![Contrec 414Q Manual Download Page 27](http://html1.mh-extra.com/html/contrec/414q/414q_manual_2658171027.webp)
3.7 THE OUTPUT PULSE AND FLOW ALARM
An
OUTPUT PULSE
is available on terminal 10 for driving remote counters
and produces a pulse each time the Accumulated Total increments by one digit.
For example, if the Accumulated Total has a resolution of 0.01 litres, a pulse is
produced each 0.01 litres.
The pulse is a current sinking pulse of approximately 10mSec produced by an
open collector transistor. The maximum pulse rate is limited to 49 pulses per
second and the resolution on the accumulated total must be set so that the
accumulated total increments at less than 49 counts per second.
Note that due to the uneven pulse output spacing on this output, the pulse output
cannot be used to drive rate indicators.
The
FLOW ALARM
uses an identical circuit to the Output Pulse, and is on
terminal 7.
The Flow Alarm is used by the Quadrature Input, if selected, and will output an
error signal if there is a difference between the input pulses as described in
Section 3.3. The Flow Alarm will also output an alarm condition if the flow
times out during a batch (ie. there is no flow registered for a time greater than the
Signal Timeout period, providing the Signal Timeout is greater than 0).
The Flow Alarm output will switch "on" (ie the signal goes low) whenever an
alarm condition exists. The Alarm will switch "off" (ie the signal goes high)
when the alarm is reset by pressing the STOP key.
Operation 25
Summary of Contents for 414Q
Page 1: ...BATCH CONTROLLER MODEL 414Q July 2001 ...
Page 2: ......