4.0 TROUBLE ANALYSIS: 

A  malfunction  chart  including  several  possible  failure  modes  is  supplied  to  assist  the  technician  in  analyzing  the 
probable  cause.  The  receiver-controller  is  warrantied  for  one  year  from  date  of  purchase.  Failures  not  caused  by 
improper installation or abnormal treatment will be corrected by the manufacturer free of charge within the warranty 
period. 
 
4.1 

TROUBLE ANALYSIS CHART:

 

The following tabulations will provide guidance for recognizing possible trouble and correction.  

 

MALFUNCTION                           

POSSIBLE CAUSE                       

 TEST AND REMEDY

 

AC voltage present but no DC         Open 1.0 A. Fuse                        

Test & Replace  

LED indication 

Bad AC Switch                          

Test & Replace 

 

Defect in power supply.               

Return receiver to  

electronic board, power               

manufacturer for service.  

transformer or series  
regulator transistors 

 
DC OK, no LED   

              Defect in receiver card  

 

Replace card, retest. Send 

indication, no audio  

 

part number 11-0255 

 

defective card to manufacturer 

                                                                                                                  

 

for repair or replacement 

 

 

 

 

 

 

 

 

if in warranty. 

 
DC OK             

 

 

Open 5A SLO BLO Fuse   

Test & Replace fuse with same 

Relay closures normal                                                                                type only 
No output voltage any  

 

 

 

 

 

 

control line 

 

 

 

 
Failure to reset Timer indicator 

Defective Receiver/Decoder card,  Use replacement card and retest. 

after 5 seconds   

 

number 11-0255   

 

Return defective card to manufacturer

 

for                    

 

 

 

 

 

 

 

 

repair or replacement if in warranty

.

 

 
Fails to turn off after 15 minutes 

Defective Receiver/Decoder Card,  Use replacement card and retest. 
Part number 11-0255 

Return defective card to manufacturer

 

for 

repair or replacement if in warranty

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC O.K., 

 

 

Defective Relay K-1, K-2, or K-3

Replace Relay Card P/N 

output indicator LED's Normal 

whichever circuit is defective 

11-0195 and retest. 

 
 

 

 
 
 
 
 
 
 
 

 

 

 

Summary of Contents for RC-1T2A

Page 1: ...MBODIES A PROPRIETARY DESIGN ORIGINATED BY CONTROL INDUSTRIES INC AND SHALL NOT BE DISCLOSED USED OR DUPLICATED FOR PROCUREMENT OR MANUFACTURING PURPOSES UNLESS SPECIFICALLY AUTHORIZED BY CONTROL INDU...

Page 2: ...rate from 120 volt 20 50 60 HZ single phase power 3 0 THEORY OF OPERATION The system is activated by counting pulses of R F energy withing a 5 second timing period After receipt of five pulses during...

Page 3: ...FIG A Functional Diagram...

Page 4: ...FIG B INTERCONNECTING WIRING DIAGRAM with Lightning Suppression Components...

Page 5: ...circuit provides the IF gain AM detection RSSI and audio output The audio output is buffered and delivered to a service jack for maintenance and test purposes A red LED indicator is included on the r...

Page 6: ...relays are turned off Resistors R 2 R 4 R 6 R 8 and LED indicators D 3 D 4 D 6 D 8 show when the relays have been activated The LEDs will be visible when the printed circuit board cover is in place R...

Page 7: ...facturer for service transformer or series regulator transistors DC OK no LED Defect in receiver card Replace card retest Send indication no audio part number 11 0255 defective card to manufacturer fo...

Page 8: ...sence of primary line voltage as measured between input terminals marked 115VAC and neutral 2 Press AC power switch and observe Green DC power indicating LED inside the controller housing Illumination...

Page 9: ...failure of the D C indicator indicates a Main Interface PCB failure The following steps should be accomplished in sequence Verify proper output voltage from Power Transformer T 1 The output voltage of...

Page 10: ...board will reset and open and Control Lines that were activated The timer will reset to 15 minutes if another selection in made during the countdown period The Time out period come preset to 15 minut...

Page 11: ...n The terminal block is clearly marked with neutral and 115V AC terminations Attention to correct connection of the neutral is important Failure to observe these instructions may damage the equipment...

Page 12: ...No 11 0255 Power Relay Board 1 Control Industries No 11 0195 Fuse 3 LittleFuse MDL 5 Fuse 1 LittleFuse MDL 1 9 0 Warranty Information Control Industries INC Warranties that the equipment has been man...

Reviews: