CONTINENTAL CONTROL SYSTEMS WattNode BACnet RWNC-3D-240-BN Installation Manual Download Page 5

5

Table 1

 above lists the WattNode models and common circuit types. In the “Electrical Service 

Types” column, when two voltages are listed with a slash between them, they indicate the line-to-

neutral / line-to-line voltages. The “Line-to-Neutral” and “Line-to-Line” columns show the operating 

ranges for the WattNode meters. “non-N.A.” refers to non-North American electrical services.
Connect the line voltages to the meter inputs as shown in the following figures for each service 

type. See 

Figure 1

 above for an overview.

2.2.1  Single-Phase Two-Wire with Neutral

This is a common residential and branch circuit connection. You may monitor up to three single-

phase circuits with one meter by also using the 

Ø

B

 and 

Ø

C

 inputs.

Ø

B

Ø

C

N

Ø

A

W

ATT

N

ODE

®

Ø

B

CT

Ø

A

CT

Ø

C

CT

L1

Neutral

Earth

2.2.2  Single-Phase Two-Wire No Neutral

This circuit occurs in residential (commonly 120/240 Vac) and some commercial applications. 

The meter is powered from the 

Ø

A

 and 

Ø

B

 terminals. We recommend connecting the 

N

 terminal 

to ground to provide a clean voltage reference for the measurement circuitry (no current will flow 

through this terminal).

Ø

B

Ø

C

N

Ø

A

W

ATT

N

ODE

®

Ø

B

CT

Ø

A

CT

Ø

C

CT

L2

L1

Earth

2.2.3  Single-Phase Three-Wire with Neutral

This is a common North American residential service at 120/240 Vac.

Ø

B

Ø

C

N

Ø

A

W

ATT

N

ODE

®

Ø

B

CT

Ø

A

CT

Ø

C

CT

L2

L1

Neutral

Earth

2.2.4  Three-Phase Three-Wire Delta No Neutral

This is common in commercial and industrial settings. In some cases, the service may be four-wire 

wye while the load is three wire (no neutral). 
Occasionally, a load will only be connected to two of the three lines (say 

L1

 and 

L2

). For this case, 

connect the two active lines to the 

Ø

A

 and 

Ø

B

 terminals and connect two CTs for the two lines.

Summary of Contents for WattNode BACnet RWNC-3D-240-BN

Page 1: ...anual WattNode BACnet Models WattNode Revenue for BACnet Models WNC 3Y 208 BN RWNC 3Y 208 BN WNC 3Y 400 BN RWNC 3Y 400 BN WNC 3Y 480 BN RWNC 3Y 480 BN WNC 3Y 600 BN RWNC 3Y 600 BN WNC 3D 240 BN RWNC 3...

Page 2: ...ct the Output Signals 9 3 6 Connect Thermistor 10 4 Operation 11 4 1 Initial Configuration 11 4 2 Power Status LEDs 11 4 3 Communication LED 12 4 4 Monitoring 12 4 5 Maintenance and Repair 12 5 Specif...

Page 3: ...Hazard from Dangerous High Voltage Functional ground should be connected to earth ground if possible but is not required for safety grounding UL Listing mark for U S A and Canada FCC Mark This logo i...

Page 4: ...neutral n a 166 276 3D 240 A and B 1 Phase 2 Wire 240V no neutral n a 166 276 3D 240 A and B 1 Phase 3 Wire 120V 240V with neutral 96 138 166 276 3Y 208 N and A 3D 240 A and B 3 Phase 3 Wire Delta 208...

Page 5: ...T L1 Neutral Earth 2 2 2 Single Phase Two Wire No Neutral This circuit occurs in residential commonly 120 240 Vac and some commercial applications The meter is powered from the A and B terminals We re...

Page 6: ...e phase delta service to be labeled as the C phase instead of the B phase The WattNode meter will work correctly with the high leg connected to A B or C See the web article https ctlsys com support fo...

Page 7: ...lled in an electrical service panel or an enclosure Do not use the meter as a drilling guide the drill chuck can damage the screw terminals and metal shavings may fall into the connectors The meter ha...

Page 8: ...onnect Current Transformers To meet the UL listing requirements the WattNode meter may only be used with UL Listed CTs with a 333 mVac output or the following UL Recognized current transformer models...

Page 9: ...pped the measured power will be negative The status LEDs indicate negative measured power by flashing red When installing WattNode Revenue models be sure to only use IEEE C57 13 class 0 6 current tran...

Page 10: ...tances and when using termination and biasing resistors If you have any questions consult the Operating and Reference Guide Be sure to connect the A B and C common terminals The X terminal is normally...

Page 11: ...eter displays the following startup sequence whenever power is first applied 1 0sec 1 0sec 1 0sec Green Yellow Red Green Yellow Red Green Yellow Red C B A 4 2 2 Positive Power Any phase with the LEDs...

Page 12: ...w Solid yellow indicates that this meter believes it is the sole master device on the network It will scan continuously for other devices until another device is found 4 4 Monitoring WattNode BACnet m...

Page 13: ...trical Meter Service Type Nominal Vac Line to Neutral Nominal Vac Line to Line Phases Wires 3Y 208 120 208 240 1 or 3 2 4 3Y 400 230 400 1 or 3 2 4 3Y 480 277 480 1 or 3 2 4 3Y 600 347 600 1 or 3 2 4...

Page 14: ...Examples are measurements on distribution boards circuit breakers wiring including cables bus bars junction boxes switches socket outlets in the fixed installation and equipment for industrial use an...

Page 15: ...onducted RF Immunity EN 61000 4 6 Voltage Dips Interrupts EN 61000 4 11 Emissions FCC Part 15 Class B EN 55022 1994 Class B 5 7 Environmental Operating Temperature 40 C to 75 C 40 F to 167 F Altitude...

Page 16: ...s the right to substitute functionally equivalent new or serviceable used parts This warranty covers only defects arising under normal use and does not include malfunctions or failures resulting from...

Reviews: