Page 1: ...Salwico GD True IR Salwico GS5000 Calibration Instruction...
Page 2: ...o revision without notice due to continued progress in methodology design and manufacturing Consilium Building Safety AB assumes no legal responsibility for any error or damage resulting from the usag...
Page 3: ...nitial calibration allow the detector to stabilize for 30 minutes after applying power When in zero and span calibration mode the current output from the detector is inhibited default 2mA to avoid fal...
Page 4: ...f you are not in access level 3 or above You will be prompted to enter the access code for level 3 before you can continue 5 You have to confirm your selection before you can proceed NOTE The detector...
Page 5: ...g the sensor Span calibration 1 Use the arrow keys on the control panel to manoeuvre through the different menus Press the right arrow key to access the menu tree 2 Scroll to 4 Gas Detectors and press...
Page 6: ...to ensure that the gas reading is stabile 9 After the gas detector reading has stabilized press Calibrate 10 You will get a confirmation message that the detector has been successfully calibrated Pre...
Page 7: ...Calibration Instruction 1 Calibration Instruction for Salwico GD True IR 5103024_Salwico GD True IR_Calibration Instruction_I0_EN_2014_C 5...