Piping Thickness and Material
Use the pipe as below.
Thickness
Material
Diameter
!
Flare Nut Dimension
Use the flare nut as below.
<Flare Nut Dimension B
in
(mm)
Diameter
R410A
Flare Nut
8
Use refrigerant R410A in the refrigerant cycle.
Do not charge oxygen, acetylene or other
flammable and poisonous gases into the
refrigerant cycle when performing a leakage
test or an air-tight
ness
test. These types of
gases
are extremely dangerous and can
cause an
explosion. It is recommended that
compressed air, nitrogen or refrigerant be
used for these types of tests.
5.1
Piping Materials
(1) Prepare locally-supplied copper pipes.
(2) Select the piping size from the Table 5.1.
(3)
Select clean copper pipes. Make sure
there is no dust and moisture inside of the
pipes. Blow the inside of the pipes with
nitrogen or dry air, to remove any dust or
foreign materials before connecting pipes.
NOTE
!
Cautions for Refrigerant Pipe Ends
When installing pipe through
the wall, secure a cap at the
end of the pipe.
Correct
Correct
Incorrect
Incorrect
Correct
Incorrect
Hole
Hole
Attach a cap
or vinyl tape.
Attach a cap
or vinyl tape.
Attach a cap
or vinyl bag with
rubber band.
Do not place the pipe
directly on the ground.
Rain water can
enter.
5.
Refrigerant Piping Work
O
O
O
O
!
Flaring Dimension
Perform the flaring work as shown below.
!
Cap the end of the pipe when the pipe is to
be inserted through a hole.
!
Do not put pipes on the ground directly
without a cap or vinyl tape at the end of the
pipe.
work according
to the tables.
Table 5.
2
Limitation of Outdoor Unit
Outer Diameter of Pipe
Gas
Liquid
5.2
Refrigerant Piping Work
(1)
Ensure that the directions for refrigerant piping
Diameter
Branch Pipe
B
-
10
2
H
Capacity
( Btu/h)
36
48
60
Table 5.
3
Indoor Unit Pipe Model
Table 5.1 Piping Size
in (mm)
Diameter
(d)
A
+0
-0.02 (-0.4)
R410A
1/4 (6.35)
0.36 (9.1)
3/8 (9.52)
0.52 (13.2)
1/2 (12.7)
0.65 (16.6)
5/8 (15.88)
0.78 (19.7)
3/4 (19.05)
(
)
1/64 ~ 1/32R
A
d
90
o
+ 2
o
45
o
+ 2
o
in (mm)
1/4 (6.35)
3/8 (9.52)
1/2 (12.7)
5/8 (15.88)
0.031 (0.8)
0.031 (0.8)
0.039 (1.0)
0.031 (0.8)
1/4 (6.35)
21/32 (17)
3/8 (9.53)
7/8 (22)
1/2 (12.7)
1-1/32 (26)
5/8 (15.88)
1-5/32 (29)
5/8 (15.88)
3/8 (9.53)
in (mm)
in (mm)
Capacity(kBtu/h)
Gas Pipe
Liquid Pipe
0 ~17
1/2(12.7)
1/4(6.35)
19~22(4-Way Cassette)
1/2(12.7)
1/4(6.35)
19(Ducted)
5/8(15.88)
1/4(6.35)
22(Ducted)
5/8(15.88)
3/8(9.53)
18~22(Wall-Mounted)
5/8(15.88)
3/8(9.53)
24~
5/8(15.88)
3/8(9.53)