ImpRopER loCATIoN oR INSTAllATIoN CAN RESulT IN STRuCTuRAl DAmAgE To
ThE buIlDINg, DAmAgE To ThE ExTERIoR FINISh oF ThE buIlDINg, oR mAy AlloW
RECIRCulATIoN oR FREEZINg oF ThE FluE gASES oNTo oR INTo ThE CombuSTIoN
AIR INTAkE.
moISTuRE IN ThE FluE gASES CoNDENSES AS IT lEAVES ThE TERmINAlS. ThIS
moISTuRE CAN FREEZE oN ExTERIoR WAllS, SoFFITS, AND oThER NEARby
objECTS. SomE DISColoRATIoN IS To bE ExpECTED.
CAuTIoN
!
!
The vent terminal should be located no fewer than 6 feet from an inside corner formed by two exterior walls. A
10 foot distance is recommended.
Recommended clearance for overhangs is a minimum of 1 foot vertically for each foot horizontally up to 6 feet.
Any adjacent painted surfaces should be in good condition; no cracks, peeling paint, etc. If wooden surfaces that
may be periodically exposed to flue gases are present, consider treating with a sealer
.
10.6 MUlTIple venTInG
COMMON vENTING IS PROHIBITED!!
If two of these furnaces are to be installed in close proximity, the combustion air intake and exhaust
terminations may be installed as shown in Figures 12 and 13.
IMPORTANT
:
WhEN INSTAllINg mulTIplE FuRNACES IN CloSE pRoxImITy, EACh REquIRES
DEDICATED CombuSTIoN AIR AND ExhAuST VENTINg.
If more than two furnaces are being installed in close proximity, each additional combustion air intake and
exhaust termination set shall not terminate less than 12 in (300 mm) apart. Note: Canadian installations of
120000 btu/hr require 3 ft (900 mm).
RECIRCULATION OF FLUE GASES MAY OCCUR CAUSING THE INTAKE PIPE TO
FREEzE SHUT DURING COLD WEATHER OPERATION IF THE vENTING SYSTEM IS NOT
INSTALLED PER THESE GUIDELINES.
WARNINg
!
!
Avoid locating the termination too close to shrubs and other vegetation. The condensate may stunt or kill them.
Caulk all cracks, seams or joints within a 6 foot radius of the termination.
Do not terminate under a deck unless there is adequate clearance to prevent damage from the flue gases.
A termination may be located at the end of a patio deck. piping running beneath the deck must be suitably
insulated and suspended in a manner to prevent condensate from collecting and freezing.
Do not locate the terminal on the side of the building facing the prevailing winter winds.
FIGURE 13 - MULTIPLE vENTING (STANDARD
vERTICAL)
12” MIN. ABOVE
SNOW LEVEL
3” MAX.
30” MAX.
12”
MIN.
3” MAX.
TO BE REDUCED
FROM 3” PVC TO
2” PVC BELOW THE
ROOF LINE
COMBUSTION AIR
INTAKE 2” PVC
TWO FURNACES VENTING THROUGH ROOF
3” MIN.
INTAKE
8” MIN.
2”
MIN.
12” MIN.
12” MIN.
12” MIN.
GRADE
EXHAUST
FIGURE 12 - MULTIPLE vENTING (STANDARD
HORIzONTAL)