105 MAINTENACE
CHV
5 COM PACT MULTI VRF UNIT
SERVICE M ANUAL
Removal operation for 4-way valve
Remark: Before removing the 4-way valve, make sure that there is no refrigerant inside the pipe system and that
the power has been cut off.
Process
Photo
Operation Instruction
1
、
Disconnect the
coil of 4-way
valve from the
4-way valve
Remove the coil of 4-way
valve at first
2
、
Disconnect the
4-way valve and
connection
pipeline
Weld those 4 connection
spots on 4-way valve, and
then
pull
out
the
connection pipe
Note:
Dur ing
welding
process, do not let the flae
burn out other parts
3
、
Replace 4-way
valve
Replace 4-way valve
Note:
Dur ing
welding
process, do not let the
flame burn out other parts
Remove
the
coil of 4-way
valve at first
Weld those 4
connection
spots on 4-way
valve