GB
69
Installation distance to walls and ceiling
550
1600
102
217
min 2300
Combustible roof
Air inlet Ø64
120
430
43
0
105
0
114
0
167
Hole in foot plate Ø120
368
15
0
72
9
781
Combustible wall
267
100
415
400
300
100
3
00
200
100
690
Combustible wall
Permitted area for
combustible material
C34T
*To prevent discolouration of painted fire walls, we recommend the same side distance as to combustible walls.
268
50
629
900
900
640
Fire-retardant wall of
brick or concrete
217
50
700
1100
50*
325*
Fire-retardant wall of
brick or concrete
Place the stove on the hearth plate and check
that the installation distances are not less than
those that are given in the figures below. The
minimum distance in front of the stove opening
to combustible parts of the building or interior
decoration must be at least 1 m.
When top connecting a steel flue, please
refer to the particular manufacturer's
installation instructions. Observe the
safety distance to combustible material
that the steel flue requires.
INSTALLATION DISTANCES