N°
LEDs
behaviour
Error
Actuator use
Actuator behaviour
Typical trouble
shooting condition
Reset
procedure
Automatic calibration
(DIP N. 7 OFF)
Manual calibration
(DIP N. 7 ON)
1
RED ON
Valve stroke
less than 5mm
Calibration/first
installation
The actuator pushes/pulls 2 times
(unexpected stall) trying to remove
the possible obstacle. After 2
tries an alarm is signalled and the
actuator moves to initial position
and does not respond to control
signal. Stroke value is not updated
because out of range
The actuator pushes/pulls 2
times against endpoint during
calibration and the actuator
moves to the initial position and
then it does not respond to the
control signal. The actuator
keeps the previous stroke
Valve with a stroke
length lower than
5mm
Remove power
and power up
again
2
RED LED
quick
bl
GREEN ON
Stroke longer
than 60mm
Calibration/first
installation
The actuator exits the 60mm stroke
range and it moves toward the new
stroke limit signalling an anomaly.
The actuator pushes/pulls 2 times
against the new stroke limit, then it
goes back to the initial position still
signalling the anomaly until it is not
within 60mm. The actuator does
not calibrate the stroke after 10s
(wrong range)
The actuator exits the 60mm
stroke range and it moves
toward the new stroke limit
signalling an anomaly. The
actuator pushes/pulls 2 times
against the new stroke limit, then
it goes back to the initial position
still signalling the anomaly until it
is not within 60mm. The actuator
does not calibrate the stroke
after 10s (wrong range)
Valve with a stroke
length longer than
60mm
Remove power
and power up
again
3
RED Quick
Blinking
Unexpected
stall within the
calibrated stroke
range
normal operation
The actuator tries 5 times against
the new stall condition and then
after 10s the actuator updates the
new stroke length
The actuator tries 5 times
against the new stall condition.
At the end of the attempts
the fault will be signalled. The
actuator does not update the
new stroke length, but after 60s
makes other attempts to verify
the stall condition
Valve stuck
Inverted control
signal
4
RED Quick
Blinking
Stroke longer
than expected Normal operation
The actuator moves toward the
new stall condition with a lower
speed; after 10s the actuator
updates the new stroke value
The actuator moves toward the
new stall condition with a lower
speed; after 10s the actuator
does not update the new stroke
value
Stem connection
loose or valve
damaged
Inverted control
signal
5
RED slow
Blinking
Low Power
Voltage
Normal operation
The actuator is still working but
performance cannot be guaranteed
The actuator is still working
but performance cannot be
guaranteed
1. Wrong transformer
size
Correct Voltage
Power
2. Unstable power
6
RED slow
Blinking
High Power
Voltage
Normal operation
The actuator is still working but
performance cannot be guaranteed
The actuator is still working
but performance cannot be
guaranteed
1. Wrong transformer
size
Correct Voltage
Power
2. Unstable power
COMPORTAMENTO STANDARD dei LED
STANDARD LEDs BEHAVIOUR
1° Emissione / 1
st
Issue
rev.
c
09/15
6 DIM205
N° Comportamento
LED
Stato servocomando
1
VERDE FISSO
Il servocomando è arrivato
all’estremo della corsa appresa
2
VERDE
LAMPEGGIANTE
Il servocomando è arrivato o si sta
muovendo verso un punto intermedio
della corsa appresa
3
ROSSO VERDE
LAMPEGGIANTE
Il servocomando sta apprendendo
la corsa o sta effettuando il
posizionamento iniziale
4
ROSSO VERDE
FISSO
Comando manuale inserito, il
servocomando ignora il segnale di
comando.
ATTENZIONE! La scheda è
alimentata
N°
LED
behaviour
Actuator status
1
GREEN ON
The actuator arrived at the extreme
point of the stroke read
2
GREEN BLINKING
The actuator arrived at the
intermediate point of the stroke read
3
RED GREEN
BLINKING
The actuator is reading the stroke or
it is going to initial position
4 RED GREEN ON
Manual control ON, the actuators
ignores the control signal.
ATTENTION! The electronic board
is electrically supplied