switch to the next IDU
C03
Indoor unit quantity
query in the system
network
1-80
Timer area: displays the number of IDUs in the system
network.
C06
Preferential operation
query
00
:
Common
operation
01
:
Preferential
operation
Operation method:
In‖C06‖status,press ―MODE‖button to enter Preferential
operation query interface.Press―
∧
‖or―
∨
‖to switch the
IDU SN.
Display mode:
Temperature area: displays project number of current IDU
Timer area:displays the preferential operation setting
value of the current IDU
C07
Indoor environment
temperature query
-
Operation method:
In‖C07‖status,press ―MODE‖button to enter the indoor
environment temperature query interface.
Press―
∧
‖or―
∨
‖to switch the IDU SN.
Display mode:
Temperature area: displays project number of current IDU
Timer area: displays the temperature value of the
environment temperature sensor after replenishment.
C08
Prompt time query for
air filter cleaning
4-416
:
days
Timer area:displays the prompt time query for air filter
cleaning
C09
Wired controller
address query
01
,
02
Timer area: displays the adrsess of the current wired
controller
C11
Indoor unit quantity
query in one-to-many
mode
1-16
Timer area: displays the number of IDUs controlled by the
wired controller
C12
Outdoor environment
temperature query
-
Timer area: displays the temperature value of the
environment temperature sensor of the master ODU.
Note:
a. In parameter query status, FAN, TIMER, SLEEP, and SWING are invalid. By pressing the‖ON/OFF‖button,
users can return to the main interface but not power on/off the unit.
b. In parameter query status, signals of the remote controller are invalid.
3
)
User Parameter Settings
Engineering Parameters can be set in power-on of power-off status.
(1)
Press and hold the ―FUNCTION‖ button for five seconds to enter the user parameter query interface. The
temperature area displays ―C00‖. Press and hold the ―FUNCTION‖button for another five seconds to entert the
Summary of Contents for CHV-5S224SNMX
Page 1: ...CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL R410A 50 60Hz...
Page 3: ...1 PRODUCT CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL PRODUCT...
Page 11: ...0 900 CONTROL CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL CONTROL...
Page 50: ...INSTALLATION 0 48 0 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL INSTALLATION...
Page 74: ...MAINTENACE 0720 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL Maintenace...
Page 120: ...MAINTENACE 01180 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL...