Cool Energy inverTech Manual v6.6 2020 ©
Engineer Settings - These should be set by your installation engineer
(Altering these settings can impact system efficiency)
4.
Main Temperature Settings
Heating setp.
= Heating / Buffer Temperature
Default 45c
(Temperature of the supplied heating / buffer probe)
Cooling setp.
= Cooling / Buffer Temperature
Default 12c
(Temperature of the supplied heating / buffer probe)
Hotwater setp.
= Hot Water Temperature
Default 50c
(Temperature of the supplied hot water probe)
5.
Differential Temperature Settings:
Hotwater setp.
Temp. diff.
=
(Default 5c)
(Temperature differential before restart)
Stop temp diff. =
(Default 0c)
(Buffer range to optimise compressor frequency)
Cool water setp.
Temp. diff.
=
(Default 5c)
(Temperature differential before restart)
Stop temp diff. =
(Default 2c)
(Buffer range to optimise compressor frequency)
6.
PID Settings:
Kp.
=
(Default 5c)
(Proportional control of frequency adjustment)