RM2 can override RM3.  The 
other configuration allows the first remote microphone to broadcast to have the top priority until it completes its message.  The remote 
microphones operate on a first in – first out basis. 
 

TECHNICAL SPECIFICATIONS: 

 

Electrical 

 
 

   

    Input 

Voltage 

      24 

VDC 

 

 

   

    Input 

Current 

      52mA 

max RM 

Page 

 

  

           62mA 

max 

Standby 

 

 

 

 

 

 

Auxiliary Audio Input      1Vrms 

 
 

   

    Min. 

Ground 

Fault:    20k 

Ohms 

 
 

 

 

 

 

Relay Ratings   

        K1 and K3:    2A, 30Vdc, 1pF 

 

 

 

 

 

 

 

 

 

 

        K2, K4, K5, and K6:    1A, 30Vdc, 1pF 

 
 

 

 

 

 

Remote Microphone  

  

 

 

 

(SPRM) 

 

Mechanical 

 

 

 

Dimensions (H x W x D)      13.0" x 7.6" x 2.15", 33cm x 19.4cm x 5.4cm 

 

    Weight 

           3.8 

pounds, 

1.7kg 

 

    Enclosure 

         0.050" 

Steel 

 

 

 

Finish   

 

 

          Black 

 

    Mounting 

         Indoor 

Surface 

Mount 

                   Top 

and 

Bottom 

Wiring 

Entry 

 

Environmental 

 

 

 

(Meets UL requirements) 

 

    Operating 

Temperature 

   32° 

to 

120.2

 

° F (0° to +49° C) 

 

 

 

Storage Temperature         -4° to 158° F (-20° to 70° C) 

 

    Humidity          85±5% 

30±2° 

Non-condensing 

 

INSTALLATION: 

 

The lives of people depend upon your safe installation of the SP4-RMX.  Please read, understand and follow the specific 
installation instructions set forth below to avoid damage to the SP4-RMX and equipment connected to it.  Installation should be 
conducted only by qualified persons in accordance with procedures in this manual. 

 

WARNING:    SHUT OFF ALL POWER BEFORE STARTING THE INSTALLATION.  ELECTRICAL SHOCK CAN 

CAUSE DEATH OR SERIOUS INJURY. 

Summary of Contents for 109919

Page 1: ...optional Remote Microphones SPRM or SPRM GP to three The PCB assembly is mounted in an enclosure READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters SP40S Panel 24VDC 24VDC Audio Out Audio Out Aux In Aux In SP4 RMX MIC 1 MIC 2 MIC 3 SP4 RMX MIC 1 MIC 2 MIC 3 Audio Out Audio Booster ...

Page 2: ...CHNICAL SPECIFICATIONS Electrical Input Voltage 24 VDC Input Current 52mA max RM Page 62mA max Standby Auxiliary Audio Input 1Vrms Min Ground Fault 20k Ohms Relay Ratings K1 and K3 2A 30Vdc 1pF K2 K4 K5 and K6 1A 30Vdc 1pF Remote Microphone SPRM Mechanical Dimensions H x W x D 13 0 x 7 6 x 2 15 33cm x 19 4cm x 5 4cm Weight 3 8 pounds 1 7kg Enclosure 0 050 Steel Finish Black Mounting Indoor Surface...

Page 3: ...fully unpack the SP4 RMX and make sure each item described on the packing slip is present and undamaged 3 Mount the SP4 RMX in the desired location as described in the Mounting section 4 Mount any additional wiring boxes or junction boxes needed to interconnect field wiring 5 Connect conduit fittings or bushings as needed using knockouts provided on the top and bottom of the SP4 RMX units see Figu...

Page 4: ...f the shield must be connected at the Safepath panel or SP4 RMX enclosure Maximum Length 20 Feet Restrictions All wiring between SP40S or Audio Booster and SP4 RMX must be run in conduit and within the same room When used with the SPB 160 SPB 80 4 or SPB320 the RMX must be located in the same room Between each SPRM and SP4 RMX Cable Size 14 22 AWG Shielded The shield must be connected only at the ...

Page 5: ...P84557 F Sheet 5 of 14 6 00 CONDUITKNOCKOUTS 2 PLACES BOTHENDS 11 00 MOUNTINGHOLES MOUNTINGHOLES GROUND TERMINALS Figure 2 SP4 RMX Mounting NOTE Drawing is not to scale ...

Page 6: ... ALL CONNECTIONS BETWEEN SP40S AND RMX ARE SUPERVISED THESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20 FT OF CONDUIT AND WITHIN THE SAME ROOM ALL CONNECTIONS BETWEEN RMX AND REMOTE MICS ARE SUPERVISED Figure 3 Wiring Diagram with up to 3 Remote Microphones to an SP40S NOTE If the SP4 RMX is configured for less than 3 Remote Microphones the DIP switch for the unused Remote Microphone port SW3 must ...

Page 7: ...ed SP4 RMX Modules AUX IN CC NAC SP40S 24 VDC 10K EOLR 10K EOLR 10K EOLR 10K EOLR S3 S2 S3 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 Figure 4 Two Ganged SP4 RMX Modules Set switches and jumpers on the SP40S as follows Set jumper J4 to 1V position Set SW6 to the contact closure CC position Remove jumper JP4 to enable supervi...

Page 8: ... MORE THAN 20FT OF CONDUIT AND WITHIN THE SAME ROOM REFER TO FIGURE 3 FOR SPRM GP CONNEC TIONS ALL CONNEC TIONS ARE SUPERVIS ED SP40S SP4 RMX SPB 10K OHM EOLR 10K OHM EOLR AUD OUT 24V OUT SPB SUP ALM NC NO C NC NO C TB4 TB1 TB6 24V OUT 24V OUT EXP OUT TB7 Figure 5 SP4 RMX Connections Diagram When Using an SPB ...

Page 9: ...SPRM connected Insure the corresponding switch is OFF for any SPRM inputs not used Set switch S1 on SW2 to the desired position according to Table 1 Set S2 to ON Switch S3 to the ON position Set switches and jumpers on the SPB as follows Set SW3 to the CC contact closure position Remove jumper JP8 to enable supervision of the CC input wiring Move jumper J4 to the 1V position FIELD WIRING CHECKOUT ...

Page 10: ...es of the SP40S and SPB audio boosters In SP40 mode each SP4 RMX provides the capability of connecting and supervising up to three SPRM emergency remote microphone modules In SPB mode the SPRM GP General Page Remote Microphones must be used These microphones are for general pages only These pages are non emergency messages Any trouble condition on the SPRM modules input and output wiring will ligh...

Page 11: ...he SPB audio booster modules the SP40S AUDIO OUT is connected to the SP4 RMX AUX IN and the SP4 RMX AUDIO OUT is connected to the SPB AUDIO IN This means that the priority level of the SPRM GP modules are after the digital voice messages on the SP40S and are considered non alarm conditions Priority Levels on SPB with SP4 RMX Connected Table 3 Priority Levels SP4 RMX to SPB Priority Source Remarks ...

Page 12: ...tion Use the following troubleshooting table to locate the trouble area Table 4 Trouble LED Indicators D30 SYS PWR D29 SYS TRB LED Indicator Remarks ON OFF Normal OFF OFF 24VDC not applied Check PWR IN terminals If 24VDC is present then SP4 RMS module is defective Replace ON ON RM CC input shorted in excess of 2 1 2 minutes or Defective SP4 RMX module D22 WIRE Open AUD OUT circuit open or 10K Ohm ...

Page 13: ... 13 of 14 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 AUX TRB ALM TRB RM1 TRB WIRE SHT WIRE OPEN SYS TRB SYS PWR D24 D25 D26 D27 D28 D23 D22 D29 D30 RM2 TRB RM3 TRB Figure 6 SP4 RMX PC Board Layout ...

Page 14: ...ITABLE FOR THE USER S PURPOSES OR WHETHER IT WILL ACHIEVE THE USER S INTENDED RESULTS THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLIACATION IMPROPER SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND SELLER S CONTROL SELLER DOES NOT WARRANT THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORM...

Reviews: