CONTROLS, INCORPORATED
C O N T R O L S Y S T E M S & S O L U T I O N S
- 11 -
CONTROL PANEL ANALOG AND DIGITAL INPUTS
The panel is shipped from the factory with the
bold
print inputs pre-wired and enabled
in the panel.
Inputs not in bold print need to be wired and enabled to be used.
Analog Inputs
Input
Heading
Default
Connector Pin
Analog 1
Function
Fuel Level
(Stewart-Warner Scale)
31-Pin
25
Digital Inputs
Input
Heading
Default
Connector Pin
Digital 1
Normally Open
31-Pin
24
Function Alarm
Message E-Stop
Check
Always
Digital 2
Normally Closed
-
-
Function Hydro-Throttle
Message None
Check
Always
Digital 3
Normally Open
31-Pin
18
Function Alarm
Message Remote E-Stop
Check
Always
Digital 4
Normally Open
31-Pin
19
Function
Available
Message
None
Check
Always
Digital 5
Normally Open
31-Pin
20
Function
Available
Message
None
Check
Always
Digital 6
Normally Open
31-Pin
21
Function
Available
Message
None
Check
Always