LAMP OPERATION 

The KS-105 comes with five high intensity LEDs lamps. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Oil Pressure Lamp 
Oil pressure lamp turns ON when the oil 
pressure switch is “closed” indicating a 
low oil pressure condition (after initial 10 
second bypass period on engine start). 

Hour Meter 
Displays engine run hours. 

Coolant Temperature Lamp 
Coolant temperature lamp turns ON 
when the engine temperature switch is 
“closed” indicating a high engine 
temperature condition. 

Alternator Charge Lamp 
Alternator charge lamp turns ON when 
alternator excite signal is received from 
the alternator. 

Glow Plug Lamp 
The glow plug lamp turns “ON” when 
the glow plug signal is being sent from 
the KS-105.  The glow plug signal is 
initiated when the key is in the “PRE-
HEAT” position or the “CRANK” 
position.  The pre-heat period is either 
4 or 10 seconds depending on the 
pre-heat interval select circuit being 
grounded or not. 

Altitude Compensation Lamp 
The altitude compensation lamp turns 
ON when the altitude compensation 
signal is received from the altitude 
compensation module mounted on 
the engine. 

Summary of Contents for KS-105

Page 1: ..._____________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon Center OH 44274 Phone 33...

Page 2: ...IEW 2 PANEL COMPONENTS 3 INSTALLATION 4 PRODUCT IDENTIFICATION 5 PANEL OPERATION 6 LAMP OPERATION 7 ENGINE HARNESS CONNECTOR 8 INTERNAL CONNECTOR 9 CIRCUIT OPERATION 10 PANEL DIMENSIONS 12 SPECIFICATI...

Page 3: ...h Water Tight Rated IP67 Water Tight Plug and Play Connector Dedicated Pre Heat Position Hour Meter Potting Provides Water Tightness and Superior Vibration Shock Protection Connector 10 Inch Pigtail t...

Page 4: ...Screws Mounting Screws Engine Harness Connector Hour Meter High Intensity LED Indication Lamps Mounting Bolts Spacers Key Switch Powder Coated Steel Case INSIDE KS Series Microprocessor Platform PANEL...

Page 5: ...S 105 installs into the engine mounting bracket via four bolts spacers and a plug and play connector Control Panel Mounted Inside Bracket Installation Procedure 1 Turn Power Off 2 Insert unit into bra...

Page 6: ...5 PRODUCT IDENTIFICATION Every panel has a product label that provides the part number and individual serial number for identification...

Page 7: ...erval select is grounded the pre heat period is 10 seconds During pre heat operation the yellow GLOW PLUG lamp illuminates Engine Start When the key is turned to the CRANK position the KS 105 energize...

Page 8: ...ure condition Alternator Charge Lamp Alternator charge lamp turns ON when alternator excite signal is received from the alternator Glow Plug Lamp The glow plug lamp turns ON when the glow plug signal...

Page 9: ...the Yanmar engine harness Panel Ratings The KS Panel is rated at 3 Amp Maximum Fuel Hold 2 1A max 12v sourcing Crank and Preheat 500mA max Close to Ground Pre Heat Interval Select A loose wire with a...

Page 10: ...INTERNAL CONNECTOR The KS 105 provides a plug and play connector to the KS Series microprocessor electronics module 794824 1 Connector 1 1586359 6 Wire Seal 1 1586362 6 Connector Seal 794831 1 Termina...

Page 11: ...from the alternator used to turn the alternator excite lamp ON H to W5 Pre Heat Signal Close to ground signal when key is in the PRE HEAT or CRANK position This is a close to ground signal circuit to...

Page 12: ...second oil pressure shutdown bypass period during engine start to allow pressure to build and open the low pressure switch Key Switch Pos 2 to W14 Crank Position Input KS 105 key switch position detec...

Page 13: ...12 DIMENSIONS...

Page 14: ...13 SPECIFICATIONS...

Page 15: ...14 REPLACEMENT COMPONENTS Replacement components are listed below Please contact Controls Inc for details...

Reviews: