CONTINENTAL CONTROL SYSTEMS WattNode WNC-3D-240-MB Installation Manual Download Page 8

8

3.3.2  Line Wiring

● 

Always turn off power

 before connecting the line voltage inputs to the meter.

● 

For the line voltage wires, CCS recommends 16 to 12 AWG stranded wire, type THHN, MTW, 
or THWN, 600 V.

 

Do not place more than one voltage wire in a screw terminal; use separate wire nuts or termi-
nal blocks if needed.

● 

Verify that the line voltages are in the range of the line-to-line 

Ø-Ø

 and line-to-neutral 

Ø-

N

 

values printed in the white box on the front label.

The screw terminals handle wire up to 12 AWG. Connect each voltage line to the green terminal 
block as shown in 

Figure 1

 above. After the voltage lines have been connected, make sure both 

terminal blocks are fully seated in the meter.

Connect each line voltage to the appropriate phase; also connect ground and neutral (if appli-
cable). The neutral connection “

N

“ is not required on delta models (3D-240, 3D-400, and 3D-480), 

but we recommend connecting it to ground if neutral is not present.

When power is first applied, check that the LEDs behave normally. If you see LEDs flashing red-
green-red-green (see 

Figure 7

), the line voltage is too high for this model, so disconnect the power 

immediately!

3.3.3  Grounding

The WattNode uses a plastic enclosure, insulation, and internal isolation barriers instead of 
protective earthing. The ground terminal on the green screw terminal block is a functional ground, 
designed to improve the measurement accuracy and noise immunity. If necessary, this terminal 
may be left disconnected on wye models (

-

3Y

).

3.4  Connect Current Transformers

To meet the UL listing requirements, the WattNode meter may only be used with UL Listed CTs 
with a 333 mVac output or the following UL Recognized current transformer models, which all gen-
erate 333 millivolts AC at rated current. See the current transformer datasheets for CT ratings.

ACT-0750-

xxx

CTL-1250-

xxx

CTM-0360-

xxx

CTS-0750-

xxx

CTS-1250-

xxx

CTS-2000-

xxxx

CTB-

WxL

-

xxxx

CTT-0300-

xxx

CTT-0500-

xxx

CTT-0750-

xxx

CTT-1000-

xxx

CTT-1250-

xxx

CTRC-

yyyyy

-

xxxx

 

xxx

” indicates the full scale current rating.

 

WxL

” indicates the opening width (

W

) and leg length (

L

) in inches.

 

dddd

” indicates the opening diameter of the loop for flexible Rogowski CTs.

 

yyyyy

” indicates the opening size in mils (thousandths of inches).

See the web article 

https://ctlsys.com/selecting_current_transformers/

 for information on 

selecting appropriate current transformers (CTs).

 

Do not

 use ratio or current output CTs such as 1 amp or 5 amp output models!

 

See the CT datasheets for the maximum input current ratings.

 

Be careful to match the CTs with the voltage phases. Make sure the 

Ø

A CT

 is measuring the 

current on the same phase as the 

Ø

voltage input, and the same for phases B and C. Use the 

supplied colored labels or colored tape to identify the CT leads.

 

To minimize current measurement noise, avoid extending the CT wires, especially in noisy 
environments. If it is necessary to extend the wires, use twisted pair wire 22 to 14 AWG, rated 
for 300 V or 600 V (not less than the service voltage) and shielded if possible.

 

Find the source arrow or label “THIS SIDE TOWARD SOURCE” on the CT and face/point 
toward the source of current.

 

OPTIONAL: if you see spurious readings on unused phases, jumper the unused CT inputs: 
for each unused CT, connect a short wire from the terminal marked with a white dot to the 
terminal marked with a black dot.

Summary of Contents for WattNode WNC-3D-240-MB

Page 1: ...anual WattNode Modbus Models WattNode Revenue for Modbus Models WNC 3Y 208 MB RWNC 3Y 208 MB WNC 3Y 400 MB RWNC 3Y 400 MB WNC 3Y 480 MB RWNC 3Y 480 MB WNC 3Y 600 MB RWNC 3Y 600 MB WNC 3D 240 MB RWNC 3...

Page 2: ...ansformers 8 3 5 Connect the Output Signals 9 4 Operation 10 4 1 Initial Configuration 10 4 2 Power Status LEDs 10 4 3 Modbus Communication LED 12 4 4 Monitoring 12 4 5 Maintenance and Repair 12 5 Spe...

Page 3: ...round should be connected to earth ground if possible but is not required for safety grounding UL Listing mark for U S A and Canada FCC Mark This logo indicates compliance with part 15 of the FCC rule...

Page 4: ...eutral n a 166 276 3D 240 A and B 1 Phase 2 Wire 240V no neutral n a 166 276 3D 240 A and B 1 Phase 3 Wire 120V 240V with neutral 96 138 166 276 3Y 208 N and A 3D 240 A and B 3 Phase 3 Wire Delta 208V...

Page 5: ...W ATT N ODE Neutral Line 2 2 2 Single Phase Two Wire No Neutral This circuit occurs in residential commonly 120 240 Vac and some commercial applications The meter is powered from the A and B terminal...

Page 6: ...lta service to be labeled as the C phase instead of the B phase The WattNode meter will work correctly with the high leg connected to A B or C See the web article https ctlsys com support four_wire_de...

Page 7: ...led in an electrical service panel or an enclosure Do not use the meter as a drilling guide the drill chuck can damage the screw terminals and metal shavings may fall into the connectors The meter has...

Page 8: ...attNode meter may only be used with UL Listed CTs with a 333 mVac output or the following UL Recognized current transformer models which all gen erate 333 millivolts AC at rated current See the curren...

Page 9: ...white dot on the label and the black wire aligned with the black dot Note the order in which the phases are connected as the line voltage phases must match the current phases for accurate power measur...

Page 10: ...ground at one end RS 485 wiring is daisy chained between meters with up to 64 devices per subnet X C B A WATTNODE WATTNODE A B C RS 485 X C B A 4 Operation 4 1 Initial Configuration Generally the net...

Page 11: ...ses can cause this Red Off Red Off Red Off C 4 2 6 Overvoltage Warning The following indicates that the line voltage is too high for this model Disconnect power immedi ately Check the line voltages an...

Page 12: ...les 4 5 Maintenance and Repair The WattNode meter requires no maintenance It is not user serviceable and there are no replace able parts except the pluggable screw terminals There are no diagnostic te...

Page 13: ...ttNode and void the warranty Over Current Limit 120 of rated current Exceeding 120 of rated current will not harm the WattNode meter but the current and power will not be measured accurately Maximum S...

Page 14: ...vice Type CAT III Voltage Rating 3Y 208 3D 240 240 Vac 3Y 400 3D 400 400 Vac 3Y 480 3D 480 480 Vac 3Y 600 600 Vac Table 4 WattNode CAT III Ratings Current Transformer Inputs Nominal Input Voltage At C...

Page 15: ...r a Class B digital device pursuant to part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any...

Page 16: ...on of Liability In no event shall CCS be liable for any indirect special incidental punitive or consequen tial damages of any kind or nature arising out of the sale or use of its products whether such...

Reviews: