CONTINENTAL CONTROL SYSTEMS WattNode WNC-3D-240-MB Installation Manual Download Page 7

7

3  Installation

3.1  Installation Checklist

See the sections referenced below for installation details.

 

Turn off power

 before making line voltage connections. 

 

Mount the WattNode meter (see 

3.2

).

 

Connect circuit breakers or fuses and disconnects (se

3.3.1

).

 

Connect the line voltage wires to the meter’s green terminal block (se

3.3.2

).

 

Mount the CTs around the line conductors. Make sure the CTs face the 

source

 (see 

3.4

).

 

Connect the twisted white and black wires from the CTs to the black terminal block on the 
meter, matching the wire colors to the white and black dots on the meter label (see 

3.4.1

).

 

Check that the CT phases match the line voltage phases (see 

3.4

).

 

Record the CT rated current for each meter, because it will be required during commission-
ing.

 

Connect the output terminals of the WattNode meter to the monitoring equipment (see 

3.5

).

 

Check that all the wires are securely installed in the terminal blocks by tugging on each wire.

 

Turn on power to the meter.

 

Verify that the LEDs indicate correct operation (se

4.2

4.3

).

3.2  Mounting

 

Protect the meter from temperatures below –40°C (–40°F) or above 75°C (167°F), excessive 
moisture, dust, salt spray, or other contamination, using a NEMA rated enclosure if necessary. 
The meter requires an environment no worse than pollution degree 2 (normally only non-con-
ductive pollution; occasionally, a temporary conductivity caused by condensation).

 

The meter must be installed in an electrical service panel or an enclosure.

 

Do not

 use the meter as a drilling guide; the drill chuck can damage the screw terminals and 

metal shavings may fall into the connectors.

The meter has two mounting holes spaced 5.375 in. (137 mm) apart (center-to-center). These 
mounting holes are normally obscured by the detachable screw terminals. Remove the screw 
terminals to mark the hole positions and mount the meter.

Self-tapping #8 sheet metal screws are included. Don’t over-tighten the screws, as long-term 
stress on the case can cause cracking.

3.3  Connect Voltage Terminals

3.3.1  Circuit Protection

The WattNode meter is considered “permanently connected equipment” and requires a disconnect 
means (circuit breaker, switch, or disconnect) and overcurrent protection (fuse or circuit breaker).

The meter only draws 10-30 milliamps, so the rating of any disconnect switches, fuses, and/or 
circuit breakers is determined by the wire gauge, the mains voltage, and the current interrupting 
rating required.

 

The disconnect or circuit breaker must be clearly marked, suitably located, and easily reached.

 

Use circuit breakers or fuses rated for 20 amps or less.

 

Use ganged circuit breakers when monitoring more than one line voltage.

 

The circuit breakers or fuses must protect the mains terminals labeled 

Ø

A

Ø

B

, and 

Ø

C

. In the 

rare cases where neutral has overcurrent protection, then the overcurrent protection device 
must interrupt both neutral and the ungrounded conductors simultaneously.

 

The circuit protection / disconnect system must meet IEC 60947-1 and IEC 60947-3, as well as 
all national and local electrical codes.

Summary of Contents for WattNode WNC-3D-240-MB

Page 1: ...anual WattNode Modbus Models WattNode Revenue for Modbus Models WNC 3Y 208 MB RWNC 3Y 208 MB WNC 3Y 400 MB RWNC 3Y 400 MB WNC 3Y 480 MB RWNC 3Y 480 MB WNC 3Y 600 MB RWNC 3Y 600 MB WNC 3D 240 MB RWNC 3...

Page 2: ...ansformers 8 3 5 Connect the Output Signals 9 4 Operation 10 4 1 Initial Configuration 10 4 2 Power Status LEDs 10 4 3 Modbus Communication LED 12 4 4 Monitoring 12 4 5 Maintenance and Repair 12 5 Spe...

Page 3: ...round should be connected to earth ground if possible but is not required for safety grounding UL Listing mark for U S A and Canada FCC Mark This logo indicates compliance with part 15 of the FCC rule...

Page 4: ...eutral n a 166 276 3D 240 A and B 1 Phase 2 Wire 240V no neutral n a 166 276 3D 240 A and B 1 Phase 3 Wire 120V 240V with neutral 96 138 166 276 3Y 208 N and A 3D 240 A and B 3 Phase 3 Wire Delta 208V...

Page 5: ...W ATT N ODE Neutral Line 2 2 2 Single Phase Two Wire No Neutral This circuit occurs in residential commonly 120 240 Vac and some commercial applications The meter is powered from the A and B terminal...

Page 6: ...lta service to be labeled as the C phase instead of the B phase The WattNode meter will work correctly with the high leg connected to A B or C See the web article https ctlsys com support four_wire_de...

Page 7: ...led in an electrical service panel or an enclosure Do not use the meter as a drilling guide the drill chuck can damage the screw terminals and metal shavings may fall into the connectors The meter has...

Page 8: ...attNode meter may only be used with UL Listed CTs with a 333 mVac output or the following UL Recognized current transformer models which all gen erate 333 millivolts AC at rated current See the curren...

Page 9: ...white dot on the label and the black wire aligned with the black dot Note the order in which the phases are connected as the line voltage phases must match the current phases for accurate power measur...

Page 10: ...ground at one end RS 485 wiring is daisy chained between meters with up to 64 devices per subnet X C B A WATTNODE WATTNODE A B C RS 485 X C B A 4 Operation 4 1 Initial Configuration Generally the net...

Page 11: ...ses can cause this Red Off Red Off Red Off C 4 2 6 Overvoltage Warning The following indicates that the line voltage is too high for this model Disconnect power immedi ately Check the line voltages an...

Page 12: ...les 4 5 Maintenance and Repair The WattNode meter requires no maintenance It is not user serviceable and there are no replace able parts except the pluggable screw terminals There are no diagnostic te...

Page 13: ...ttNode and void the warranty Over Current Limit 120 of rated current Exceeding 120 of rated current will not harm the WattNode meter but the current and power will not be measured accurately Maximum S...

Page 14: ...vice Type CAT III Voltage Rating 3Y 208 3D 240 240 Vac 3Y 400 3D 400 400 Vac 3Y 480 3D 480 480 Vac 3Y 600 600 Vac Table 4 WattNode CAT III Ratings Current Transformer Inputs Nominal Input Voltage At C...

Page 15: ...r a Class B digital device pursuant to part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any...

Page 16: ...on of Liability In no event shall CCS be liable for any indirect special incidental punitive or consequen tial damages of any kind or nature arising out of the sale or use of its products whether such...

Reviews: