Cable & Wiring
Only the cable types listed below are allowable for loop connections.
DRAKA Cables (Part Number 910234)
Technical Specification
When choosing your preferred cable type, you must take note of the following cable and
wiring requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 1KM
3. Multicore cable should not be used for detector wiring.
4.
The screen or drain wire of the network cable should not be considered as a
safety earth.
5. Screen continuity must be maintained throughout the entire network circuit
including at each junction point.
6. Where the network cable passes between buildings, screen continuity should not
be maintained from building to building. A booster device must however be used
irrespective of cable length and should be fitted at a suitable point in the link
between buildings. The cable screen should be connected to the earth of one
panel in each building.
10
Cabling Application
Applicable Standards
Circuit integrity Structured
Wiring
Alarm/Lighting Cable Part Number 910234
Patent Protected Design
ISO/IEC 11801:95
EN 50173:95
Fire Propagation Test : UL 1581 VW1;
IEC60332.3;
Cct Integrity tests: IEC 60331; BS5839: 2002
Cable construction
Conductor
Insulator Material
Number of Twisted Pairs
Glass Tape
Screen Material
Braid
Sheath Material
Bare Cu
Wire
PE/Sil Rbr
1
Mica
Ali/Mylar
TCWB
OHLS
Outside Diameter of Conductor
Outside Diameter of Insulation
Outside Diameter of Sheath
Weight OHLS
Sheath Colour
(OEM Specified)
Sheath Printing
(up to 24
characters)
0.65 mm
1.70 mm
5.3 mm
15.8 kg/km
Various
Batch No. &
Metre marking
Cable Properties
Electrical Characteristics @ 20 ºC
Min. Installation Bend Radius
Min. Installed Bending Radius
Max. Installation Tension
Max. Installed Tension
InstTemp. Range Installed
Operating Temp. Range
8 x Dia
4 x Dia
50N
Zero
0 to 0ºC
-20 to 60ºC
Return Loss Rl
Characteristic impedance
@
10MHz
DC Conductor Loop Resistance
Max. Resistance unbalance
Nominal Velocity of Propagation
Insulation Resistance
(500V)
300/500v rated
>IEC dB
100±5
Ù
30 Ù/100m
?2%
57%
?5000
MÙ.km
Fire tests BS 5839: 2002 & IEC60331
Continued Data Operation @ 950
°
Smoke test
Approvals
>3 Hours
passed
passed
Summary of Contents for CTPR3000
Page 4: ...Contents ...
Page 5: ...Contents Contents Page ...
Page 6: ...System Installation and Design Section 1 6 ...
Page 16: ...Commissioning Section 2 16 ...
Page 18: ...Panel Controls Indicators Section 3 18 ...
Page 50: ...Appendix Section 4 50 ...