COOK LO-PRO Installation, Operation And Maintenance Manual Download Page 6

6

LO-PRO IO&M

B51021-004

Wiring Diagrams

Single Speed, Single Phase Motor

T-1
T-4

Ground B

L 2

L1

Ground A

Line

When ground is required, attach to ground A or B with No. 6 thread forming 

screw. To reverse, interchange T-1 and T-4.

2 Speed, 2 Winding, Single Phase Motor

Ground A

Ground B

T-1

T-4

Low Speed

High Speed

L1

L2

Line

When ground is required, attach to ground A or B with No. 6 thread forming 

screw. To reverse, interchange T-1 and T-4 leads.

Single Speed, Single Phase, Dual Voltage

Ground B

J-10

T-5

Ground A

Link A
Link B

Low Voltage

Line

L 2

L 1

Ground A

Link A & B

L1

L2

Line

Ground B

T-5

J-10

When ground is required, attach to ground A or B with No. 6 thread forming 

screw. To reverse, interchange T-5 and J-10 leads.

Typical Damper Motor Schematic

Fan

Motor

Damper

Motor*

Second

Damper

Motor

Transformer**

Transformer**

L3

L2

L1

For 3 Phase, damper motor voltage should be the same between L

1

 and L

2

For single phase application, disregard L

3

. *Damper motors may be avail-

able in 115, 230 and 460 volt models. The damper motor nameplate voltage 

should be verified prior to connection. **A transformer may be provided in 

some installations to correct the damper motor voltage to the specified volt-
age.

3 Phase, 9 Lead Motor

4 5 6

1

7

2

8

3

9

L1 L2 L3

4 5 6

7 8 9

1 2 3

L1 L2 L3

Low Voltage

208/230 Volts

High Voltage

460 Volts

3 Phase, 9 Lead Motor

Y-Connection

7

1

6

7 8 9

4 5 6

1 2 3

Low Voltage

208/230 Volts

High Voltage

460 Volts

8

2

4

9

3

5

L1

L3

L2

L1

L3

L2

3 Phase, 9 Lead Motor

Delta-Connection

To reverse, interchange any two line leads.

2 Speed, 1 Winding, 3 Phase Motor

Motor

1
2

3

4
5

6

Together

High Speed

Line

L1

L 2
L 3

1
2

3

4
5

6

Open

Low Speed

Line

L1

L 2
L 3

Motor

To reverse, interchange any two line leads. Motors require magnetic 

control.

2 Speed, 2 Winding, 3 Phase

L

1

T

1

T

2

T

3

Low Speed
Low Speed
Low Speed

High Speed
High Speed
High Speed

Motor

T

13

T1

2

T

11

L

3

Line

L

3

To reverse: High Speed-interchange leads T

11

 and T

12

. Low Speed-inter-

change leads T

1

 and T

2

. Both Speeds-interchange any two line leads.

Summary of Contents for LO-PRO

Page 1: ...left unguarded Any object pulled into the inlet will become a projectile capable of causing serious injury or death When air is allowed to move through a non powered fan the impeller can rotate which...

Page 2: ...leys are properly aligned Refer to Figure 2 Tolerance Center Distance Max Gap Up thru 12 1 16 12 up through 48 1 8 Over 48 1 4 OFFSET ANGULAR OFFSET ANGULAR A W X Y Z B CENTER DISTANCE CD GAP GAP Pull...

Page 3: ...the inspections stop the fan and inspect as per the chart below 30 Minute Interval Inspect bolts setscrews and motor mounting bolts Adjust and tighten as necessary 8 Hour Interval Inspect belt alignm...

Page 4: ...months 2 weeks Motors are provided with a polyurea mineral oil NGLI 2 grease All additions to the motor bearings are to be with a compatible grease such as Exxon Mobil Polyrex EM and Chevron SRI Maxi...

Page 5: ...and setscrews and re peat from step 5 Wheel Replacement 1 Drill two holes approximately centered between the shaft and the edge of the hub OD with the following dimensions 1 4 diameter 3 8 to 1 2 dee...

Page 6: ...le phase application disregard L3 Damper motors may be avail able in 115 230 and 460 volt models The damper motor nameplate voltage should be verified prior to connection A transformer may be provided...

Page 7: ...nced wheel Belts too loose worn or oily belts Speed too high Incorrect direction of rotation Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly Bearings need...

Page 8: ...d other than for the uses described in the com pany manual This warranty does not cover defects resulting from normal wear and tear To make a warranty claim notify Loren Cook Company General Offices 2...

Reviews: