QM CONTROLLER
COOL
The system has been pre-set to provide a 5 minute wash cycle before the fan starts. Water is circulated
over the pads to wash off any dust. To bypass this wash cycle, press FAN and then COOL. After each 5
hours of operation a periodic drain cycle empties the tank of water. This 5 hour cycle may be altered if re-
quired. See “Water Management System Settings”.
When the air conditioning system is switched off, the water tank is emptied and a fresh tank of water is
taken in. This fresh water is used to perform an 8 minute FLUSH cycle. Fresh water rinses and cleans the
pads of any impurities or minerals left from the cooling evaporation process. To by-pass this FLUSH Mode,
press FAN then OFF.
As a final process, the tank is emptied of water leaving it clean and dry.
Once the end of day FLUSH cycle has commenced it takes 15 minutes to complete. The FLUSH cycle can
be stopped sooner than 15 minutes by pressing FAN then OFF.
FAN
The FAN Mode is useful when the outside ambient temperature has dropped and no direct cooling is
required.
EXHAUST
A delay occurs when switching to EXHAUST Mode. This is to protect the motor and allow it time to stop,
before the rotation is reversed.
Exhaust mode is useful for eliminating odours from the home without the in-rush of air experienced with the
COOL and FAN modes. It is particularly useful in winter when a cold draft of air is not desirable.
OFF
Turns the system off.
WATER MANAGER SYSTEM SETTINGS
The Water Manager System has been factory set at 5 hours. This can be changed if required.
On the rear of the keypad are four Dip switches. They function as follows:-
DRAIN
- Dip switch “3” in off position if no periodic drain cycle and flush cycle is
required.
WASH
- Dip switch “2” in off position if a DRAIN after WASH cycle is required.
This function is useful for dusty environments. The tank of water is emptied after the
5 minute WASH cycle.
LONG
- Dip switch “1” in on position - 2.5 hour periodic cycle
.
-
Dip switch “1” in off position - 5 hour periodic drain cycle.