441-622-015   

Type 500X 

Page 2 

WARNING 

CAUTIO

 

 

 

  

DANGER 

ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL. 

 
 
 
 
 

Functional Specifications 

 

 

 

Standard Range 

High Output  

INPUT 

 

4-20 mA, 0-5 VDC, 1-9 VDC, 0-10 VDC

 

4-20 mA, 0-5 VDC, 0-10 VDC  

Outputs psig  
(bar) 
 
Supply Pressure 
psig (bar) 

3-9  
(0.2-0.6) 
 
12-100  
(0.8-6.9) 

9-15  
(0.6-1.0) 
 
18-100  
(1.2-6.9) 

 

 

3-15, 15-3  
(0.2

-

1.0) 

 
18-100  
(1.2-6.9) 

3-27, 27-3  
(0.2-1.8) 
 
30-100  
(2.1-6.9) 

6-30, 30-6  
(0.4-2.0) 
 
33-100  
(2.3-6.9) 

1-17  
(0.1-1.2) 
 
20-100  
(1.4-6.9) 

2-60  
(0.14-4.1) 
 
65-150  
(4.5-10.3) 

3-120  
(0.2-8.2) 
 
125-150 (8.6-10.3) 

Air Consumption 

 

 

 

0.05 scfm (1.41 NL/min) midrange typical 

0.07 scfm (1.98 NL/min) midrange 
typical 

Flow Rate

 

4.5 scfm (127 NL/min) 
at 25 psig (1.7 bar) supply 

12.0 scfm (340 NL/min 
at 100 psig (6.8 bar) 

20.0 scfm (566 NL/min) 
at 150 psig (10.5 bar) 

 

Temperature Range 
(Operating) 

 

-20

0

F to 140

0

F (-30

0

C to 60

0

C) 

 

Relief Capacity 

 

 

2 scfm (56.6 NL/min) at 5 psig (2.4 bar)  
above 20 psig (1.3 bar) setpoint 

7 scfm (198 NL/min) at 10 psig (0.7 bar) 
above 20 psig (1.3 bar) setpoint 

Impedance 

4-20 mA 
  90 Ohms 

4-20 mA 
  90 Ohms 

4-20 mA 
  180 Ohms 

0-5 VDC 
   615 Ohms 

1-9 VDC 
   985 Ohms 

4-20 mA 
   220 Ohms 

0-5 VDC 
   530 Ohms 

1-9 VDC 
   840 Ohms 

4-20 mA 
   220 Ohms 

0-5 VDC 
   530 Ohms 

1-9 VDC 
   840 Ohms 

4-20 mA 
   250 Ohms 

4-20 mA 
   225 Ohms 

0-5 VDC 
   500 Ohms 

4-20 mA 
   260 Ohms 

0-10 VDC 
     805 Ohms 

 

Performance Specifications 

 

Terminal Based 
Linearity  

 

<

± 

0.75% of span 

<± 1.5% of span typical,  

± 

2.0% max. 

Hysteresis 

 

< 1.0% of span 

< 0.5% of span 

Repeatability 

 

< 0.5% of span  

< 0.5% of span 

Response Time 

 

Dependent on pressure range - typically less than 0.25 sec for 3-15 psig units 

Supply Pressure 
Sensitivity 

 

<

± 

0.1% of span per psig (<

± 

0.15% of span per 0.1 bar) 

<

± 

0.1% of span per psig, 

± 2.0% max. 

 
Physical Specifications 

 

Housing 

  

NEMA 1 (standard); NEMA 4X (IP65) (optional) 

 

DANGER, WARNING, CAUTION and NOTE statements 

DANGER 

NOTE 

 

Refers to conditions or hazards which could result in serious personal injury or death. 

 

Refers to conditions or hazards which could result in personal injury. 

 
 

Refers to conditions or hazards which could result in equipment or property damage. 

 

 

Alerts you to facts or special instructions. 

1.

 

SPECIFICATIONS 

 

Summary of Contents for 500X

Page 1: ...allation 3 3 0 Operation 4 4 0 Maintenance 6 5 0 Troubleshooting 6 6 0 Warranty 6 Type 500X Electro Pneumatic Transducer I P E P Installation Operation and Maintenance Instructions 8 Columbia Drive Amherst New Hampshire 03031 USA Phone 603 886 9400 Fax 603 889 1844 sales controlair com www controlair com ...

Page 2: ... at 10 psig 0 7 bar above 20 psig 1 3 bar setpoint Impedance 4 20 mA 90 Ohms 4 20 mA 90 Ohms 4 20 mA 180 Ohms 0 5 VDC 615 Ohms 1 9 VDC 985 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 220 Ohms 0 5 VDC 530 Ohms 1 9 VDC 840 Ohms 4 20 mA 250 Ohms 4 20 mA 225 Ohms 0 5 VDC 500 Ohms 4 20 mA 260 Ohms 0 10 VDC 805 Ohms Performance Specifications Terminal Based Linearity 0 75 of span 1 5...

Page 3: ...through the coil 2 3 Mounting 2 3 1 Unit may be pipe panel or bracket mounted Mounting may be at any angle though may require field adjustment High external vibration may cause output fluctuations Mounting in a vibration free area is recommended 2 4 Pneumatic Connections 2 4 1 The 1 4 NPT 1 4 BSP option supply and output ports are marked IN and OUT respectively on the base of the unit Clean all pi...

Page 4: ...w counterclockwise for up to 30 revolutions until output pressure rises 5 Increase electrical input signal to its maximum value e g 20 mA for a 4 20 mA unit 6 Observe the output pressure If necessary adjust the span screw until reaching maximum output pressure setting For I P current input models turn span screw counterclockwise to increase pressure clockwise to decrease pressure For E P voltage i...

Page 5: ...SURES FOR ELECTRICAL EQUIPMENT 1000 VOLTS MAX NOTES 1 INSTALLATION TO BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE NFPA 70 ARTICLE 504 AND ANSI ISA RP 12 6 2 APPARATUS CONNECTED TO THE SYSTEM SHALL NOT USE OR GENERATE VOLTAGE GREATER THAN 250 V 3 INSTALL INTRINSICALLY SAFE BARRIERS IN ACCORDANCE WITH BARRIER INSTRUCTIONS 4 FM APPROVALS APPROVED AS INTRINSICALLY SAFE FOR CLASS I II AND III DIV ...

Page 6: ...o be free from defects in materials and workmanship for a period of eighteen months from the date of sale provided said products are used according to ControlAir LLC recommended usages ControlAir LLC s liability is limited to the repair purchase price refund or replacement in kind at ControlAir Inc s sole option of any products proved defective ControlAir LLC reserves the right to discontinue manu...

Reviews: