Installation
—
CPS-PC341MB-ADSC1-9201 Reference Manual (Hardware)
—
65
—
Example of connecting to the LED
The corresponding LED lights up when you output "1" into the appropriate bit.
The corresponding LED turns off when you output "0" into the appropriate bit.
Connecting to an external device
Connecting the output to the sink output acceptable input
Connecting the output to the source acceptable input
CAUTION
Removing the connector plug by grasping the cable can break the wire. Always grasp the
connector to remove it.
Tightening torque of the supplied connector is described below.
DEGSON : 0.19 N·m, PHOENIX CONTACT, PTR MESSTECHNIK : 0.25 N·m
For wiring, strip off approximately 7mm (plus or minus 0.5mm) of the covered part of a cable
to connect with the connector.
About a caution mark on the product: Please use copper wires that tolerate the
temperature of 75 °C and higher.
Output pin (+)
LED
5.1kΩ
Output pin (-)
External power
supply
12 - 24 VDC
+
-
Th
is P
ro
du
ct
This Product
Output pin(-)
Output pin(+)
Sink output
acceptable input
External
power supply
Source output
acceptable input
This Product
Output pin(+)
Output pin(-)
External
power supply