Installation
—
CPS-MCS341-DS1-111, CPS-MCS341-DS1-131 Reference Manual (Hardware)
—
50
—
3.
Cable Connection
1.
Power
Power Cable
Use the power cable described below.
Cable
Twisted pair cable (when using a single wire, twist V+ wire and V- wire)
Cable Diameter
AWG20 - 16(0.5mm
2
- 1.25mm
2
)
Cable Length
Within 3 meters
*Refer to
in the
page 24
for details of the power connector and pin assignment.
FG Cable
Use the FG cable described below.
Applicable wire
AWG18 - 16(0.75mm
2
- 1.25mm
2
)
Specification of External Power Supply
This product is designed to operate at least with 30 - 90 watt power supply.
In addition, the power supply must fulfill the following requirements.
Rising time for
up to 24 voltage
2 milliseconds up to 30 milliseconds
Cable
Use copper wires that tolerate a temperature of 75 °C or higher.
Recommended power supply is the optional products of the CPS-PWD-30AW24-01 or CPS-PWD-
90AW24-01(CONTEC).
CAUTION
If the maximum output current of the external power supply is smaller than the maximum
consumption current of the product, the abnormal operations might occur due to the inrush
current at the start-up time or the load fluctuation. The aging external power supply could cause
a start-up failure.
ATTENTION
Si le courant de sortie maximum de l’alimentation externe est moindre que le courant maximum
absorbé par ce produit, il y a possibilité d’un dysfonctionnement en raison de l’appel de courant
au moment de la mise en route ou de la fluctuation de charge. Le vieillissement de l’alimentation
externe peut provoquer un défaillance au démarrage.
Summary of Contents for CONPROSYS CPS-MCS341-DS1-111
Page 70: ... 70 Index ...