Cooper & Hunter CHV-07WTU Operation Installation Maintenance Manual Download Page 22

1

7.1  General Check  
(1) Make sure that the field-supplied electrical

components (main power switches, circuit breakers,
wires, conduit connectors and wire terminals) have
been properly selected according to the electrical 
data given in “Technical Catalog

” . Make sure that 

the components comply with National Electrical Code
(NEC).

(2) Use shielded twist pair cable for transmission

wiring between outdoor unit and indoor unit, remote
controller wiring between indoor units and remote
control switch.

(3) Check to ensure that the power supply voltage is

within ±10% of the rated voltage.

(4) Check the capacity of the electrical wires.

If the power source capacity is too low, the system
cannot be started due to the voltage drop.

(5) Check to ensure that the earth wire is connected.
(6) Power Source Main Switch

.

Install a multi-pole main switch with a space of

9 4

(

5

) or more between each phase.

 7.2

7.2  Electrical Wiring Connection    

The electrical wiring connection for the indoor unit 
is shown in Fig. 7.1. 

(1) Unscrew and remove the conduit mount plate

from the machine base. Fix a conduit for power
supply wiring to the plate with a lock nut and reattach
them at original position.

(2) Connect the wires of an optional remote control

switch to A, B terminals of the terminal board inside
the electrical box through the connecting hole in the
cabinet.
(3) Connect the wires between the indoor unit and
the outdoor unit to 1,

 

2 terminals of the terminal 

board inside the electrical box through the 
connecting hole in the cabinet.

(4) Connect power supply wires to L1, L2 and

connect earth wire to the earth. Please connect to the
power circuit with a ELB.

(5) Check to ensure that the terminal specification is

applied to the screw (M3.5 for power supply and
operating line) of the terminal box.

(6) Fix all the wires securely with cord clamp.

Remote Controller Wiring 

Indoor and Outdoor 
Transmission Wiring

Fig.7.1 Wiring Connection

 Power Supply 

 

08/ 3

0

60Hz

Earth Wiring 

Screw 

Cord Clamp(All wirings are
 fixed with cord clamp)

L1

   

L2

   

1       2      A      B

Hole for Power Wiring

Conduit Mounting Plate

For the minimum size of field-supplied power 
cord, please refer to Section 10.1.

S

crew 

C

T

Summary of Contents for CHV-07WTU

Page 1: ...ORIGINAL INSTRUCTIONS VRF INDOOR UNIT Wall Mounted Type CHV 07WTU CHV 09WTU CHV 12WTU CHV 15WTU CHV 18WTU CHV 24WTU CHV 28WTU...

Page 2: ......

Page 3: ...anual are only for illustration Please refer to the actual appearance The lowest moving parts should be mounted at least 8ft 2 4m above floor or grade level Refer to Installation Maintenance Manual of...

Page 4: ...al recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was p...

Page 5: ...Section2 Installation Maintenance Manual Setting of Swing Louver Filter Cleaning Taking Out the Filter Cleaning the Filter Reset of Filter Indication 5 1 1 3 4 4 5 5 Identification of Parts Remote Co...

Page 6: ...19 15 1 1 18 18 19 19 Common 21 the Filter Indication Interval 10 4 Indoor Unit Address 22 10 3 10 2 10 1...

Page 7: ...bilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety laundry O If the supply cor...

Page 8: ...ntake Air Outlet Vertical Adjustment Louver Front Panel Display Panel Horizontal Adjustment Louver Air Filter Remote Controller Figures in the manual are only simple representation of the appliance It...

Page 9: ...remote control switch Signal Receptor 3 2 5 4 Display set temperature It shows FC after 200 hours of usage as reminder to clean the filter After filter cleaning press the filter reset button located...

Page 10: ...actual angle of the louver and the liquid crystal indication When the switch is pressed the louver will not stop immediately The louver will move one extra swing at the next Discharge air angle is fix...

Page 11: ...7 8 5 8 1...

Page 12: ...9 9 1 9 2 9 3 9 4 8 2 8 3 approximately d RESET water...

Page 13: ...o not install the indoor unit outdoor unit remote control switch and cable within approximately from strong electromagnetic wave radiators such as medical equipment Users shall not change power lines...

Page 14: ...For Refrigerant Pipe Thermal Insulation Pipe 6 1 07 12 3 15 28 1 1 Wall 5 4 2 to 1 1 5 Diameter of 2 9 1 5 Hole for Piping INDOOR UNIT 8 2 4 5 29 2 150 15 1 100 unit wall and hanging board 1 Wireless...

Page 15: ...he wall with anchor bolts as shown in Fig 4 4 Mounting Bracket Screw Fig 4 4 Mounting on Concrete Wall or Concrete Block Wall Fixing Screw for Mounting Bracket Mounting Bracket Utilize Six Screws NOTE...

Page 16: ...racket 15 07 12 unit 1 37 64 40 4 49 64 121 3 3 64 90 1 7 32 31 15 1 100 2 4 70 20 5 4 522 5 127 15 1 100 15 1 100 22 2 5 1 2 19 2 7 4 155 15 1 100 Hole 2 9 1 5 for Pipe and Wring Hole 2 9 1 5 for Pip...

Page 17: ...el and open it and pull the right arm toward the inner side Slightly close the flat panel and pull it then remove the flat panel Flat Panel 2 Pay attention to the junction of grille from each side to...

Page 18: ...s 1 Prepare locally supplied copper pipes 2 Select the piping size from the following table 3 Select clean copper pipes making sure there is no dust and moisture inside the tubes Before connecting pip...

Page 19: ...side of the unit respectively Therefore most appropriate piping for a room can be selected Right Side Piping Take off the small cover from right side Take off the small cover from left side Rear Side...

Page 20: ...d direction of drain piping connection is right side as viewed from the discharge grilles However it can be performed from the left side or rear side Pipe Diameter 29 5 40 59 80 a b Fig 5 5 Stopper Pl...

Page 21: ...s Check to ensure the indoor and outdoor fans have stopped before electrical wiring or periodical check Protect the wires drain pipes electrical parts etc from rats or other small animals If not prote...

Page 22: ...hown in Fig 7 1 1 Unscrew and remove the conduit mount plate from the machine base Fix a conduit for power supply wiring to the plate with a lock nut and reattach them at original position 2 Connect t...

Page 23: ...ew for the electrical box cover Electrical box cover TB1 for Power Supply L1 L2 and Transmission wiring 1 2 and Remote control switch A B TP terminal plate for Earth wire Cord clamp Pass the wires thr...

Page 24: ...ified screw for terminal board and fasten the screw firmly Wired Remote Control Switch and Wireless Remote Control Switch can not be used simultaneously If Wired Remote Control Switch is connected dis...

Page 25: ...ment 15 DSW3 DSW6 DSW4 DSW5 DSW7 10 2 Setting of Dip Switches 1 1 DIP switch must be set with power sources of indoor and outdoor units in OFF state Otherwise the settings are invalid 2 2 The DIP swit...

Page 26: ...red Setting position before shipment is at OFF Once strong current is accidentally connected to Terminals 1 and 2 of TB the PCB fuse will be blown In such a case it s essential to correct the wiring a...

Page 27: ...2 Select Optional Setting from the test run menu pressing and 3 Select the indoor unit by pressing press This screen is NOT displayed when the number of indoor unit connected with the remote control s...

Page 28: ...63 5 The confirmation screen will be displayed Select Yes and press to stard address change process Result will be displayed in seconds If No is pressed the screen will go to 6 When the process succes...

Page 29: ...Indoor Unit Address Initialization This function initializes the indoor unit address that has been changed by Indoor Adds Change function or set by the automatic address a llocation Initializing the a...

Page 30: ...08 2022 V01 The Company is committed to continuous product improvement We reserve the right therefore to alter the product information at any time and without prior announcement...

Reviews: