Cooper Crouse-Hinds CHB 310-7 Instructions Manual Download Page 22

                                                                 Cooper Industries Inc. 
                                                                Crouse-Hinds Division                                                              IF 1551 

 

                                                                      PO Box 4999,                                                                     Rev 1 
                                                         Syracuse, New York 13221  •  U.S.A.                                            New 01/08 
                                                        Copyright© 2007, Cooper Industries, Inc. 

 

Section 3 — Maintenance 
and Troubleshooting 

Maintenance 

This equipment requires no scheduled 
maintenance although the circuit boards 
should be kept free of accumulated dust. 
Brush as necessary. 

Do not use compressed air for cleaning 
this equipment. 

Clean the printed circuit board connectors 
when necessary — use a contact cleaner 
recommended for electronic circuit 
components only. Do not polish with any 
kind of abrasive material. 

Circuit boards, when not installed in the 
equipment, should be kept in antistatic 
bags or containers. 

Troubleshooting 

Good observation of the behavior of the 
system often leads directly to a faulty 
component or other abnormal condition. 
Many abnormal symptoms observed at the 
controller may originate at some other part 
of the system, such as the photoelectric 
control units or the beacons. 

The following tables may help locate the 
cause of a problem: Table 3-1 is a list of 
observable symptoms; Table 3-2 relates 
symptoms to possible causes. 

Troubleshooting Hints 

Failing to Switch State in AUTO 
Mode 

The PEC ALARM should be on if the 
photocell failed to switch state. If possible, 
swap the photocell with one known to be 
operative. 

Switch the Mode Selector Switch through 
the manual modes and see if the structure 

lights follow the intensity indicated by the 
switch position. It they do, the trouble is 
likely the photocell. Note that some lights 
may be difficult to see in bright daylight. 

Erratic or Confused Tower or 
Structure Light Operation 

Nearby radio transmitters or radar may 
cause radio frequency interference on 
control and monitor lines or within the 
lights or controller. Also, check power line 
phasing on 3-phase power systems. 

Try swapping the PCB100 Control Board 
with a PCB100 Control Board known to 
be in good condition. 

Beacons 

If any beacon is not flashing in the correct 
mode or is out of sync with its position or 
other beacons, check the communication 
cable to that beacon. Check that the sync 
LED on the PCB1 board is flashing once 
every 1.5 seconds (non-catenary), 
matching the output of the controller sync. 

Check that the DIP switches on PCB100 
conform to the setup of the structure 
lights. 

LED Displays 

Look at and analyze the LED displays on 
the front panel. LEDs indicate manual 
operating modes when you use the Mode 
Selector Switch. LEDs in the Tier/Beacon 
Display Window indicate failed beacons. 

The Display switch on PCB100 shows 
previously failed beacons in the 
Tier/Beacon Display Window. The Clear 
switch on PCB100 resets these stored 
failures. 

 

Summary of Contents for CHB 310-7

Page 1: ...rademarks and product names mentioned are properties of their respective companies and are recognized and acknowledged as such by Cooper Crouse Hinds Applicable Specifications This equipment meets or...

Page 2: ...r While every effort has been made to ensure that the information in this manual is complete accurate and up to date Cooper Crouse Hinds assumes no liability for damages resulting from any errors or o...

Page 3: ...itry while the equipment is operating Do not change components or make adjustments inside the equipment with power on Dangerous Voltages Can Persist with Power Disconnected Under certain conditions da...

Page 4: ...hing Live Circuits 3 Dangerous Voltages Can Persist with Power Disconnected 3 Do Not Depend on Interlocks 3 Section 1 CHC 140 1 Controller Introduction and Operation 7 Controller 7 Options 7 Photocell...

Page 5: ...oting 22 Troubleshooting Hints 22 Failing to Switch State in AUTO Mode 22 Erratic or Confused Tower or Structure Light Operation 22 Beacons 22 LED Displays 22 Checkout Procedure 24 Photocell Maintenan...

Page 6: ...rs 12 Figure 1 3 Beacon Programming Switches 13 Figure 2 1 CHC 140 1R Controller Mounting and Outline 16 Figure 2 2 CHC 140 1W Controller Mounting and Outline 17 Figure 2 3 PEC 510 Photocell Mounting...

Page 7: ...The CHC 140 1R fits in a standard 19 inch equipment rack System connections are made at a terminal block at the rear of the unit The CHC 140 1W is in an enclosure that allows the controller to be wall...

Page 8: ...osition sets all the LEDs to green Fuses The F1 fuse is a 1 ampere fuse in the primary power circuit PCB100 Control Board Switches Display and Clear Buttons on PCB100 Green glowing LEDs correspond to...

Page 9: ...L Cut to allow dual system operation it inhibits white light flashing at night A dual system is one that flashes only white lights during the day and flashes only red lights at night Dual systems may...

Page 10: ...are observed to flash simultaneously This may cause some of the Tier and Beacon Display LEDs to temporarily switch to RED Failure Detection Monitoring provides an alarm if a beacon becomes inoperativ...

Page 11: ...allowing you to manually synchronize with another system having its own independent controller Table 1 2 Front Panel Controls Fail Conf Display Switch Position Function FAIL Applies uniformly a fail s...

Page 12: ...ON OFF ON DAYINHIBIT FAILCLOSE J507 1 1 1 1 1 1 1 6 6 6 6 6 2 2 PEC TWI PEC NITE GND CTRL MON SR SD ALARM COM ALARM NO GND 24V LOW 24V HIGH COM NO NC COM NO NC PEC ALARM DAY MODE TWI MODE NITE MODE N...

Page 13: ...4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc FRONT OF UNIT TIERS ON OFF BEACON 1 BEACON 2 BEACON 3 BEACON 4 ON OFF ON OFF OFF ON 1 2 3 4 5 7 6 SECTION OF PCB...

Page 14: ...oper performance Place the unit at an adequate distance from a powerful RF radiator Controller Wiring Figure 2 5 shows the controller and photocell wiring in a typical installation Only general inform...

Page 15: ...tocell Be certain that these connections are correct before applying power otherwise equipment damage will result See Figure 2 6 Installation Checklist Controller Checklist Consult the installation dr...

Page 16: ...Cooper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 2 1 CHC 140 1R Controller Mounting and Outline...

Page 17: ...Cooper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 2 2 CHC 140 1W Controller Mounting and Outline...

Page 18: ...New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc 0 33 8 38 2 275 57 8 2 58 65 5 0 125 3 175 HEX 1 0 25 4 3 06 77 7 1 2 NPT 0 10 2 54 NOTE ALL DIMENSIONS ARE IN INCHES MILLIMETERS 1...

Page 19: ...Cooper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 2 4 CHC 140 1 Panel Connections...

Page 20: ...Cooper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 2 5 Typical Installation Wiring...

Page 21: ...Cooper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 2 6 CHC 140 Internal Wiring...

Page 22: ...led to switch state If possible swap the photocell with one known to be operative Switch the Mode Selector Switch through the manual modes and see if the structure lights follow the intensity indicate...

Page 23: ...ies Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Table 3 1 Major Troubleshooting Symptoms Table 3 1 Major Troublesho...

Page 24: ...UTO Perform the remaining steps with the CONTROL and MONITOR wires attached for normal operation and verify that the programming switches see Programming on Page 1 2 are set correctly 7 All LED indica...

Page 25: ...Use a nut driver Take care to prevent scratching the paint while removing the nuts 4 Behind the front panel remove the four screws holding the display panel board to the front panel Replacement Revers...

Page 26: ...Industries Inc Section 4 Recommended Spare Replaceable Parts Customer Service Customer Service 1 866 764 5454 Shipping Address Cooper Crouse Hinds Wolf 7th North Street Syracuse NY 13208 Ordering Par...

Page 27: ...oper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 4 1 CHC 140R System Controller Component Locatio...

Page 28: ...oper Industries Inc Crouse Hinds Division IF 1551 PO Box 4999 Rev 1 Syracuse New York 13221 U S A New 01 08 Copyright 2007 Cooper Industries Inc Figure 4 2 CHC 140W System Controller Component Locatio...

Page 29: ...ator Site Owner provide all that apply owner agent or subcontractor Contractor Name Contractor Company Point of Contact Information Name Phone Number Email Address Fax Number and Cell Phone or alterna...

Page 30: ...will be issued to the customer for the new product 5 After receiving the Cooper Crouse Hinds RMA number please adhere to the following packaging guidelines All returned products should be packaged in...

Reviews: