COOK CA DWDI Installation, Operation And Maintenance Manual Download Page 2

2

7. place adjusting nut and locking nut on threaded rod 

near fan mounting bracket

8. alternately rotate adjusting nut at each mounting 

location until the fan weight is uniformly transferred to 
the isolators. Remove bracing.

Floor Mounted Spring Isolators

1. Mount fan and motor on isolation base or rails (if 

supplied).

2. Elevate fan (or isolation base) to operating height and 

insert blocks to hold in position.

3. Position isolators under the fan and vertically align by 

inserting leveling bolt through mounting holes in the 
fan or the base. The isolator must be installed on a 
level surface.

4. Adjust the isolators by turning the leveling nut counter 

clockwise several turns at a time alternately on each 
isolator until the fan weight is transferred onto the 
isolators and the fan raises uniformly off the blocks. 
Then remove the blocks.

5. Turn lock nut onto leveling bolt and secure firmly in 

place against the top of the mounting flange or frame.

6. Secure isolators to mounting surface.

Floor Mounted Rubber-In-Shear (RIS) Isolators

1. Mount fan and motor on an isolation base or rails (if 

supplied).

2. Elevate fan to provide room to insert isolators between 

the base and foundation and block in position.

3. Position isolators under fan and secure bolts.
4. Remove blocks and allow fan to rest on floor. Isolators 

must be installed on a level surface (leveling should 
not be required).

5. Secure isolators to mounting surface.

Rubber-In-Shear Ceiling Isolators

Ceiling Mounted Spring Isolator

Figure 1 - Ceiling Mount Isolators

Figure 2 -Floor Mount Isolators

Rubber-In-Shear Isolator

Spring Isolator

Foundation

This fan requires a strong, level foundation of reinforced 

poured concrete. A correctly designed concrete foundation 
provides the best means for mounting floor units. The 
foundation’s size is determined by fan size and 
arrangement, motor size and position, and the specific 
location of the installation.

Use the following guidelines to calculate foundation size:

• The overall dimensions of the foundation should

extend at least 6 inches beyond the outline of the fan
and its motor.

• The weight of the foundation should be 2 to 3 times the

weight of the unit and its motor.

Isolation 

NOTICE!

 

Although a certain amount of vibration is 

inherent in operating centrifugal fans, extreme 
vibration is a serious problem that may cause 
structural and mechanical failure.

Isolation Base

To prevent vibration and noise from being transferred to 

the building isolators are recommended. Arrangement 1, 2, 
& 3 (CA or CF) fans require an isolation base to effectively 
isolate the fan system which includes the fan, base, motor, 
drive, guards, etc. Bases must have sufficient rigidity to 
resist belt pull and prevent drive distortion which can lead to 
excessive belt and bearing wear; its perimeter should 
contain all base angles and rotating parts. Arrangement 9 
or 10 fans (CA, CF, and CP) above size 270 require 
isolation rails. Please consult factory for isolation of 
arrangement 9 fans due to the potential of uneven loading 
caused by the motors and drives. Isolators should be 
located between the fan system and the support structure.

Ceiling Mounted Spring and Rubber-in-Shear (RIS) 

Isolators

1. Mount fan on isolation base or rails
2. Elevate fan to operating height and brace
3. Attach threaded rod to overhead support structure 

directly above each mounting hole. Rod should extend 
to within a few feet of fan.

4. Attach isolator to end of threaded rod using a nut on 

each side of isolator bracket

5. Insert another section of threaded rod through the fan 

mounting hole and isolator

6. Attach two nuts to threaded rod isolator

The attachment of roof mounted fans to the roof curb
as well as the attachment of roof curbs to the building
structure must exceed the structural requirements
based on the environmental loading derived from the
applicable building code for the site. The local code
official may require variations from the recognized
code based on local data. The licensed engineer of
record will be responsible for prescribing the correct
attachment based on construction materials, code
requirements and environmental effects specific to
the installation.

Failure to follow these instructions could result in
death or serious injury.

Summary of Contents for CA DWDI

Page 1: ...mental documents prior to any installation or maintenance procedure Loren Cook Company s catalogs CA CF CP provide additional information describing the equipment fan performance available accessories...

Page 2: ...extend at least 6 inches beyond the outline of the fan and its motor The weight of the foundation should be 2 to 3 times the weight of the unit and its motor Isolation NOTICE Although a certain amoun...

Page 3: ...32 210 1 4 225 5 32 245 9 32 270 445 1 4 490 17 32 540 600 27 32 660 730 25 32 Duct Installation Efficient fan performance relies on the proper installation of inlet and discharge ducts Be sure your...

Page 4: ...ameplate See page 5 for diagram Leave enough slack in the wiring to allow for motor movement when adjusting belt tension Some fractional motors have to be removed in order to make the connection with...

Page 5: ...T1 and T2 Both Speeds interchange any 2 line leads Typical Damper Motor Schematic For 3 phase damper motor voltage should be the same between L1 and L2 For single phase application disregard L3 Dampe...

Page 6: ...r Class II Normal Conditions Clean Dry Smooth 2 7 500 2 1 000 Extreme Conditions Dirty Wet Rough 2 1 500 2 200 Centrifugal Blower Class III Normal Conditions Clean Dry Smooth 2 3 000 2 500 Extreme Con...

Page 7: ...local Loren Cook representative or your nearest authorized electric motor service representative Changing Shaft Speed belt drive All belt driven fans with motors up to and including 5 HP 184T max are...

Page 8: ...lacement 1 Remove pulleys from their respective shafts 2 Clean the motor and fan shafts 3 Clean bores of pulleys and coat the bores with heavy oil 4 Remove grease rust or burrs from the pulleys and sh...

Page 9: ...or oily belts Speed too high Incorrect direction of rotation Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly Bearings need lubrication or replacement Fan...

Page 10: ...SI Arrangement 3 5 4 3 2 1 6 10 13 9 8 12 11 14 Drive Side View Discharge Side View Inlet Side View 7 Part No Arr 1 Arr 3 ARR 9 1 Motor Slide Base 2 Motor 3 Motor Sheave 4 Belt Set 5 Fan Sheave 6 Hous...

Page 11: ...SI CF 4 SWSI Arr 4 1 Motor Slide Base 2 Motor 3 Motor Sheave 4 Belt Set 5 Fan Sheave 6 Housing 7 Isolation Base optional 8 Shaft 9 Drive Side Bearing 10 Free Side Bearing 11 Wheel 12 Inlet Cone 12 5 3...

Page 12: ...F DW CA 4 DWDI 5 4 3 2 1 6 10 13 9 8 11 12 14 7 Drive Side View Free Side View Discharge Side View Part No CA DWDI CAF DW CA 4 DWDI 1 Motor Slide Base 2 Motor 3 Motor Sheave 4 Belt Set 5 Fan Sheave 6...

Page 13: ...S A CPV Part No CPA CPA A CPS CPS A CPV w Optional Curb Cap and Inlet Box Accessory Parts List 1 CP Vent Set 2 Adjustable Draw Latch 3 Access Door Assembly 4 Latch Keeper 5 Curb Cap Plenum Box Assembl...

Page 14: ...A CPV Arr 4 CPV EC 1 Motor 2 Housing 3 Wheel 4 Inlet Cone 5 Pedestal 6 Optional Weather Cover 7 Discharge Flange 8 Inlet Side Support CPV EC 5 4 2 3 7 1 6 Inlet Side View Discharge Side View 8 Drive...

Page 15: ...15...

Page 16: ...le Street Springfield Missouri 65803 4637 explaining in writing in detail your complaint and referring to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your w...

Reviews: