background image

 

EMC-D3b 

EMC-D3b-485 

instructon manual 

IM450-U v3.1 

page 3 

 

For a correct use of the device, the wiring diagram contained in the present manual, must be respected. 
The connections are available on the screw terminal: 
 

-  auxiliary power supply: 

The power supply is take from voltage inputs. 
Are available 5 different auxiliary supply: 
0 - 115V = 100-130V 50-60Hz  (N-L1)  (on request by single phase option) 
0 - 230V = 220-240V 50-60Hz  (N-L1)  (on request by single phase option) 

0 - 400V = 380-415V 50-60Hz  (L1-L2) standard model 

0 - 230V = 220-240V 50-60Hz  (L1-L2) (on request) 
0 - 115V = 100-130V 50-60Hz  (L1-L2) (on request) 
It’s possible, for example, to give an auxiliary power supply between phase and neutral, in a 4 wires system, or phase-
phase in a 3 wires system, without neutral or from a VT in a medium voltage application. 

In the standard version the voltage is 400V and it’s taken between the phases L1-L2. 

In the following table it’s possible to see the measurable voltage depending of the type of power supply. 

power supply terminals 

rated voltage

range of measurable voltage 

VL1 - VL2

 

(phase to phase power supply for 3-phase networks) 

400V 

300÷500V phase to phase (175÷290V phase-neutral) 

230V 

175÷290V phase to phase (130÷170V phase-neutral) 

110V 

85÷145V phase to phase (50÷85V phase-neutral) 

VL1-N

 

(phase-neutral power supply for single phase networks) 

230V 175÷290V 

phase-neutral 

110V 100÷170V 

phase-neutral 

The standard version allows to apply the instrument at all the three-phase network 400V with or without neutral supplied. 
For example for application on single phase 230V will need the L1-N / 230V. while for applications in medium voltage (for 
example using external voltage transformer 15 / 0.1 kV phase to phase) will need the version L1-L2 / 110V. 
 

- measuring voltage inputs: 

4 screw terminals are available for the 3 phase plus neutral system network. The maximum voltage between phase to 
phase must not overcome 500 Vrms

.

, depending always on the instrument's power supply. 

In case of three phase application with or without neutral not distributed, it is enough not to connect the terminal N. 
The transformation ratio of the external Potential Tranformer’s can be set on the instrument's SETUP menu (see 

SeT 

VT

 ratio. 

 
- measuring current inputs: 

6 screw terminals are available for the connection of the external CT with secondary 5A. It is also possible to use 2 CT in 
a three phase system (3Phase Aaron wiring system). 

It’s compulsory to use external CT’s.

 

The transformation ratio of the external CT's can be set on the instrument's SETUP menu. 

 
NOTE: It’s fundamental to respect the correct phase sequence. The connections between current and voltage phase inputs must not be 
inverted (for example, CT placed on phase L1 must correspond to the I1 input) and at the same time it’s not correct to invert the S1 and 
S2 terminals considering that the energy metering won't be reliable. 

 
- digital input 

On the terminal board 30 (DI+) and 32 (DI-) is available the digital input. 
This input can operate in three differents mode: 
- Sync: 

can recognize pulse (minimum time = 200 mS) to syncronize the internal average period timer to an external 
device; this property is available with the energy count mode ( refer to SETUP section) is set to 
'TOTAL/PARTIAL' or to 'NORMAL'; 

- Reset 

when a voltage pulse of minimum 1 second is applied, perform the reset of the only PARTIAL energy 
counters of each energy type (kWhr, kVArhr, kVAhr); this property is available with the energy count mode 
(refer to SETUP section) is set to  'TOTAL/PARTIAL'; 

- Disabled  No operation is done depending the digital input status. 
 
When the energy count mode ( refer to SETUP section) is set to  'TIME.BAND’ the counting is divided in T1 or T2 band 
depending the status of digital input;  SETUP of digital input is disabled; 
Timeband T1 is selected when no voltage is applied, T2 when the input is powered  
Each parameters (kWh, kVArh and kVAhr) have two counters T1 and T2, in which the energy is counted depending the 
status of digital input. 

Summary of Contents for EMC-D3b

Page 1: ...other than the standard specify when ordering power supply separated from measuring voltage specify when ordering single phase network power supply is taken from VL1 and neutral specify when ordering...

Page 2: ...nd authorised staff must carry out maintenance and or repair Should it be considered that there is a safety loss during operation the instrument must be disconnected and precautions taken against acci...

Page 3: ...ust not overcome 500 Vrms depending always on the instrument s power supply In case of three phase application with or without neutral not distributed it is enough not to connect the terminal N The tr...

Page 4: ...INSERTION ON THREE PHASE LINE WITH 4 WIRES AND 3 VT BALANCED THREE PHASE LINE LOAD P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure cu rren t inputs measure vo ltag...

Page 5: ...erred at the L1 phase The others data displayed relatives at value of three phase system are not to consider VL1 VL2 VL3 N EMC measure vol tage in puts LOAD S2 S2 S2 S1 S1 S1 I1 I2 I3 measure cu rren...

Page 6: ...he energy counting is being accumulated on time band 2 F LED indicating energy counting The frequency of blinking is proportional to the energy displayed G LED for indication of reactive energy counti...

Page 7: ...L1 PUL 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 00 1 kW kVAr pulse 0 01 kW kVAr pulse TPL 100 mS Set the duration pulse 200 mS 300 mS 400 mS 500 mS only for EMC D3b 485 ID Increase Set...

Page 8: ...RMAL Only one counter is available for each energy resetting the energies is available only by the front panel E TOT PAR Two counters are available for each energy the total counters are not resettabl...

Page 9: ...he instrument when it will be connected in a EIA485 communication network proceed with the modality already described The settable values are from 1 to 247 To confirm press the C key Programming of th...

Page 10: ...CHED OFF SWITCHED OFF SWITCHED OFF SWITCHED ON Energy operating mode TIME BAND Parameter LED s STATUS LED kWh LED kVARh LED T1 LED T2 Visualisation active energy T1time band Energy counting on T1 time...

Page 11: ...POWER FACTOR PHASE L3 PF3 000 ACTIVE POWER PHASE L1 PL1 000 ACTIVE POWER PHASE L2 PL2 000 ACTIVE POWER PHASE L3 PL3 000 REACTIVE POWER PHASE L1 QL1 000 REACTIVE POWER PHASE L2 QL2 000 REACTIVE POWER...

Page 12: ...80 Vac to 250 Vac 50 60Hz From 90 Vdc to 300Vcc polarised Serial output Only for EMC D3b 485 one RS485 port 2400 to 19200 baud s MODBUS RTU protocol GENERAL Display operation keys 1 display with red...

Reviews: