COOK FCE Series Installation, Operation And Maintenance Manual Download Page 2

2

FCE/FCRU IO&M

B51150-003

1.  Remove the top cap which covers the motor assembly 

by unbolting the lid.

2.  For internal wiring, run the electrical wire and conduit 

through the opening drilled in the damper shelf (refer 

to Damper Installation), then through the wiring con-

duit in the ventilator base to the motor compartment. 

For external wiring, run the wires through the horizon-

tal conduit on upblast units, or under top cap in down-

blast units.

3.  Pull the wires through and complete the wiring. For 

further information. Refer to 

Wiring Diagrams

 on page 

3.

Final Installation Steps

1.  Ensure fasteners and set screws, particularly fan 

mounting and bearing fasteners are tightened accord-

ing to the recommended torque shown on the table 

below.

2.  Inspect for correct amperage with an ammeter and 

correct voltage with a voltmeter.

3.  Ensure that all accessories are installed.

4.  Test the fan to be sure the rotation is the same as indi-

cated by the arrow marked “Rotation.”

NOTICE! Do not allow the fan to run in the wrong 

direction. This will overheat the motor and cause 

serious damage. For 3-phase motors, if the fan is 

running in the wrong direction, check the control 

switch. It is possible to interchange two leads at 

this location so that the fan is operating in the cor-

rect direction.

5.  Inspect wheel-to-inlet clearance. Wheels may shift in 

shipment. To realign wheel-to-inlet, shift upper bearing 

so there is an equal radial clearance between the wheel 

and inlet. Refer to 

Wheel to Inlet Clearance

, page 6.

Recommended Torque for Setscrews/Bolts on Metal (IN-LB)

Setscrews

Hold Down Bolts

Size

Key Hex 

Across 

Flats

Recommended 

Torque

Size

Recommended 

Torque

Min.

Max.

#8

5/64”

15

21

3/8”-16

324

#10

3/32”

27

33

1/2”-13

780

1/4

1/8”

70

80

5/8”-11

1440

5/16

5/32”

140

160

3/4”-10

2400

3/8 

3/16”

250

290

7/8”-9

1920

7/16

7/32”

355

405

1”-8

2700

1/2 

1/4”

560

640

1-1/8”-7

4200

5/8 

5/16”

1120

1280

1-1/4”-7

6000

3/4 

3/8”

1680

1920

-

-

7/8 

1/2”

4200

4800

-

-

1

9/16”

5600

6400

-

-

Recommended Torque for Setscrews/Bolts on FRP (FT-LB)

Size (inches)

18-8 SST Hardware Torque

No. 10

7

1/4”

12

5/16”

20

3/8”

30

7/16”

41

1/2”

54

5/8”

86

3/4”

128

To maintain good working condition of the fan when it is 

stored outdoors, follow the additional instructions below.

•  Coat the shaft with grease or a rust preventative 

compound.

•  Wrap bearings for weather protection. Cover the inlet 

and outlet to prevent the accumulation of dirt and mois-

ture in the housing.

•  Periodically rotate the wheel and operate dampers (if 

supplied). Periodically inspect the unit to prevent dam-

aging conditions.

Installation

If the fan was delivered with the motor unmounted, see 

the maintenance section for belt and pulley installation.

Damper Installation

If your fan is supplied with dampers, follow the directions 

below. If your fan does not include dampers, proceed to 

Belt and Pulley Installation

.

1.  Place the damper inside the curb or inside the duct 

work. Ensure the damper will open freely for the cor-

rect direction of the airflow.

2.  Secure to curb at the damper shelf.

3.  Drill hole in the curb shelf for conduit needed for mo-

tor wiring.

4.  Operate the dampers manually to ensure the blades 

move freely.

5.  Install fan over curb while aligning the conduit location 

with the conduit hole in the curb.

Wiring Installation

NOTICE! All wiring should be in accordance with 

local ordinances and the National Electrical Code, 

NFPA 70. Ensure the power supply (voltage, fre-

quency, and current carrying capacity of wires) is 

in accordance with the motor nameplate (see page 

3 for diagram). Fan must be grounded to prevent 

electrical discharge.

For Units Without A Junction Box:

An  approved  metal  field  wiring  compartment  must  be 

secured to the unit with two screws in order that the box 

does not rotate. All wires must be protected from abrasion 

where they enter and exit the wiring compartment.

The green ground wire from the motor must be secured 

under  the  green  ground  screws  inside  the  field  wiring 

compartment using a closed loop connector. Complete 

connections in accordance with the wiring diagram on the 

motor.

For Units With A Junction Box:

Pull wires through the appropriate conduit. Protect wires 

from abrasion where they enter the field wiring compart

-

ment and complete connections in accordance with the 

diagram on the motor.

Leave enough slack in the wiring to allow for motor 

movement when adjusting belt tension. Some fractional 

motors have to be removed in order to make the connec-

tion with the terminal box at the end of the motor.

NOTICE! Follow the wiring diagram in the discon-

nect switch and the wiring diagram provided with 

the motor. Correctly label the circuit on the main 

power box and always identify a closed switch to 

promote safety (i.e., red tape over a closed switch).

Summary of Contents for FCE Series

Page 1: ...tile capable of causing serious injury or death When air is allowed to move through a non powered fan the impeller can rotate which is referred to as windmill ing Windmilling will cause hazardous cond...

Page 2: ...ative compound Wrap bearings for weather protection Cover the inlet and outlet to prevent the accumulation of dirt and mois ture in the housing Periodically rotate the wheel and operate dampers if sup...

Page 3: ...8 230 Volts High Voltage 460 Volts 8 2 4 9 3 5 L1 L3 L2 L1 L3 L2 3 Phase 9 Lead Motor Delta Connection To reverse interchange any 2 line leads 2 Speed 1 Winding 3 Phase Motor Motor 1 2 3 4 5 6 Togethe...

Page 4: ...vron SRI The above intervals should be reduced to half for verti cal shaft installations Inspection Inspection of the fan should be conducted at the first 30 minute 8 hour and 24 hour intervals of sat...

Page 5: ...rest authorized electric motor service representative Changing Shaft Speed All belt driven ventilators 5HP or less are equipped with variable pitch pulleys To change fan speed perform the following 1...

Page 6: ...s with cast frames can be ex tremely heavy and should not be lifted without addi tional aid Set motor aside 4 Locate the 4 to 8 bolts on the flat surface of the interior of the housing Begin to loosen...

Page 7: ...anced wheel Belts too loose worn or oily belts Speed too high Incorrect direction of rotation Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly Bearings nee...

Page 8: ...ing to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your written complaint you will be notified within thirty 30 days of our receipt of your complaint in wri...

Reviews: