441-622-015   

Type 500X 

Page 3 

Port Sizes 

 

1/4” NPT (Pneumatic) 
1/2” NPT (Electric)

 

1/4” NPT (Pneumatic) 
1/2” NPT (Electric)

 

Media 

 

Clean, dry, oil-free, instrument air, filtered to 40 micron

 

Electrical Connections 

 

Conduit 1/2” NPT (standard); DIN 43650 (optional) 

Mounting 

 

Pipe, panel, or bracket 

 

Weight 

 

2.1 lbs. (0.94 kg) 

 

 

2.1 lbs. (0.94 kg)

 

 
 

 
 

 

2.1  Description

 

2.1.1     The ControlAir Type 500X converts a current or voltage input signal to a linearly proportional 

pneumatic output  pressure. This versatile instrument is designed for control applications that 
require a high degree of reliability and  repeatability at an economical cost. 

2.2  Principle of Operation

 

2.2.1 

The Type 500X is a force balance device in which a coil is suspended in the field of a magnet by a 
flexure. Current  flowing through the coil generates axial movement of the coil and flexure. The 
flexure moves towards the nozzle  and creates back pressure which acts as a pilot pressure to an 
integral booster relay. Input signal increases (or  decreases for reverse acting) cause proportional 
output pressure increases. 

Zero and Span are calibrated by turning adjust screws on the front face of the unit. Adjustment of 
the zero screw  repositions the nozzle relative to the flexure. The span adjustment is a 
potentiometer that controls the amount of  current through the coil. 

2.3  Mounting 

2.3.1    Unit may be pipe, panel, or bracket mounted. Mounting may be at any angle, though may require field 

adjustment. High external vibration may cause output fluctuations. Mounting in a vibration-free area is 
recommended. 

2.4  Pneumatic Connections

 

2.4.1     The 1/4 NPT (1/4 BSP option) supply and output ports are marked “IN” and “OUT” respectively on 

the base of the unit. Clean all  pipe lines to remove contamination before installation. Apply pipe 
compound to male threads of the air line only.  Avoid getting compound in the air lines. 

Clean dry instrument quality air must be used. To ensure optimum performance supply pressure 
should be  regulated. To provide stable inlet pressure and prevent contamination of the internal 
section of the transducer the  use of an Instrument Air Filter Regulator is recommended. 

The two unmarked ports on the base of the unit are gage ports but may be used as alternative 
output ports. Any  unused ports must be plugged. 

 WARNING  

The I/P transducer enclosure contains aluminum and is considered to constitute a potential risk of 

ignition by impact or friction and must be considered during installation.

 

 

2.5  Electrical Connections

 

2.5.1     Electrical connections are made to the black and white leads extending out from the 1/2 NPT conduit 

fitting. When the side of the input signal is connected to the black lead, the output pressure will 
increase as the  t signal increases. 

 

 

 

Figure 1 DIN 43650 Connector (“D” option) 

 

2. DESCRIPTION AND INSTALLATION 
 
 

 

Summary of Contents for 500X

Page 1: ...allation 3 3 0 Operation 4 4 0 Maintenance 6 5 0 Troubleshooting 6 6 0 Warranty 6 Type 500X Electro Pneumatic Transducer I P E P Installation Operation and Maintenance Instructions 8 Columbia Drive Amherst New Hampshire 03031 USA Phone 603 886 9400 Fax 603 889 1844 sales controlair com www controlair com ...

Page 2: ... at 10 psig 0 7 bar above 20 psig 1 3 bar setpoint Impedance 4 20 mA 90 Ohms 4 20 mA 90 Ohms 4 20 mA 180 Ohms 0 5 VDC 615 Ohms 1 9 VDC 985 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 250 Ohms 4 20 mA 225 Ohms 0 5 VDC 500 Ohms 4 20 mA 260 Ohms 0 10 VDC 805 Ohms Performance Specifications Terminal Based Linearity 0 75 of span 1 5...

Page 3: ...through the coil 2 3 Mounting 2 3 1 Unit may be pipe panel or bracket mounted Mounting may be at any angle though may require field adjustment High external vibration may cause output fluctuations Mounting in a vibration free area is recommended 2 4 Pneumatic Connections 2 4 1 The 1 4 NPT 1 4 BSP option supply and output ports are marked IN and OUT respectively on the base of the unit Clean all pi...

Page 4: ...w counterclockwise for up to 30 revolutions until output pressure rises 5 Increase electrical input signal to its maximum value e g 20 mA for a 4 20 mA unit 6 Observe the output pressure If necessary adjust the span screw until reaching maximum output pressure setting For I P current input models turn span screw counterclockwise to increase pressure clockwise to decrease pressure For E P voltage i...

Page 5: ...SURES FOR ELECTRICAL EQUIPMENT 1000 VOLTS MAX NOTES 1 INSTALLATION TO BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE NFPA 70 ARTICLE 504 AND ANSI ISA RP 12 6 2 APPARATUS CONNECTED TO THE SYSTEM SHALL NOT USE OR GENERATE VOLTAGE GREATER THAN 250 V 3 INSTALL INTRINSICALLY SAFE BARRIERS IN ACCORDANCE WITH BARRIER INSTRUCTIONS 4 FM APPROVALS APPROVED AS INTRINSICALLY SAFE FOR CLASS I II AND III DIV ...

Page 6: ...o be free from defects in materials and workmanship for a period of eighteen months from the date of sale provided said products are used according to ControlAir LLC recommended usages ControlAir LLC s liability is limited to the repair purchase price refund or replacement in kind at ControlAir Inc s sole option of any products proved defective ControlAir LLC reserves the right to discontinue manu...

Reviews: