CONTROL PANEL RELAY OUTPUTS
The panel provides relay outputs defined below located in the
Output Configuration menu
. The
relays are rated at 5 amps.
The panel is shipped from the factory with the
highlighted
outputs enabled and pre-
wired in the panel.
Relay
Heading
Default
Connector
Pin
Relay 1
Ground output
only
Function
None
Polarity
Positive
Initial State
Off
Relay 2
Function
Fuel/Run
16 Pin
Connector
R
Polarity
Positive
Initial State
On
Relay 3
Function
Preheat
16 Pin
Connector
J
Polarity
Positive
Initial State
Off
Relay 4
Function
None
Polarity
Positive
Initial State
Off
RELAY FUNCTIONS
Available relays can be assigned for different uses.
a.
None - Assign to “none” when not used.
b.
Throttle B1 - Reserved for OEM applications.
c.
Throttle B0 - Reserved for OEM applications.
d.
Pre Alarm - Relay will be active when there is a pre alarm condition. Typically used to
drive an alarm horn or lamp. Also can be used to send a signal to a monitoring station.
e.
Alarm - Relay will be active when there is an alarm condition. Typically used to drive an
alarm horn or lamp. Also can be used to send a signal to a monitoring station.
f.
Pre Alarm & Alarm - Energizes an external audible alarm when a pre alarm or alarm
condition is present. Pressing the ENTER button will silence.
g.
Alarm Horn - Energizes an external audible alarm when an alarm condition is present.
Pressing the ENTER button will silence.