UD55 User Guide
Issue code: 55nu3
10
6 Loading Parameters
6.1 Loading a Parameter-set from the UD55
If the Drive trips and a trip code is displayed while this procedure is being
followed, refer to
Appendix A, Diagnostics
.
1
Ensure the destination Drive is configured in the same operating mode
as the source Drive. (The UD55 cannot change the operating mode of
the Drive.)
2
Ensure terminals 40 and 41 on the UD55 are
not
connected.
3
Insert the UD55 in the source Drive.
4
Ensure terminal 30 of the Drive
Signal connector
is open-circuit so that
the Drive does not become enabled when powered-up.
5
Re-fit the terminal cover to the Drive.
6
Connect the
AC
supply to the Drive.
7
It is recommended that the following is performed:
•
Set parameter
11.38
at the number of the parameter-set to be used.
•
Note the value of
11.40
UD55 full parameter checksum
.
•
Compare this value against the value noted when the parameter-set
was saved in the UD55.
If the values differ, this indicates that a different parameter-set has
been selected or the values contained in the parameter-set have been
changed.
8
Set parameter
.00
(in any menu) at
400X
, where
X
is the parameter-set
number of the configuration to be loaded in the destination Drive.
9
Press
. The parameter values are now copied from the UD55
(loaded) to the Drive. (If the operating mode of the destination
differs from that of the source, parameter values will not be loaded
and the Drive will trip; the display will indicate
FSH.TYP
).
Loading is almost instantaneous. Parameter
.00
returns to zero.
10
Set parameter
.00
at 1000 and press
in order to save the
parameter values.
11
Disconnect the
AC
supply from the Drive.
12
Remove the terminal cover.