Contemporary Controls BASstat BAST-221C-B2 User Manual Download Page 20

 

UM-15090000-AA8 

 

Page 

19

 

 

 

Occupancy Setting 

There are three ways to define thermostat occupancy state. 

NOTE:

 Occupancy will be detected by 

ESI contact by default.   

  Energy Savings Input (ESI) This is a dry contact input meant for communication from a 

customer supplied occupancy sensor. (default)  

  Occupancy status (occupied/unoccupied) can be set by a BACnet supervisor using 

writable object ESI Contact Definition [BV14]. “0” for occupied, and “1” for unoccupied. 

E12/AV18 must be set with a value of 64 (disabled) in advance (E12/AV18 is set as 0 by 

default) 

  User control of occupancy state is allowed from the SET button if E12/ AV18 Lock has the 

ESI Contact disabled. Pressing the SET button and UP/DOWN buttons will toggle the 

occupancy state. Press SET button to confirm. The SET button can work in conjunction 

with BACnet occupancy Command [BV14] on last-write-wins basis. The SET button could 

be locked to limit user control (use Lock [AV18] BACnet object or (LOC) engineering 

menu item to lock SET button). In this case only the BACnet supervisor can set 

occupancy states.  

  Occupancy Status [BI0] is a read-only BACnet object indicating current occupancy state -

“0” for occupied, and “1” for unoccupied. (AV18 is set as 0 by default). 

  When in unoccupied state, a Moon (   ) icon will be displayed on the LCD and the 

thermostat will change the set-point temperatures to the Unoccupied Cool and 

Unoccupied Heat setpoints [AV8 – 9]. When the state changes back to occupied, the 

thermostat will return to the occupied set-point values for Cooling and Heating 

Temperature Setpoint [AV0, AV3] and a sunlight icon (

) will be displayed to indicate 

occupied state on LCD. 

 

4.3.  Engineering Mode Menu 

Thermostat configuration can be performed using the engineering mode menu described below or 

BACnet objects using a BACnet client tool such as Contemporary Controls free BACnet Discovery 

Tool (BDT). It is highly suggested that engineering mode be operated by trained installers only 

because it is related to system parameters that will affect the control results. 

 

Operation of Engineering Menu 

 

  At power “ON”, press and hold both the UP and DOWN buttons simultaneously for 5 

seconds to enter Engineering Mode menu. 

  Press the UP or DOWN buttons to rotate through the menu items. The last item loops 

back to first item at the end of items in menu. Press the MODE button to enter a submenu 

item. 

  Press the UP or DOWN button to change the setting in the submenu item or hold to speed 

up setting value change. Press the MODE button to confirm the setting and return to 

menu item selection. If no button is pressed for 10 seconds, the display will return to the 

menu item selection. After another 10 seconds, the display will return back to User mode. 

Settings are not changed unless confirmed using the MODE button. 

Summary of Contents for BASstat BAST-221C-B2

Page 1: ...BAST 221C CH B2 BACnet Communicating Thermostat for Multi Stage Heating Cooling Ventilation BASstat Multi Stage Thermostat User Manual UM 15090000 AA8...

Page 2: ...ut the prior written permission of Contemporary Control Systems Inc Tel 1 630 963 7070 2431 Curtiss Street Fax 1 630 963 0109 Downers Grove Illinois 60515 USA E mail info ccontrols com Contemporary Co...

Page 3: ...Electromagnetic Compatibility 8 2 7 Mechanical all dimensions are in mm 9 3 Installation 11 3 1 Terminal Block Pin Assignments 11 3 2 Limited Power Source 11 3 3 Power Supply Precautions 12 3 4 Wirin...

Page 4: ...BACnet object no control action is taken based on humidity Both models have five relays two for stage heating two for stage cooling and one for fan The BASstat is configurable locally using the Engine...

Page 5: ...n metering Full configurable control parameters such as deadband proportional gain integral rate stage trip points and cycle time Adjustable minimum maximum set point ranges Three options for temperat...

Page 6: ...UM 15090000 AA8 Page 5 1 2 Product Image and Main Features BASstat 221C B2...

Page 7: ...UM 15090000 AA8 Page 6 BASstat 221CH B2...

Page 8: ...g 1 Heating 2 Cooling 1 Cooling 2 Fan Contact Rating SPST 2A at 30 VAC with inductive load Minimum contact life 100 000 cycles 2 3 Communication Item Description Protocol Compliance BACnet MS TP with...

Page 9: ...rd Test Method Description EN 61000 6 2 IEC 61000 4 2 Electrostatic Discharge Immunity EN 61000 6 2 IEC 61000 4 3 Radiated Radio Frequency Electromagnetic Field Immunity EN 61000 6 2 IEC 61000 4 4 Ele...

Page 10: ...l dimensions are in mm Wiring 14 to 22 AWG wires or 1 5mm2 wires Mounts directly onto wall panel standard 65 65mm junction box hole pitch 60 mm or standard 2 4 inch vertical junction box hole pitch 83...

Page 11: ...UM 15090000 AA8 Page 10...

Page 12: ...ice on the MS TP bus a termination resistor 120 must be applied across pins 16 and 17 of the input terminal The remote sensor input RS is at terminals 13 and 14 The remote occupancy ESI input is a dry...

Page 13: ...f wave devices have a common secondary connection called COMMON LO or GROUND Connect the HOT side of the secondary to the 24 VAC high side input on the BASstat and the LO side to 24 VAC common WARNING...

Page 14: ...rmostat outputs This will disable control ON OFF control can be accomplished over BACnet as well 2 At power ON press any button to start the User Mode operation Press the MODE button to toggle between...

Page 15: ...to a desired value from BACnet supervisor 3 Mode Select Select the working mode Cooling Heating or Ventilating After pressing the MODE button press the UP DOWN button to rotate the selections Depende...

Page 16: ...type automatically The default control type is set to 2 stage Heating and Cooling with Auto Changeover This is the most common control type 2 stage Heating and Cooling with Manual Changeover can be u...

Page 17: ...net object and Engineering Menu object but are not available for use Fan Output in Heat Mode By default the BASstat thermostat will not provide Fan output signal when in Heat Mode since most HVAC comf...

Page 18: ...g can be selected by pressing the MODE button or using a BACnet command to object MSV1 In application where user control needs to be limited the lock button function can be used to disable MODE button...

Page 19: ...g its state The default setting is 3 minutes Maximum cycles per hour will count the number of cycles in an hour When the cycle count reaches the maximum cycles in an hour it won t allow additional cyc...

Page 20: ...d the thermostat will change the set point temperatures to the Unoccupied Cool and Unoccupied Heat setpoints AV8 9 When the state changes back to occupied the thermostat will return to the occupied se...

Page 21: ...MODE button Alternately pressing no buttons for 10 seconds will return the thermostat back to User mode Engineering Menu Flow Chart Press Up down for over 5s MODE MODE E01 E01 Setting _ MODE MODE E02...

Page 22: ...8 0 0 1 C F E11 diFF Stage differential 0 5 0 1 1 0 1 0 0 1 1 8 0 1 C F E12 LOC Bit Definition 0 MODE button dec 1 1 Down buttons dec 2 2 Up button dec 4 3 FAN SPEED button dec 8 4 Power On Off button...

Page 23: ...0 3 0 0 1 0 stop 1 low E20 Pct Output Percentage not used 0 0 100 0 0 100 1 E21 Baud BACnet MS TP Baud rate 38 4 9 6kbps 19 2kbps 38 4kbps 57 6kbps 76 8kbps 38 4 9 6kbps 19 2kbps 38 4kbps 57 6kbps 76...

Page 24: ...Hour Extension Time not used E41 VALL Input Low Value of Valve Feedback not used E42 VALH Input High Value of Valve Feedback not used E43 AI L Analog Input Low Value not used E44 AI H Analog Input Hig...

Page 25: ...utton dec 16 5 SET or button dec 32 6 ESI contact detection dec 64 7 Door Window contact detection unused unused 8 Modification for communication parameters dec 256 i e baud rate MAC addr device inst...

Page 26: ...s is required to distinguish it from other MS TP devices on the bus default MAC address 1 When more than one BASstat is installed at the same time their MAC addresses must be configured prior to commu...

Page 27: ...able Writable Range BACnet Thermostat Device 100001 Model Name R Application Software Version R Object Identifier R Object Name R W 32 characters max Max_Master R W 1 127 Object name Type Instance Rea...

Page 28: ...g Temperature Setpoint AV 0 R W Cooling Temperature Set Point C 0 500 0 0 50 0 F 320 1220 32 0 122 0 F Space Temperature Via BACnet AV 1 R W BACnet Assigned Current Temperature 999 9999 99 9 999 9 F T...

Page 29: ...ure C 0 500 0 0 50 0 F 320 1220 32 0 122 0 F Object name Type Instance Readable Writable Description Range and Definition High Setpoint Limit AV 14 R W High Limit for Set Point Temperature C 0 500 0 0...

Page 30: ...15 reserved unused Bit Value 0 Unlock enable 1 Lock disable Examples add dec values to lock multiples For more details see Lock Function Setup and Examples section of this manual Control Out Percenta...

Page 31: ...trol Minimum Output AV 33 R W CO2 Control Minimum Output Percentage 0 20 After Hour Extension Time AV 34 R W After Hour Extension Run Time 5 20 0 5 2 0 Hour Input Low Value of Valve Feedback AV 35 R W...

Page 32: ...Closed 1 Door Window Open Cooling heating Status BI 2 R Status of Cooling Heating Control Output 0 Close Off 1 Open On Relay 1 Status BI 3 R Status of Relay 1 Cooling Stage 1 0 Off 1 On Relay 2 Statu...

Page 33: ...I1 Contact Definition this feature is model specific 0 N O 1 N C Cooling Direct Reverse Acting BV 1 R W Modulating Cooling Direct Reverse Signal Output 0 Direct 0 To10v 1 Reverse 10 To 0V Heating Dire...

Page 34: ...n Mode MSV 0 R W Fan Mode 1 Auto 2 Low 3 Med 4 Hi System Mode MSV 1 R W Working Mode Heat Cool or Ventilation 1 Cool Mode 2 Heat Mode 3 Ventilation Cool Mode 4 Ventilation Heat Mode Sleep MSV 2 R W Sl...

Page 35: ...anty period CC will at its option repair or replace the product at no charge The customer is however responsible for shipping the product CC assumes no responsibility for the product until it is recei...

Page 36: ...nd on our website www ccontrols com United States China United Kingdom Germany Contemporary Control Systems Inc Contemporary Controls Suzhou Co Ltd Contemporary Controls Ltd Contemporary Controls GmbH...

Reviews: