2
6
Installation and Maintenance
Service Manual
Energize the unit
If the above cases are existed?
Test the isolation impedance
between the three phases of the
compressor and thecopper pipe
Malfunction is eliminated
End
If the wire of compressor is connected
well and correctly?
Correct according to the service
manual and then energize the
unit to operate
Test the resistance between
the three phases
Reconnect the wire of the
compressor according to the
correct wiring method
If the resistance is normal?
If the resistance is above 500M ?
Replace the
compressor
Replace the outdoor
mainboard
Please check:
1. if the indoor and outdoor heat exchanges are
dirty, if there is obstacle to affect the radiation;
2. if the indoor and outdoor fans are running
normally;
3. if the pressure of the system is too high;
4. if the refrigerant is too much which causes
the high level of pressure;
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No