6. System Reference
CNT16-8(FIT)GY, CNT16-8L(FIT)GY
59
CNT16-8L(FIT)GY
Table 6.3. Specifications
Item Specification
Counter input section
Channel count
8 (8 points/common)
Counting system
Up/down counting
Max. count
FFFFH (binary data)
Response frequency
10kHz (Max.)
Duty 50% (Max.)
Input format
Opto-isolated input (Compatible with both current sinking output and courrent
source output)
Input resistance
1.2k
Ω
Input ON /OFF current
3.8 mA(Min.) / 0.16 mA (Max.)
External circuit power
5 VDC (±10%)
(4 mA per channel)
Digital filter
0.25
μ
sec - 131.072
μ
sec
Interrupt
The interrupts for all eight channels are combined as a single interrupt output
signal. An interrupt is generated when a count carry-up occurs.
Common section
Interrupt level
Using CPU-SBxx(FIT)GY: IRQ 5, 7, or 9
Internal power consumption 5 VDC(±5%) 150 mA (Max.) *1
Allowable distance of signal
extension
Approx. 50m (depending on wiring environment)
Physical dimensions (mm)
25.2 (W) x 64.7 (D) x 94.0 (H) (exclusive of protrusions)
Weight of the module itself
100g
Module connection method
Stack connection by the connector that is provided with the side of module
Module installation method
One-touch connection to 35mm DIN rails
(standard connection mechanism provided in the system)
Applicable wire
AWG 28 - 16
Applicable plug
FRONT-MC 1,5/12-STF-3,81 (made by Phoenix Contact Corp.)
*1 The stack connector accepts currents of up to 3.0A (Max.).
Table 6.4. Installation Environment Requirements
Parameter Requirement
description
Operating temperature
0 - 50
°
C
Storage temperature
-10 - 60
°
C
Operating humidity
10 - 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
CAUTION
When connecting the Module to a controller module, the internal power consumption should be
taken into account. If the total current exceeds the capacity of the power supply unit, the integrity of
the operation cannot be guaranteed. For further details, please see the Controller Module manual.