background image

10

W415-0120 / F / 10.25.11

FLAME MUST ENVELOP 
UPPER 3/8” TO 1/2” OF 
THERMOPILE

4 SCREWS

ACCESS DOOR

4 SCREWS

FIGURE 12

FIGURE 11

FIGURE 12

FIGURE 13

FIGURE 14

PILOT SCREW

BLOWER SYSTEM

BLOWER REPLACEMENT INSTRUCTIONS

ADJUSTMENTS

PILOT BURNER ADJUSTMENT

VENTURI ADJUSTMENT

Drywall dust will penetrate into blower bearings causing ir-
repairable damage and must be prevented from coming into 
contact with the blower or its compartment.
Any damage resulting from this condition is not covered by 
the warranty policy.

The CONTINENTAL gas fi replace insert comes standard with 
a blower, a heat sensor, variable on/off speed control and a 
power cord. Because the blower is thermally activated, when 
turned on, it will automatically start approximately 15 minutes 
after lighting the fi replace and will run for approximately 30 
minutes after the fi replace has been turned off. Use of the fan 
increases the output of heat. Air, drawn in through the lower 
louvre access door, is driven up the back of the fi rebox, and 
exhausted as hot air between the upper louvres.

 

 • Turn off the gas and electric power to the unit.
 • Remove the upper glass bracket. Loosen the lower glass 

bracket and remove the glass.

 • Remove the logs.
 • Remove the burner assembly. 
 • Remove the 

eight

 screws holding the access door in place 

on the control assembly (located at the back of the burner 
support).

 • Remove the four screws holding the blower duct and slide 

it forward from beneath the burner support.   

 • Disconnect the electrical connectors at the blower.
 • Remove the blower.

1.

 

Remove the pilot adjustment cap.

2.

 

Adjust the pilot screw to provide properly sized fl ame. 

 

3.

 

Replace the adjustment cap.

Natural gas models have air shutters set at 1/16 (.063") inch 
open. Propane gas models have air shutters set at  3/8 (.375) 
inch open. Closing the air shutter will cause a more yellow 
fl ame, but can lead to carboning. Opening the air shutter will 
cause a more blue fl ame, but can cause fl ame lifting from 
the burner ports. The fl ame may not appear yellow immedi-
ately; allow 15 to 30 minutes for the fi nal fl ame colour to be 
established. 

AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY 

A QUALIFIED GAS INSTALLER!

  

Summary of Contents for CBI 360-N

Page 1: ...mmediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be perfor...

Page 2: ...r other flammable material should not be placed on or near the fireplace Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace It is imperative that the co...

Page 3: ...material for life subject to the following conditions During the first 10 years CONTINEN TAL will replace or repair the defective parts at our option free of charge From 10 years to life CONTINENTAL...

Page 4: ...ing of the fireplace This insert must be recessed into a vented noncombustible woodburning fireplace prefabricated or masonry only The minimum fireplace size in which the heater is to be installed is...

Page 5: ...installing the insert Remove the existing fireplace damper or lock into an open position Using screws attach the fireplace warning tag W385 0199 to the inside of the firebox of the fireplace into whic...

Page 6: ...ded maximum lead length depends on wire size WIRE SIZE MAX LENGTH 14gauge 100 feet 16gauge 60 feet 18gauge 40 feet Attach the two leads to terminals 1 and 3 located on the gas valve Do not connect the...

Page 7: ...ntered evenly above the pilot assembly 3 While supporting the back log to prevent it from fall ing forward set the three smaller logs into the pockets and grooves of the front and back logs respective...

Page 8: ...LE DEATH A CHECK FOR CORRECT VENTING ACTION MUST BE MADE BEFORE THE INSTALLED INSERT IS LEFT WITH THE CUSTOMER Test after installing the unit into a vented non combustible fireplace in the following m...

Page 9: ...g the pilot with the push button ignitor Keep the knob fully depressed for one 1 minute then release If the pilot does not continue to burn repeat steps 3 through 7 9 With the pilot lit turn the gas k...

Page 10: ...up the back of the firebox and exhausted as hot air between the upper louvres Turn off the gas and electric power to the unit Remove the upper glass bracket Loosen the lower glass bracket and remove t...

Page 11: ...XE 6 PORCELAIN FLASHING KIT ALMOND 26 GI 909K6 DELUXE 6 PORCELAIN FLASHING KIT BLACK 26 GI 909F6 DELUXE 6 PORCELAIN FLASHING KIT GREEN FOR OPENINGS SMALLER THAN 30 X 48 26 GI 900B9 DELUXE 9 FLASHING K...

Page 12: ...12 W415 0120 F 10 25 11 20 12 9 15 26 39 38 16 14 1 2 5 6 4 3 21 13 10 11 27 33 34 37 35 36...

Page 13: ...he valve call the gas distributor turn on all gas appliances and see if pilot flame flutters di minishes or extinguishes especially when main burners ignite Monitor supply pressure check if supply pip...

Page 14: ...ney blockage check that chimney is installed to building code room is in negative pressure increase fresh air supply Fireplace is spilling reverse Remote wall switch is in off position main burner com...

Page 15: ...15 W415 0120 F 10 25 11 43 1...

Page 16: ...16 W415 0120 F 10 25 11 44 1 NOTES...

Reviews: