Calibration Instruction

1 Calibration Instruction for Salwico ST400 H2S

5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C

3

6

You will get a confirmation message that
the detector has been disabled.
Press

Close

to continue.

7

NOTE!

For the following steps in the
zero calibration instruction
proceed to the Salwico ST400
detector.

1.3 Calibrating the sensor (Zero calibration)

1

Connect the Multi-meter (set to mA) as
shown in the picture.

2

Adjust with the “ZERO” potentiometer to
4,0 mA signal output.

1.4 Calibrating the sensor (Span calibration)

Verification of detector type 0-25 ppm or 0-30 ppm

NOTE!

The ST400 for H

2

S is available in two types.

Type 1: 0-25 PPM. mA-signal at 20 ppm = 16.8 mA.

Type 2: 0-30 PPM. mA-signal at 20 ppm = 14.6 mA.

To verify which type is in use, make a span calibration as below and verify the
display reading in the central cabinet.

If the readout at 14.6 mA is less than 20 PPM a calibration with 16.8 mA
set-point must be done.

Summary of Contents for Salwico ST400 H2S

Page 1: ...Salwico ST400 H2S CGD50 500 Calibration Instruction...

Page 2: ...to revision without notice due to continued progress in methodology design and manufacturing Consilium Building Safety AB assumes no legal responsibility for any error or damage resulting from the usa...

Page 3: ...ntrations H2S is a sticky gas and smells very distinctly from rotten eggs Consilium Replacement article number for ST400 H2S detectors is no 004462 S A new sensor is supplied without the metal housing...

Page 4: ...2 Prerequisites 1 Use the arrow keys on the control panel to manoeuvre through the different menus Press the right arrow key to access the menu tree 2 Scroll to 4 Gas Detectors and press Continue 3 S...

Page 5: ...ibration 1 Connect the Multi meter set to mA as shown in the picture 2 Adjust with the ZERO potentiometer to 4 0 mA signal output 1 4 Calibrating the sensor Span calibration Verification of detector t...

Page 6: ...When the reading is stabilized adjust the readout to 14 6 mA or 16 8 mA with the SPAN potentiometer NOTE Response can be estimated to several minutes in some cases If this reading cannot be reached th...

Page 7: ...Calibration Instruction 1 Calibration Instruction for Salwico ST400 H2S 5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C 5...

Page 8: ...logies for the marine oil and gas transport and building sectors Our commitment goes beyond the products We protect the lives of mothers and fathers sisters and brothers colleagues and friends With re...

Reviews: