CONTROL PANEL SPECIFIC ALARMS AND SHUT DOWNS 

The panel has its own engine safety alarms and shut downs that can be enabled.  These alarms and 
shut downs are managed by the control panel.  The available options are listed below and can be 
accessed via the Engine Safety Configuration menu.   

Each alarm must be enabled in the Engine Safety Configuration menu to activate. 

Heading 

Default 

Range 

Units 

Sender Check Bypass 

0:10 

0:05 – 1:00 

Min:Sec 

Fuel Level Check 

Off 

Off / Always / Run 

 

Low Fuel Pre Alarm 

20 

0 - 100 

Low Fuel Alarm 

0 - 100 

Fuel Alarm Delay 

0:05 

0:01 – 1:40 

Sec 

Fuel Level Alarm Action 

Shutdown 

 

 

Oil Pressure Check 

Run 

Off / Always / Run 

 

Low Oil Press Pre Alarm 

15 

0 - 100 

PSI 

Low Oil Press Alarm 

10 

0 - 100 

PSI 

Oil Pressure Alarm Action  

Shutdown 

 

 

Oil Press Alarm Delay 

0:05 

0:01 – 1:40 

Sec 

Temperature Check 

Run 

Off / Always / Run 

 

High Temp Pre Alarm 

220 

150 - 300 

Deg F 

High Temp Alarm 

230 

150 - 300 

Deg F 

Temperature Alarm Action 

Shutdown 

 

 

Temp Alarm Delay 

0:05 

0:01 – 1:40 

Min:Sec 

Battery Volts Check 

Off 

Off / Always / Run 

 

Low Battery Pre Alarm 

12.0 

0.0 – 40.0 

Volts 

Hi Battery Pre Alarm 

15.0 

0.0 – 40.0 

Volts 

Over Speed Check 

Off 

Off / Always / Run 

 

Over Speed Alarm 

3000 

650 - 5000 

RPM 

Over Speed Alarm Delay 

0:05 

0:01 – 1:40 

Min:Sec 

 
1) Off / Always / Run – Describes when the parameter will be monitored for alarm conditions.  Run 

refers to when the engine is running.  Off disables the alarm conditions.  Always enables the alarm 
constantly regardless of engine state. 

2) Alarm Delay – The time period, after Sender Check Bypass, that the parameter must be on the 

alarm condition before the alarm becomes latched. 

Summary of Contents for MVP-G142

Page 1: ...yright Controls Inc P O Box 368 Sharon Center OH 44274 Phone 330 239 4345 Fax 330 239 2845 www controlsinc com Product Manual Generator Display Control Panel J1939Engines Part Number MVP G142 Revision...

Page 2: ...INSTALLATION INFORMATION 2 MODULE CONNECTOR 4 ENGINE ALARMS CODES AND MESSAGES 5 ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS CONTROL PANEL ANALOG AND DIGITAL INPUTS 7 MENU SYSTEM 9 MENU...

Page 3: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 3 INSTALLATION INFORMATION...

Page 4: ...O L S Y S T E M S S O L U T I O N S 4 MODULE CONNECTOR INFORMATION BATTERY CAN HIGH CAN LOW DIGITAL INPUT 1 FUEL LEVEL INPUT BATTERY BATTERY ALARM OUTPUT DIGITAL INPUT 3 N A N A DIGITAL INPUT 2 RELAY...

Page 5: ...e Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Pressure Alarm Action Shutdown Oil Press Alarm Delay 0 05 0 01 1 40 Sec Temperature Check Run Off Always Run High Temp Pre Alarm 220 150 300 D...

Page 6: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 6 Indicator Lamps Engine Fault Lamp Engine Alarm Lamp...

Page 7: ...arm Energizes an external audible alarm when a pre alarm or alarm condition is present Pressing the ENTER button will silence 4 Alarm Horn Energizes an external audible alarm when an alarm condition i...

Page 8: ...ardless of engine state 2 Alarm Delay The time period after Sender Check Bypass that the parameter must be on the alarm condition before the alarm becomes latched CONTROL PANEL RELAY OUTPUTS The panel...

Page 9: ...croll menu options Press UP arrow button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up br...

Page 10: ...g View Scroll Stored Alarm Events Engine Identification Engine Model View Engine Serial View Module Information Control Unit Part View Control Unit Software Version View Controller Setup Quick Setup 1...

Page 11: ...arameter 3 Generator Configuration Phase Type Voltage Type Generator Pole Pairs Generator Run Detect Activation Frequency Activation Delay Deactivation Frequency KWH Reset 4 Input Configuration Config...

Page 12: ...ge Display English Metric Selection Performance Display Off On Fuel Display 9 CAN Configuration Engine Manufacturer TSC1 Address Default 3 Others available Source Address Default 44 Others available E...

Page 13: ...Engage Load Default 0 Clutch 1 Engage Coolant Temperature Default 150 F Clutch 1 Engage Delay Default 0 00 Clutch 1 Engage Interval Default 0 00 Clutch 1 Release Trip Default None Clutch 1 Release Spe...

Reviews: