background image

 

Ver.1.10 

  ADI16-4(FIT)GY   

  1   

 

F&eIt Series   

Isolated High-Resolution Analog Input Module 

ADI16-4(FIT)GY 

 

* Specifications, color and design of the products are subject to change 

without notice. 

 

 

Congratulations on your recent purchase of an Isolated Analog Input 

Module. 

The ADI16-4(FIT)GY can be connected to the F&eIT series of controller 

modules (such as the   

CPU-CAxx(FIT)GY and CPU-SBxx(FIT)GY) to construct a system. 

The isolation between external signals and the Controller Module 

permits the use of the Controller Module without compromising the 

communications features of the latter. 

 

 

* The contents in this document are subject to change without notice. 

* Visit the CONTEC website to check the latest details in the document. 

* The information in the data sheets is as of August 2018. 

 

 

Features

 

 

-  Bus-isolated analog input module providing high precision at a 

resolution of 16 bits. 

-  Selectable input ranges common to channels: Bipolar input from -10 

to +10 V and current input from 0 to 20 mA. 

-  Support for differential input, capable of accurate measurement of 

voltages over a distance from the signal source or with potential 

differences. 

-  A rotary switch allows you to set device IDs to help you keep track of 

device numbers. 

-  Flanged two-piece connector used to prevent disconnection from 

the connector on the controller module. 

-  Similar to other F&eIT series products, the system, in the module 

itself, incorporates a 35-mm DIN rail mounting mechanism as a 

standard item.    A connection to a controller module can be effected 

on a lateral, stack basis in a unique configuration, which permits a 

simple, smart system configuration without the need for a backplane 

board. 

 

 

Packing List 

 

Module[ADI16-4(FIT)GY] …1 
First Step Guide …1 
CD-ROM [F&eIT Series Setup Disk] *1…1 
Interface connector plug…1 
Warranty Certificate …1 
Serial number label …1 

*1 The CD-ROM contains various software and User’s Manual 

 

 

 

 

 

 

 

 

Specifications

 

 

Function specifications 

Item 

Specifications 

Voltage input 

Current input 

Analog input section 

 

Input format   

Bus-isolated voltage input 

Bus-isolated current input 

Input range   

Bipolar ±10V 

0 to 20mA 

Maximum input ratings 

±20V 

30mA 

Input impedance   

1M

(Min.) 

250

(Typ.) 

Input channel 

Differential input, 4 channels 

Resolution 

16-bit 

Non-linear error *1*3 

±8LSB(±0.012% of FSR) 

±20LSB (±0.030% of FSR) 

Conversion rate   

Number of conversion channels x 

10

µ

sec + 20

µ

sec 

Number of conversion channels x 

40

µ

sec + 20

µ

sec 

Data buffer   

64-Word 

Interrupt  

Either IRQ5 or IRQ7 or IRQ9 *2 

Internal sampling timer   

10

sec to 1,073,741,824

sec *2 

Common section 

 

Internal power consumption    5VDC±5%   300mA(Max.) 
Maximum distance of   

signal extension 

1.5m 

Physical dimensions (mm) 

25.2(W) x 64.7(D) x 94.0(H) (exclusive of protrusions) 

Weight (module itself) 

100g 

Module installation method  One-touch connection to 35mm DIN rails   

(standard connection mechanism provided in the system) 

Compatible wires 

AWG28 to 16  Cross-section 0.08 to 1.25mm 

Connectors 

FK- MC1.5/12-STF-3.81 plug (made by Phoenix Contact Corp.) Equivalent. 

3.81 mm-pitch, nominal current: 4A (Max.) 

*1  The non-linearity error means an error of approximately 0.1% occurs over the maximum range at 0

C   and 

50

C ambient temperature. 

*2   Available only when the ADI16-4(FIT)GYs connected to the CPU-SBxx(FIT)GY. 
*3    For this product, as the analog signal is input to A/D converter without being processed in order not make the 

frequency characteristics to deteriorate, if the connection cable is affected by noise, correct analog input may 
not be achieved. 

 

 

When connecting one of the modules to a controller module, the internal power consumption should be 
taken into account.    If the total current exceeds the capacity of the power supply unit, the integrity of the 
operation cannot be guaranteed.    For further details, please see the Controller Module manual. 

Depending upon the specific controller module that is used, some of the functions are not supported. 

 

Installation Environment Requirements 

Parameter 

Requirement description 

Operating temperature   

0 to 50

Storage temperature   

-10 to 60

Humidity 

10% to 90%RH (No condensation) 

Floating dust particles 

Not to be excessive 

Corrosive gases 

None 

 

 

 

 

CAUTION