8
Electrical Connections
Envirosun AS Installation Manual Rev1a PVNW.docx
Page 26
Figure 8.2.2 PM-600 Wiring Diagram
8.2.1
Controller Setting
It is not recommended that you alter the optimal factory settings or run the system
in manual for extended periods.
If there is a need to change a field you have noticed to be incorrect:
1.
Turn on the power supply and wait 15 seconds.
2.
Press and hold down Button 1 until “SEt” appears on the display screen.
3.
Using Buttons 1 & 2 to scroll, move up and down the channels until you reach the
one requiring amendment.
4.
Change the channel:
a.
Press Button 3. The “SEt” on the display will start to flash.
b. Using Buttons 1 & 2 to scroll, adjust the channel to the desired value.
c.
Save the channel setting by pressing Button 3. The “SEt” will return to
the steady state.
5.
Check all channels for conformity to the table, and change as required using the
same procedure.
6.
The controller will return to the main screen in 30 seconds once you stop pushing
buttons.
Field
Value
DO
6
DF
4
SX
70
CL
200
CX
190
CN
4
FN
3
MM
2
Table 8.2.1 Controller settings