CMP 6050 RETROFIT INSTALLATION INSTRUCTIONS
4.
From the rear of the control panel door, locate and remove the existing mounting hardware from
the threaded studs. Keep the mounting hardware as it will be re-used to mount the new control
panel assembly and retrofit cover panel. Some existing control panel doors are equipped with six
threaded studs instead of four.
5.
Remove controller power supply (Figure 2) (if not mounted to existing controller assembly), input
board and relay board (Figure 3)
along with all associated existing wires. Place input and relay
boards in static sensitive packaging. Existing wires may be discarded.
6.
Locate and remove all controller communications cables (RJ11 modular jacks) from control panel
(Figure 4).
F
Mounting hardware
Mounting hardware
Figure 1
F
TB3
•
Mounted to existing
controller assembly
Controller power supply
•
Mounted to existing
controller assembly
Figure 2
Figure 3
Input board
Relay board
F
Figure 4