1 Calibration Instruction for Salwico GD True IR
Calibration Instruction
4
5103024_Salwico GD True IR_Calibration Instruction_I0_EN_2014_C
6
Use the
and
keys to enter
calibration gas concentration that will be
used during the span calibration; the default
value will be half of the detector range.
Press
Continue
to proceed.
7
In the Span calibration menu you will be
able to see the real time value of the
detector.
8
Apply calibration gas to the detector.
Wait for a minimum of two minutes to
ensure that the gas reading is stabile.
9
After the gas detector reading has stabilized
press
Calibrate
.
10
You will get a confirmation message that
the detector has been successfully
calibrated.
Press
Close
to get back to menu
Gas
Detectors
.
11
Close all valves on the calibration test gas
and disconnect it from the detector.
The detector has now been
calibrated from the control
panel.
1.4 Reconnecting disabled detectors
All disablements in the Salwico GS5000 gas detection system are presented in the
disablements list. Any enablement is made from this list.
1
Scroll to
Menu » Disablements
.
2
Choose the detector you just disabled and press
Options
.
3
Select
Reconnect
and press
Continue
.