background image

FAN ASSEMBLY AND MOUNTING 

Before installation of fan, check carefully for shipping damage which may result in blade misalignment, 
deformed parts or other damage.  After motor has been mounted, check pulley alignment and belt 
tension.  (For details on pulley alignment, refer to 

Page 8 

in this booklet.)  Before connecting the power 

source, check motor nameplate to be sure the correct phase and voltage will be applied.  Single phase 
motors are shipped from factory wired for 230 volt operation.  For low voltage operation see motor 
manufacturer’s instructions on nameplate.  Make sure propeller turns freely without striking fan frame or 
any foreign object which may interfere with its operation.  Note direction arrow on orifice to make sure 
propeller is rotating in the correct direction when power is applied. 
 

Motor Mounting 

If the fan and housing are factory assembled

, then the motor bracket is already mounted in the correct 

holes.  

If the fan is not factory mounted to the housing

, the motor bracket will need to be moved from it’s 

shipping position.

 

 

1.  If needed, remove the motor bracket from its shipping position and bolt it to the uprights using the 2nd 

and 3rd holes (2nd & 4th holes for Model MNEFDD or MNBCDD-RM) from the bottom of the uprights.  
Note: It may be necessary to slightly adjust the motor bracket in its slots to achieve proper belt 
tension. 

2.  Place the motor on the motor bracket and bolt it down using the 5/16” hardware provided.  Make sure 

the motor base remains level. 

3.  The motor pulley should be placed on the motor shaft with the “set screw” side of the pulley toward the 

motor.  Using a long straight bar, check the alignment of the motor pulley and the fan hub pulley.  If 
necessary, loosen the motor pulley set-screw and/or the motor mounting bolts and adjust as 
necessary.  Re-tighten pulley set screw and motor mounting bolts.  IMPORTANT: Motor bracket bolts 
must be secured to maintain proper belt alignment and tension. 

 
Once the motor has been properly mounted 
and the pulleys have been aligned, complete 
the assembly of the fan by threading the belt 
over the fan hub pulley groove, motor pulley, 
and belt tensioner (if included) as shown in 
Figures 5 & 6.  For Model MNBCDD, the 
tensioner is assembled and should be set for 
proper belt tension.  If a tension adjustment 
becomes necessary, refer to 

Page 8 

in this 

booklet.  Again, check for belt alignment 
using a straight bar as described above.  
Next, turn the blade assembly by hand to 
insure free rotation.  The fan is now ready to 
be mounted into the wall housing, if not 
already factory assembled. 
 

Fan Mounting 

If the fan is not factory mounted to the housing, 

lift the fan (from the outside of the building) and place it 

inside the assembled wall housing so that the fan panel is flush with the end of the wall housing.  Using 
twelve 5/16” X 3/4” bolts and twelve 5/16” whiz-lock nuts, fasten the fan into place in the housing.  

Caulk 

around the perimeter of the fan panel to seal the housing. 

 

Weatherproofing 

IMPORTANT: 

To prevent rainwater intrusion, caulk the outside top seam between the top of the fan and 

the housing.

 

Page 4 

 

Figure 5 — MNBCDD 

Figure 6 — MNEFDD 

Summary of Contents for MNBCDD36J

Page 1: ... MNBCDD36K MNEFDD36J MNEFDD36K MNBCDD36J RM MNBCDD36K RM MNEFDD36J RM MNEFDD36K RM UNPACKING Inspect the fan for signs of shipping damage It is the responsibility of the customer to report any shipping damage to the freight carrier WHAT SHOULD YOU FIND Fan 4 Housing Sheets Damper Door Assembly Cone 4 cone panels and 4 cone gussets Rear Housing Guard Front Cone Guard and Hardware Package Figure 1 4...

Page 2: ...RAMING FRAME CONSTRUCTION RECOMMENDED MINIMUM SPACING IS 12 POST CONSTRUCTION Page 2 Figure 2 DD36 44 3 4 SQ I D DD36 RM 40 3 4 SQ I D Spacing Figure 3 4 x 4 Post DD36 44 3 4 SQ I D DD36 RM 40 3 4 SQ I D ...

Page 3: ...lts from the outside in and thread the nuts on the inside This process should be repeated for the two remaining sheets After the fourth sheet has been fastened to the third it should also be fastened to the first completing the housing Next lift the housing into place in the wall opening Using the 4 overlapping corner holes and the 3 individual holes in each sheet flange fasten the housing to the ...

Page 4: ...he motor base remains level 3 The motor pulley should be placed on the motor shaft with the set screw side of the pulley toward the motor Using a long straight bar check the alignment of the motor pulley and the fan hub pulley If necessary loosen the motor pulley set screw and or the motor mounting bolts and adjust as necessary Re tighten pulley set screw and motor mounting bolts IMPORTANT Motor b...

Page 5: ...he cone so that the larger diameter is up Using four 1 4 flat washers insert four 1 4 X 2 3 4 Guard Stud Bolts into the overlapping holes on the edge of the cone panels from the outside in Place a Guard Spacer over each Guard Stud Bolt Next place a 1 4 whiz lock nut on each Guard Stud Bolt and tighten securely creating the guard studs as shown in Figures 8 9 Now tighten ALL of the 1 4 cone hardwar...

Page 6: ...e First invert the cone again so that the guard end is on the ground Take the damper door assembly making sure the doors open downward and insert it at an angle into the cone as shown in Figure 11 The end with the door restraining cable should be opposite the drain hole in the cone Once the entire ring assembly has been placed inside the cone level the ring and align the pre drilled ring holes wit...

Page 7: ...o check for proper damper operation open the doors fully and allow them to close If either door fails to close properly 1 make sure the door rods are aligned exactly vertically If necessary rotate the cone door assembly slightly on the fan orifice until both door rods are vertical 2 make sure the top of the door assembly is leaning 0 5 2 toward the building To do this place a level on each of the ...

Page 8: ... side of the fan orifice it will be necessary to loosen the two 2 3 8 bolts that secure the blade assembly s hexagonal shaft to the fan x braces center the blade assembly and tighten the bolts to 25 30 ft lbs torque If the blades rub in the fan orifice at the top or bottom it will be necessary to loosen the four 4 3 8 bolts that secure the fan x braces to the fan uprights center the blade assembly...

Page 9: ...y such that the alignment mark is between mark 1 and 2 on the idler arm see Figure 21 Re tighten the 3 8 bolt Turn the blade assembly by hand to insure free rotation Do Not Over Tension The Belt This will cause premature belt and bearing failure To check that the belt tension is not too high place a finger midway between the fan pulley and motor pulley and push inward about 1 2 The force required ...

Page 10: ...nd cone See Figure 21 WARNING Protect Fan and Cone from Snow and Ice Buildup WARNING Fan and or cone damage caused by this type of external source WILL NOT be covered by AMERICAN COOLAIR warranties Figure 21 During winter months you may not need to operate all of your fans It is advisable to seal up those fans which will not be used during the colder months to minimize heat loss as well as condens...

Page 11: ... bearing failure may be induced The damper door assembly should be wiped clean so that the doors will pivot freely open completely and close securely The interior sides of the fan wall housing doors should be washed properly after disinfecting the house to prevent rusting We recommend using Simple Green detergent or a similar product CHECK FASTENERS Inspect all fasteners on the fan This is a very ...

Page 12: ... USE UNLESS ELECTRICAL WIRING COMPLIES WITH ALL APPLICABLE CODES DO NOT WIRE WITHOUT PROVIDING FOR A POWER SOURCE DISCONNECT AT THE FAN ITSELF DO NOT SERVICE EXCEPT BY A QUALIFIED MAINTENANCE TECHNICIAN AND ONLY AFTER DISCONNECTING THE POWER SOURCE FAILURE TO OBSERVE THESE PRECAUTIONS CAN RESULT IN SERIOUS INJURY OR DEATH WARNING CAUTION FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPO...

Reviews: