Continental Fireplaces CDCS600-P Installation And Operation Instructions Manual Download Page 6

6

W415-0162 / E / 03.05.04

Use only Wolf Steel or Simpson Dura-Vent Model DV-GS
venting components. Minimum and maximum vent lengths,
for both horizontal and vertical installations, and air termi-
nal locations for either system are set out in this manual
and must be adhered to. For Simpson Dura-Vent, follow
the installation procedure provided with the venting com-
ponents. Both Wolf Steel and Simpson Dura-Vent venting
components may have a 0" rise per foot on horizontal runs.

When using Wolf Steel venting components, use only the
following vent kits: 

WALL TERMINAL KIT GD175 

(7-1/2' of

venting included), or 

1/12 TO 7/12 PITCH ROOF TERMINAL

KIT GD110

,

8/12 TO  12/12 ROOF TERMINAL KIT GD111

,

FLAT ROOF TERMINAL KIT GD112

or

STOVE PERISCOPE

KIT GD180 

(for wall penetration below grade) in conjunc-

tion with the appropriate venting components.

For optimum perform-
ance, it is recom-
mended that all hori-
zontal runs have a mini-
mum ¼ inch rise per
foot.

These vent kits allow for either
horizontal or vertical venting of
the stove.  T h e   m a x i m u m
number of 4" flexible
connections is two horizontally
or three  vertically (excluding
the stove and the air terminal
connections).
When terminating vertically, the minimum vertical rise is
34 inches   above the stove and the maximum vertical rise
is 40 feet.

FIGURE 4.

Deviation from the minimum vertical vent length can cre-
ate difficulty in burner start-up and/or carboning.
Use an adjustable pipe as the final length of rigid piping
to the stove for ease of installation.

For optimum flame appearance and stove performance,
keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify that it
is unobstructed and undamaged.
The maximum horizontal run is 34 inches with a 90

o

 elbow

located 29" above the stove. 

FIGURE 5.

The maximum horizontal run with a 57 inch vertical rise
immediately above the stove is 20 feet 

. FIGURES 6a & b.

IF VERTICAL RISES GREATER THAN 57 INCHES ARE NECES-

SARY, THE INCREASED RISE MUST BE DEDUCTED FROM THE

MAXIMUM HORIZONTAL RUN.

FIGS 6a-b

FIGURE 5

HORIZONTAL RUN NOT TO
EXCEED VERTICAL RISE

Use the chart on this page to calculate horizontal runs for
vertical rises between 29 and 57 inches. When calculating
maximum run lengths, include 5 feet for each 90°  or 45°
elbow.
(DO NOT INCLUDE  THE FIRST  ELBOW DIRECTLY OFF
THE UNIT.)

FIGURE 4

R E Q U I R E D
V E R T I C A L
R I S E   F R O M
F I R E P L A C E
TO FIRST EL-
B O W   I N
INCHES

FIGURE 7

CALCULATED HORIZONTAL  VENT RUN IN FEET

DIRECT VENT SPECIFICS - MODEL CDVS600

VENTING LENGTHS &

AIR TERMINAL LOCATIONS

Summary of Contents for CDCS600-P

Page 1: ...ller service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOU...

Page 2: ...he same room as the stove Due to high temperatures the stove should be located out of traffic and away from furniture and draperies Clothing or other flammable material should not be placed on or near...

Page 3: ...orkmanship and material for life subject to the following conditions During the first 10 years WOLF STEEL Ltd will replace or repair the defective parts at our option free of charge From 10 years to l...

Page 4: ...installation of a fireplace insert or gas log The appliance off valve must be a T handle gas cock The flexible connector must not be longer than 36 inches The appliance is not approved for installati...

Page 5: ...forsafeoperation Useafirestop when penetrating interior walls floor or ceiling Provide adequate ventilation and combustion air Provide adequate accessibility clearance for servicing and operating the...

Page 6: ...ertical rise is 34 inches above the stove and the maximum vertical rise is 40 feet FIGURE 4 Deviation from the minimum vertical vent length can cre ate difficulty in burner start up and or carboning U...

Page 7: ...7 W415 0162 E 03 05 04 FIGURE 8...

Page 8: ...ns and elbows must be sub tracted from this maximum vertical length The maximum allowable horizontal run that B can be is 40 ft maximum vertical run length 11 ft through the roof vertical rise A 10 ft...

Page 9: ...off Lift the gasket off Unscrew the 4 screws securing the 4 collar and its gasket in place and remove it and the knock out from the rear panel Remove the 7 and 4 covers and gaskets from the back Posit...

Page 10: ...aulking not supplied to the framework or to the shield plate in the case of a finished wall and secure the shield through the opening to the interior wall The final location of the vent pipe shield sh...

Page 11: ...ent non combustible strapping to maintain the 1 clearance from combustibles FIGURE 23 FIGURE 24 This application occurs when venting through a roof Installation kits for vari ous roof pitches are avai...

Page 12: ...the caulking Tighten to ensure that a weather tight seal between the air terminal and the collar is achieved Attach the other storm collar centered between the air intake and air exhaust slots onto th...

Page 13: ...cept a standard matte black 7 stove pipe and the Con tinental decorative brass band standard with the GS 150KT Both are available from your Continental dealer Attach the B Vent label shown below in th...

Page 14: ...r 1 2 type L copper tubing with a shut off valve to the stove 2 Seal and tighten the gas line securely to the flex connec tor DO NOT KINK FLEXIBLE CONNECTOR 3 Check for gas leaks by brushing on a soap...

Page 15: ...front out of its retainers located at either side on the top Figure 37b 4 Open the valve control cover Pull the latch handles forward to release Figure 37c The door may now be safely removed by swing...

Page 16: ...d at the end of the grate as shown to prevent it from rocking Position the notch located in log 6 against the grate post 1 4 2 3 LOG PLACEMENT 5 6 Place the bottom of log 7 against the right outermost...

Page 17: ...ill quickly transform to a dull black finish during the curing process FIGURE 40 OPERATION MAINTENANCE When lit for the first time the fireplace will emit a slight odour for a few hours This is a norm...

Page 18: ...FF unless the knob is depressed 2 Push in gas control knob slightly and turn clock wise to off Do not force TURN OFF THE GAS AND UNPLUG ELECTRICAL POWER BEFORE SERVICING THE STOVE CAUTION Label all wi...

Page 19: ...clockwise direction to reduce the gas flow Remove the 2 screws securing the log support bracket Natural gas models have air shutters set to 0 375 open 3 8 Propane models have air shutters set to 0 31...

Page 20: ...ER 37 GD222 TERMINAL ASSEMBLY 38 BM67ADJ 30 TO 53 ADJUSTABLE PIPE 7 DIA 39 W500 0077 FIRESTOP WALL PLATE 40 W020 0032 HARDWARE 41 BRTC7 BRASS TRIM COLLAR 42 BM6724 24 STOVE PIPE 7 DIAMETER 43 W010 030...

Page 21: ...21 W415 0162 E 03 05 04 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 22: ...ing no gas to main burner gas knob is on HI wall switch thermostat is on Main burner orifice is plugged Faulty thermopile Faulty themostat or switch remove stoppage in orifice replace connect a jumper...

Page 23: ...free of holes and well sealed at all joints check that minimum rise per foot has been adhered to for any horizontal venting Air shutter has become blocked ensure air shutter opening is free of lint or...

Page 24: ...24 W415 0162 E 03 05 04...

Reviews: