1 Calibration Instruction for Salwico GD True IR

Calibration Instruction

4

5103024_Salwico GD True IR_Calibration Instruction_I0_EN_2014_C

6

Use the

and

keys to enter

calibration gas concentration that will be
used during the span calibration; the default
value will be half of the detector range.
Press

Continue

to proceed.

7

In the Span calibration menu you will be
able to see the real time value of the
detector.

8

Apply calibration gas to the detector.
Wait for a minimum of two minutes to
ensure that the gas reading is stabile.

9

After the gas detector reading has stabilized
press

Calibrate

.

10

You will get a confirmation message that
the detector has been successfully
calibrated.
Press

Close

to get back to menu

Gas

Detectors

.

11

Close all valves on the calibration test gas
and disconnect it from the detector.

The detector has now been
calibrated from the control
panel.

1.4 Reconnecting disabled detectors

All disablements in the Salwico GS5000 gas detection system are presented in the
disablements list. Any enablement is made from this list.

1

Scroll to

Menu » Disablements

.

2

Choose the detector you just disabled and press

Options

.

3

Select

Reconnect

and press

Continue

.