direct venting - model CDVS600-1

2.1  typical vent installations

TOP VENT

REAR VENT

24"

(61cm)

16" (40.6cm)

min.

40 ft. (12m)

max.

34" (864mm)

min.

40 ft. (12m)

max.

34" (864mm) min.

!

WARNING

•  Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.

•  The vent system must be supported every 3’(0.9m) for both vertical and horizontal runs. Use support ring assembly W010-

0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both vertical and 

horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air gap to the outer 

pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this 

gap is maintained. These spaces must not be removed.

This appliance uses a 4” (102mm) exhaust / 7” (178mm) air intake vent pipe system. Refer to the section applicable 

to your installation.

For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical 

vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several minutes 

(5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through 

unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize 

condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a 

fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.

The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 

400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.

Connections made by means of an adaptor at the appliance, as well as the connection at the vent terminal must be sealed. 

RTV sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems, 

except for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature 

sealant Mill Pac.
For all vent systems is strongly recommend for all installations but required when power venting the appliance, that the outer 

air intake joints are sealed using either high temperature silicone (RTV) or a suitable aluminum tape that covers each joint in the 

vent system entirely around its circumference.  This will ensure the best performance in every application and avoids perfor-

mance or condensation concerns that may occur in “tightly” constructed homes, particularly those in cold climates.

For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a minimum. 
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that 

it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not 

be combined.

These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 

feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two 

horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0” rise per foot or 0mm rise per meter however for optimum performance it is recommended 

that all horizontal runs have a minimum 1/4” rise per foot or 21mm rise per meter using fl exible venting. For safe and proper 

operation of the appliance, follow the venting instructions exactly.  
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings 

and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap 

all around between the inner liner and outer liner is required for safe operation. 

Venting System

Manufacturer

Starter Adapter 

Part Number

Supplier

Website

SureSeal

Metal-Fab

4DNA

Wolf Steel

www.mtlfab.com

Direct Vent Pro

Simpson DuraVent W175-0053

Wolf Steel

www.duravent.com

Pro-Form

BDM

DVR6-STA7

BDM

www.dalsinmfg.com

Direct Temp

Selkirk

4DT-AAN

Selkirk 

www.selkirkcorp.com

Ventis

Olympia Chimney 

and Venting

VDV-NA04-47F

Olympia Chimney 

and Venting

www.olympiachimney.com

Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp venting components. Minimum and 

maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air 

terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Metal-Fab, BDM, Simpson 

Dura-Vent, or Selkirk Direct Temp, follow the installation procedure provided with the venting components or on the website for 

your venting supplier.

A starter adaptor must be used with the following vent systems and may be purchased through Wolf Steel or from the 

corresponding supplier listed below:

note:

If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate 

constructions such as a chimney as part of the vent system is not permitted.

This template must be used in conjunction with templates 7.1.1 or 7.1.2, depending on 

termination shape (i.e. round, or round and square). See appropriate templates folder. 

If approved for use with a power vent kit, state: “This appliance is certifi ed for use with a 

power vent kit. Contact your local authorized dealer for more information.”

If not, cover with a white box.

DRAFT

Use a firestop when penetrating interior walls, floor or ceiling.

A terminal shall not terminate directly above a sidewalk or paved driveway which is located between 

two single family dwellings and serves both dwellings. Local codes or regulations may require different 

clearances.

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or American Metal Amerivent venting components. 

Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for 

either systems are set out in this manual and must be adhered to.

30 1/2" 

(77.5cm)

16" (40.6cm)

min.

Summary of Contents for CDVS600-1NA

Page 1: ...cannot reach your gas supplier call the re department Installation and service must be performed by a quali ed installer service agency or the supplier This appliance may be installed in an aftermarke...

Page 2: ...m touching hot surfaces Even after the appliance is off it will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect...

Page 3: ...and repair should be done by a qualified service person It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean For outdoor products only this...

Page 4: ...gas installation 29 4 6 natural vent specifics model CS600 1 29 4 6 1 chimney installation 29 4 6 2 installing natural vent 30 4 6 3 natural vent 30 4 6 4 combustion air 30 4 6 5 adding vent sections...

Page 5: ...e 4 500ft 1371m and in the absence of specific recommendations from the local authority having jurisdiction the certified high altitude input rating shall be reduced at the rate of 4 for each ad ditio...

Page 6: ...system at test pressures equal to or less than 1 2 psig 35 mb When installed with a blower or fan the junction box must be electrically connected and grounded in accordance with local codes In the abs...

Page 7: ...re 13 w c P Pression au Collecteur 10 d une colonne d eau P Pression d Alimentation Min 11 d une colonne d eau P Pression d Alimentation Max 13 d une colonne d eau P Pression d alimentation maximale n...

Page 8: ...ard to release The door may now be safely removed by swinging the bottom out and lifting it off SHIPPINGBRACKET LATCH The top casting is not fastened to the stove assembly It simply sits on the stove...

Page 9: ...tion and avoids perfor mance or condensation concerns that may occur in tightly constructed homes particularly those in cold climates For optimum flame appearance and appliance performance keep the ve...

Page 10: ...the appliance follow the venting instructions exactly A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both d...

Page 11: ...nting model CDVS600 1 20 ft 6m max 12 305mm min to grade 24 610mm min regardless of horizontal vent length Max horizontal run 34 86 4cm max 29 73 7cm min 59 1 2 151 1cm min plus rise 24 61cm max 24 61...

Page 12: ...n is 10 3m for a fireplace and 8 2m for a stove An insulation sleeve is illustrated in the top vent image below use only when supplied with the appliance The insulation sleeve is not required with a s...

Page 13: ...learance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without openings Q 3 0 9m 3 0 9m See chart for wider wall dimensions R 6 1 8m 6 1 8m See ch...

Page 14: ...zontal run Horizontal run vertical rise to maximum of 40 feet 12 2m Horizontal run vertical rise to maximum of 40 feet 12 2m Vertical Termination 10 2 REAR EXIT Horizontal Termination Vertical Termina...

Page 15: ...HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in feet HO offset factor 03 total degrees of offset 135 in feet VT combined vertical vent lengths in feet 12...

Page 16: ...both formulas are met this vent configuration is acceptable 0 5 1 5 15 4 6 20 6 1 8 3 2 5 4 2 1 3 12 5 3 8 1 6 5 4 8 1 5 12 3 3 8 2 0 6 The shaded area within the lines represents acceptable values fo...

Page 17: ...40 feet 12 2m Example V1 3 ft 0 9m V2 8 ft 2 4m VT V1 V2 3 ft 0 9m 8 ft 2 4m 11 ft 3 4m H1 2 5 ft 0 8m H2 2 ft 0 6m HR H1 H2 2 5ft 0 8m 2 ft 0 6m 4 5 ft 1 4m HO 03 two 90 elbows 90 03 180 90 5 4 ft 1...

Page 18: ...figurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 9 FT 2 7m V2 6 FT 1 8m VT V1 V2 9FT 2 7m 6FT 1 8m 15FT 4 6m H1 3 FT...

Page 19: ...eet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4FT 1 2m 1 5FT 0 5m 5 5 FT 1 7m H1 2 FT 0 6m H2 1 FT 0 3m H3 1 FT 0 3m H4 1 5 FT 0 5m HR H1 H2 H3 H4 2FT 0 6m 1FT 0 3m 1FT 0 3m 1 5FT 0 5m 5 5 FT...

Page 20: ...9 HT VT 14 2 For vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5...

Page 21: ...0 8 1 FT 2 5m HT HR HO 8FT 2 4m 8 1FT 2 5m 16 1FT 4 9m HT VT 16 1FT 4 9m 4 5FT 1 4m 20 6FT 6 3m Formula 1 HT 3 5 VT 3 5 VT 3FT 0 9m x 4 5FT 1 4m 13 5 FT 4 1m 16 1FT 4 9m 13 5 FT 4 1m Since this formul...

Page 22: ...ifice supplied In order to access the orifice the log support secured by two screws must be removed Care should be taken not to damage the manifold gas pipe When removing the orifice using a socket wr...

Page 23: ...e and proper operation of the appliance follow the venting instructions exactly The appliance exhaust flue collar must be sealed using Mill Pac All exhaust and intake vent pipe joints must be sealed u...

Page 24: ...roof pitches are available from your authorized dealer distributor See the accessories section to order specific kits required A Determine the air terminal location cut and frame a square opening as i...

Page 25: ...ing not supplied D If more vent pipe needs to be used to reach the fireplace couple them together as illustrated The vent system must be supported approximately every 3 feet 0 9m for both vertical and...

Page 26: ...shing over the air terminal connector leaving a min 3 4 19mm of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles...

Page 27: ...ound the inside of the air intake collar Pull the adjustable pipe a minimum 2 50 8mm into the air intake collar 19 2 INSERT IMAGE HERE note Always finish vent system installation with the appliance ve...

Page 28: ...ion instructions Different manufacturer s venting components must not be combined Once the preferred manufacturer s appliance adaptor has been attached the remainder of the system must be that of the...

Page 29: ...out the connector it is designed to accept a 3 8 9 5mm gas supply The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance Connect the gas supply in accordanc...

Page 30: ...ld of the adapter base and push the crimped edge into the appliance flue collar F Connect the upper wire terminals to the spill switch G Disconnect the wire leads to on off switch see wiring diagram s...

Page 31: ...e chimney extends more than 5ft 1 5m above the roof it must be secured using a roof brace or guide wires A raincap must be installed to avoid internal damage and corrosion 3 FT 1m MIN 3 FT 1m MIN 10 F...

Page 32: ...from the shingles above and to the sides of the chimney Place the flashing over the chimney pipe and slide underneath the sides and upper edge of the shingles Ensure that the chimney pipe is properly...

Page 33: ...k of burns from the hot viewing glass is provided with the appliance and shall be installed A Remove the safety barrier by lifting up slightly swing out bottom then lower screen Remove and discard pla...

Page 34: ...ollowed in order to not damage the compo nents 1 2 B Remove securing bolts on cast front located behind either side on the top using a 10mm wrench not supplied C Tilt top of cast front forward and lif...

Page 35: ...r scratch Do not operate appliance with glass removed cracked broken or scratched NOTE If gap adjustment is required between cast front and side tighten or loosen wing nut screws located be hind eithe...

Page 36: ...the gas and disconnect the electrical power supply from the appliance B Open the cast front to easily access the control panel assembly Open control panel C Locate the battery housing inside the valve...

Page 37: ...our pigments burn in during the heat activated curing process POSITIONING THE LOGS IMPROPERLY WILL CAUSE FLAME IMPINGEMENT AND CARBONING The notch in log 5 should be pressed down onto the skewering pi...

Page 38: ...pplied and place as illustrated 45 5 INSERT IMAGE HERE 5 7 logo placement 5 8 switch and bracket installation 1 2 3 CONNECT THE TWO WIRES TO THE SWITCH TERMINALS 1 2 3 CONNECT THE TWO WIRES TO THE SWI...

Page 39: ...e that the on off switch wires pass through the appropriate slot located on either side of the blower housing F Remove the 2 screws from the side of the blower housing that you want the switch to be l...

Page 40: ...use any other type of battery pack note BATTERY HOLDER GAS VALVE PILOT ASSEMBLY IGNITION MODULE PILOT GAS LINE I S AC ADAPTOR BATTERY RELAY WIRE HARNESS MAIN BURNER SWITCH JUNCTION BOX NOTE PLUGTHE 3...

Page 41: ...match does not stay lit turn the unit off and check for vent blockage or restriction If necessary consult with a qualified inspector 8 1 operating instructions The on off switch is located on the back...

Page 42: ...AY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE INITIAL LIGHTING OF THE PILOT AND MAIN BURNERS MUST BE DONE WITH THE GLASS DOOR OFF DO NOT CONNECT VALVE OR WALL SWITCH TO ELECTRICITY...

Page 43: ...pressure can be checked by turning screw A counter clockwise 2 or 3 turns and then placing pressure gauge tubing over the test point Gauge should read as described on the chart below Check pressure wi...

Page 44: ...ctions are included with the kit 9 3 flame characteristics It s important to periodically perform a visual check of the pilot and burner flames Compare them to the illustration provided If any flames...

Page 45: ...e burner 5 If your appliance is equipped with a safety barrier cleaning may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 6 If your appliance...

Page 46: ...d be performed by a qualified service technician The firebox becomes very hot during operation Let the appliance cool completely or wear heat resistant gloves before conducting service Never vacuum ho...

Page 47: ...r warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appli...

Page 48: ...et W660 0009 On Off switch W135 0802 Top casting Metallic Black GL 646 Log set 10 13 12 10 11 Stocked Yes Yes Yes W135 0802N Top casting Majolica Brown 13 Yes 8 W010 3296 Safety barrier assembly W135...

Page 49: ...98 PILOT BRACKET W010 3968 PILOT ASSEMBLY NG W456 0052 BURNER ORIFICE 52 NG W725 0062 ELECTRONIC IGNITION VALVE NG W725 0041 GAS VALVE W707 0024 TRANSFORMER W190 0072 ELEC IGNITION ASSEMBLY W432 0078...

Page 50: ...t number Description 1 2 3 4 Ref No Stocked Stocked Part number Description GS 64KT Blower kit F45 F60 Handheld remote control GDS819KT GDS819KT GS831K Trivet black 1 8 4 8 5 8 6 8 7 GDSLL KT Leg leve...

Page 51: ...y Verify that the incoming gas line and ball valve is Open Verify that the inlet pressure reading is within the acceptable limits Inlet pressures must not exceed 14 w c 34mb Out of propane gas Fill th...

Page 52: ...he glass may become permanenttly marked Flames are very ag gressive Door is ajar Tighten door clamps if applicable Venting action is too great Restrict vent exit with restrictor plate See restricting...

Page 53: ...h as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused b...

Page 54: ...6 01 22 EN 54 service history 15 0 service history Appliance Service History This appliance must be serviced annually depending on usage Date Dealer Name Service Technician Name Service Performed Spec...

Page 55: ...EN W415 4084 A 06 01 22 55 notes 29 1...

Page 56: ...Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 7200 Route Transcanadienne Montr al Qu bec Canada H4T 1A3 P 1 866 820 8686...

Page 57: ...nou le fournisseur Cet appareil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si les r glements locaux le permettent Cet appareil doit tre utilis uniquement avec le type d...

Page 58: ...ts et loin des meubles et des rideaux Les meubles ou autres objets doivent tre gard s une distance d au moins 4 pieds 1 22m du devant de l appareil Assurez vous de disposer de mesures de s curit ad qu...

Page 59: ...on devraient tre effectu es par un technicien qualifi Il est imp ratif que les compartiments de contr le le br leur et les passages de circulation d air soient gard s propres afin de fourni une combus...

Page 60: ...areil mod le CDVS600 1 83 4 3 terminaison verticale travers une chemin e existante 84 4 4 installation dans une maison mobile mod le CDVS600 1 85 4 5 branchement du gaz 85 4 6 sp cification pour le ti...

Page 61: ...permanence dans les endroits o les codes locaux ne l interdisent pas vacuation arri re Pour les installations vacuation arri re qui se terminent horizontale ment et ne comportent pas de conduits d ve...

Page 62: ...es locaux En l absence de codes locaux utilisez la version courante du Code Canadien de l lectricit CSA C22 1 au Canada ou le National Electrical Code ANSI NFPA 70 aux tats Unis Dans le cas o le souff...

Page 63: ...X C t s X Arri re X Dessus du conduit d vent X C t s et dessous du conduit d vent X Profondeur d encastr une face X Tablette X de l ouverture de l appareil WARNING Do not add any material to the appl...

Page 64: ...s vers l avant pour ouvrir La porte peut maintenant tre enlev e en toute s curit en tirant sur le bas et en la soulevant LOQUET SUPPORTDETRANSPORT Le dessus du po le n est pas fix l appareil Il repose...

Page 65: ...a ture RTV ou d un ruban d aluminium appropri qui couvre toute la circonf rence de chaque joint dans le syst me de ventilation Cela garantira les meilleures performances dans chaque application et vit...

Page 66: ...re deux maisons unifamiliales et servant aux deux maisons Les codes ou r glementations locaux peuvent exiger des d gagements diff rents Ne laissez pas la gaine flexible se tasser contre les courses ho...

Page 67: ...m MAX 12 305mm MINIMUM AU NIVEAU DU SOL 24 610mm MINIMUM IND PENDAMMENT DE LA LONGUEUR D VENT HORIZONTAL COURSE HORIZONTALE MAXIMALE 34 86 4cm max 29 73 7cm min 59 1 2 151 1cm min plus l l vation 24 6...

Page 68: ...une po le Un manchon isolant est illustr dans l illustration ci dessous de l vacuation sur le sessus utiliser seulement lorsqu ils sont fournis avec l appareil Un manchon isolant n est pas requis avec...

Page 69: ...ur les dimensions d un mur plus large R 6 1 8m 6 1 8m Voir la tableau pour les dimensions d un mur plus profond La terminaison ne doit pas tre install e sur quelconque mur ayant une ouverture entre la...

Page 70: ...se verticale jusqu un maximum de 40 12 2m La course horizontale la course verticale jusqu un maximum de 40 12 2m Terminaison verticale 10 2 VACUATION L ARRI RE Terminaison Horizontale Terminaison Vert...

Page 71: ...facteur de la valeur d une d viation 0 03 du total des degr s de d viation 90 en pieds HO facteur de la valeur d une d viation 0 03 total des degr s de d viation 135 en pieds VT longueur des courses...

Page 72: ...5PI 1 5m 8PI 2 4m HO 03 two 90 elbows 90 03 180 90 2 7PI 0 8m HT HR HO 8PI 2 4m 2 7PI 0 8m 10 7PI 3 3m HT VT 10 7PI 3 3m 6PI 1 8m 16 7PI 5 1m Formule 1 HT 4 2 VT 4 2 VT 4 2PI 1 3m x 6PI 1 8m 25 2PI 7...

Page 73: ...e 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 3 pi 0 9m V2 8 pi 2 4m VT V1 V2 3 pi 0 9m 8 pi 2 4m 11 pi 3 4m H1 2 5 pi 0 8m H2 2 pi 0 6m HR H1 H2 2 5 pi 0 8m 2 pi 0 6m 4 5 pi 1 4m HO 0 03 deux 9...

Page 74: ...es valeurs acceptables pour HT et VT Lorsque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1...

Page 75: ...u un coude de 90 les formules suivantes s appliquent Formule 1 HT 3 5VT Formule 2 HT VT 24 75 pieds 7 5m Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI 0 5m 5 5 PI 1 7m H1 2 PI 0 6m H2 1...

Page 76: ...eptables pour HT et VT Lorsque les configurations de l vacuation exigent plus que z ro coude de 90 vacuation sur le dessus ou un coude de 90 vacuation l arri re les formules suivantes s appliquent For...

Page 77: ...HO 0 03 quatre coudes 90 90 0 03 360 90 8 1 PI 2 5m HT HR HO 8PI 2 4m 8 1PI 2 5m 16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3 PI 0 9m x 4 5 PI 1 4m 13 5 PI 4 1m 16 1P...

Page 78: ...torde ou ne se plie 3 0 pr paratifs pour l installation mod le CDVS600 1 3 1 remplacement de l injecteur du br leur 3 2 modification d vacuation sur le dessus vacuation l arri re Afin de convertir le...

Page 79: ...07 non fourni l exception du raccordement du conduit d vacuation la buse de l appareil qui doit tre scell avec le scellant Mill Pac Si vous utilisez des colliers pour tuyau pour raccorder les composan...

Page 80: ...ure de l espaceur coupe feu de fa on ce l cran protecteur couvre le haut du conduit d vent l int rieur de l ouverture Assurez vous que l espaceur coupe feu et l cran protecteur conservent le d gagemen...

Page 81: ...t autour et placez un espaceur coupe feu par dessus le protecteur de conduit d vacuation pour emp cher l arriv e d air froid dans la pi ce ou autour de l appareil Assurez vous que l espaceur coupe feu...

Page 82: ...fixez la au mur ext rieur et rendez la tanche en la scellant avec du calfeutrage non fourni D Si plus de sections de gaine doivent tre utilis es pour atteindre l appareil raccordez les ensemble tel q...

Page 83: ...une vent de 8 10 ou 8 11 D Faites passer le montage du connecteur de terminaison gaines flexibles travers le toit La terminaison doit tre verticale et d aplomb Fixez le connecteur de terminaison au su...

Page 84: ...reil est con u pour tre raccord un syst me d vent flexible colin aire de 3 7 6cm en aluminium se prolongeant sur toute la longueur de la chemin e de ma onnerie Les conduits flexibles s adaptent tous l...

Page 85: ...dimensions Lorsque le branchement est termin tous les raccords de gaz doivent se trouver l int rieur de l appareil foyer de gaz seulement Les pressions lev es endommageront la soupape L alimentation...

Page 86: ...in e peuvent tre utilis s avec cet appareil Toutes les courses horizontales doivent avoir une l vation minimale de 1 4 6 4mm par pied 0 3m VENT DE TYPE A CHEMIN E POUR COMBUSTION AU BOIS ET RACCORD D...

Page 87: ...la buse de l appareil F Branchez les connecteurs l interrupteur d coulement G D branchez les fils de l interrupteur marche arr t voir la section SCH MA DE C BLAGE et rebranchez les l extr mit des fil...

Page 88: ...5m elle devra tre fix e au toit avec un support de toit ou des brides de s curit Un chapeau de chemin e devra tre install afin d viter des dommages internes et la corrosion 3 PI 1m MIN 3 PI 1m MIN 10...

Page 89: ...evez les clous des bardeaux sur le dessus et les c t s de la chemin e Placez le solin par dessus le tuyau d vacuation et glissez le sous les c t s et le bord sup rieur des bardeaux Assurez vous que le...

Page 90: ...protection vers l appareil et fixez sous la coul e haut C Faites basculer l inf rieure de l cran de protection en position et inf rieure ce qui permet aux pinces de fond pour reposer sur l ouverture...

Page 91: ...F Soulevez la porte vers l haut en loignant du bord sup rieur et retirez la en glisser sous les dispositifs de retenue sup rieurs REMARQUE Lors du retrait de la porte vitr e de simples instructions do...

Page 92: ...de remplacement est remplac compl te telle que fournie par le fabricant de l appareil 5 4 installation de bo tier de piles 5 5 remplacement de la vitre de porte A Coupez l approvisionnement en gaz et...

Page 93: ...i tu e sur le poteau de chenet tel qu illustr afin d emp cher la b che de bouger 5 1 4 2 3 Placez l encoche de la b che 6 contre le poteau du chenet Placez le bas de la b che 7 contre le poteau le plu...

Page 94: ...dorsal du logo fourni et positionnez le de fa on camoufler les trous 5 8 installation de l interrupteur et du support 1 2 3 RELIEZ LES DEUX FILS AUX BORNES DE L INTERRUPTEUR 1 2 3 RELIEZ LES DEUX FILS...

Page 95: ...pteur marche arr t passent travers la fente appropri e situ e sur l un ou l autre c t du bo tier de la soufflerie F Retirez les 2 vis du c t du bo tier de la soufflerie sur lequel vous voulez installe...

Page 96: ...de gaz l alimentation lectrique 110 V AVERTISSEMENT SAUVEGARDEDE PILES I S ADAPTEUR HARNAIS DE FILS MAIN BURNER SWITCH 1 4 3 16 3 8 1 2 9 5mm 12 7mm LA FLAMME DOIT ENVELOPPER LA PARTIE SUP RIEURE DE L...

Page 97: ...ayez nouveau Si l allumette ne reste pas allum e teignez l appareil et v rifiez s il n y aurait pas un blocage ou une obstruction dans l vacuation Si n cessaire consultez un inspecteur qualifi 8 1 ins...

Page 98: ...IRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE INITIAL LIGHTING OF THE PILOT AND MAIN BURNERS MUST BE DONE WITH THE GLASS DOOR OFF DO NOT CONNECT VALVE OR WALL SWI...

Page 99: ...PPER LA PARTIE SUP RIEURE DE LA SONDE DE FLAMME DE 3 8 9 5mm 1 2 12 7mm LA SONDE DE FLAMME 3 8 1 2 9 5mm 12 7mm VEILLEUSE Pour v rifier la pression d arriv e tournez la vis A vers la gauche deux trois...

Page 100: ...thermocouple thermopile 3 8 1 2 9 5mm 12 7mm La flamme doit envelopper la thermocouple et thermopile de 3 8 1 2 9 5mm 12 7mm SIT MILLIVOLT 3 8 1 2 9 5mm 12 7mm Flame must envelop upper 3 8 to 1 2 12...

Page 101: ...eigne le br leur 5 Si votre appareil est fourni avec une cran de protection le nettoyage peut tre n cessaire en raison d un exc s de poussi re peluches des tapis animaux etc utilisez un l attachement...

Page 102: ...de flamme l aide d une morceau de laine d acier ou un tampon r curage Scotch BriteMD afin de retirer toute trace d oxydation Nettoyez l assemblage du pilote l aide d un aspirateur muni d une brosse s...

Page 103: ...cement de pi ce sous garantie une photocopie de la facture originale sera requise afin de pouvoir honorer la demande Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et...

Page 104: ...us en fonte noir m tallique GL 646 Ensemble de b ches 10 13 12 10 11 En stock Oui Oui Oui W135 0802N Dessus en fonte brun majolique 13 Oui W010 3296 Barri re de protection 9 W135 0803N Fa ade en fonte...

Page 105: ...LOT BRACKET W010 3968 PILOT ASSEMBLY NG W456 0052 BURNER ORIFICE 52 NG W725 0062 ELECTRONIC IGNITION VALVE NG W725 0041 GAS VALVE W707 0024 TRANSFORMER W190 0072 ELEC IGNITION ASSEMBLY W432 0078 3 8 M...

Page 106: ...F60 GDS819KT GDS819KT Panneaux d coratifs simili briques en fini pierre de sable GS831K Trivet noir 1 8 4 8 5 8 6 8 7 GDSLL KT 8 2 8 3 5 6 7 Ces articles peut diff rer de celle illustr Soufflerie T l...

Page 107: ...et 2 8 volts C A Syst me de d pannage piles s il y a panne de courant V rifiez les piles Une connexion desserr e ou causant un court circuit Retirez et r installez le harnais de fils qui se branche d...

Page 108: ...e mise la terre entre l assemblage de la veilleuse et la soupape de gaz V rifiez si le harnais de fils est solidement branch au module V rifiez si l isolateur de c ramique autour de la sonde est craqu...

Page 109: ...ls que les ventilateurs d vacuation les fournaises les s cheuses de linge etc Tous dommages caus s a l appareil la chambre de combustion l changeur de chaleur aux garnitures de laiton ou autres compos...

Page 110: ...FR historique d entretien Historique de service de l appareil Cet appareil doit tre entretenu annuellement selon son usage Date D taillant Nom du Technicien Travail Effectu Probl mes Particuliers 15...

Page 111: ...W415 4084 A 06 01 22 111 notes FR 29 1...

Page 112: ...Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 7200 Route Transcanadienne Montr al Qu bec Canada H4T 1A3 P 1 866 820 8686...

Reviews: