UM-15090000-AA8
Page
14
User Mode Thermostat Operation
#
Item
Description
Remarks
1
Normal Display
Display current room or set-point
temperature
Use the (
SP
) parameter in
the Engineering Menu or
[
MSV6
]
Display Option
for
BW2
or
[
MSV7
]
Display
Option
for B2 model to
choose Current room or Set-
point temperature on display.
2
Temperature
Setpoint
Setting using
Up/Down
Arrows
Set the desired temperature
The [
AV0
] / [
AV3
] Cool / Heat
Occupied and [
AV8
] / [
AV9
]
Unoccupied Cool / Heat
temperature setpoints BACnet
objects can be used to write or
force the setpoint to a desired
value from BACnet supervisor.
3
Mode Select
Select the working mode:
Cooling (
), Heating (
)
, or
Ventilating (
)
.
After pressing the MODE
button, press the UP/ DOWN
button to rotate the selections.
Dependent on Control Type.
4
Fan Auto/
Continuo
us
Change the Fan mode between
Auto or Continuous.
When AUTO is displayed, the
fan is handled automatically.
When AUTO is flashing, the
fan is working under a delay
timer. When FAN icon is
spinning but AUTO is not
displayed, the fan will run
continuously until commanded
off.
5
Occupancy
Setting
Press SET, Used UP and DOWN
arrows to toggle between the
Occupied and Unoccupied setting.
Use MODE or SET buttons to apply.
The SET button could be
locked for applications
forbidding user occupancy
state control.